Communications wiring
Fan Coil
CARRIER CORPORATION ©2020
Integration Guide
All rights reserved
12
Wire specifications
○
A dedicated 22 AWG shielded twisted pair wire (EIA 485)
○
Maximum wire length 2000 feet (610 meters) or 32 nodes
○
Devices should be daisy-chained and not star-wired
○
Attach the drain/shield wire to both ends of the network segment and through every controller
NOTE
Use the same polarity throughout the network segment.
7
Turn on the power for the Fan Coil by connecting power terminals.
Troubleshooting Modbus communication
The most common communication problems result from not properly following the configuration steps outlined
above in this manual. Review all of the steps and use the following list to check your settings.
Verify accuracy of the following:
Hardware settings
for Modbus (8 Data bits, No Parity, and 1 Stop bit):
•
Baud rate DIP switches 1 and 2
•
Protocol DIP switches 3 and 4
•
Jumper set to EIA-485
•
Proper connection wiring
•
Unique rotary address switches 1
–
99. If controllers have duplicate addresses, network communication can
be lost.
NOTES
•
If RX LED is solid, then the terminations are incorrect.
•
If the network has greater than 32 devices or exceeds 2,000 feet, a Repeater should be installed.
•
If a controller begins or ends a network segment, a terminating resistor may be needed.
•
The controller recognizes physical changes (DIP switches, rotary switches, and jumpers) upon power up.
Modbus Exception Codes that might be returned from this controller
Codes
Name
Description
01
Illegal Function
The Modbus function code used in the query is not
supported by the controller.
02
Illegal Data
Address
The register address used in the query is not supported
by the controller.
04
Slave Device
Failure
The Modbus Master has attempted to write to a non-
existent register or a read-only register in the
controller.