22
Table 7 — Available Liquid Lift (ft)* — English
*Allows 7 psi drop for liquid line accessories with maximum charge.
†Saturated Condensing Temperature (entering) – Entering Air Tem-
perature (dry bulb)
q
F.
NOTES:
1.
Data based on 15 F subcooling.
2.
Subcooling = Saturated condensing temperature of refrigerant
– Actual temperature of refrigerant leaving the coil.
Table 8 — Available Liquid Lift (m)* — SI
*Allows 48 kPa drop for liquid line accessories with maximum
charge.
†Saturated Condensing Temperature (entering) – Entering Air Tem-
perature (dry bulb)
q
C.
NOTES:
1.
Data based on 8.3° C subcooling.
2.
Subcooling = Saturated condensing temperature of refrigerant
– Actual temperature of refrigerant leaving the coil.
UNIT
REFRIGERANT
R-410A
R-134a
Temperature Difference (F)†
20
30
20
30
09DPS018
75
75
60
45
09DPS020
50
35
09DPS030
45
30
09DPM035
55
40
09DPM040
50
35
09DPM050
50
35
09DPM060
45
30
09DPM065
55
40
09DPM075
50
35
09DPM085
50
35
09DPM095
50
35
09DPM115
50
35
09DPM130
50
35
UNIT
REFRIGERANT
R-410A
R-134a
Temperature Difference (C)†
11.1
16.6
11.1
16.6
09DPS018
23
23
18
14
09DPS020
15
11
09DPS030
14
9
09DPM035
17
12
09DPM040
15
11
09DPM050
15
11
09DPM060
14
9
09DPM065
17
12
09DPM075
15
11
09DPM085
15
11
09DPM095
15
11
09DPM115
15
11
09DPM130
15
11