C.
Manufactured Housing
In Manufactured Housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric
heat be locked out at outdoor temperatures above 40 degrees F., except for a heat pump defrost cycle. Refer to Fig. 13 for typical low voltage wiring
with outdoor thermostat.
D.
Ground Connections
WARNING: According to NEC, ANSI/NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken
ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal
conduit when installed in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate
ground wire must be used. Failure to follow this warning could result in electric shock, fire, or death.
NOTE:
Use UL-listed conduit and conduit connector for connecting supply wire(s) to unit to obtain proper grounding. Grounding may also be
accomplished by using grounding lugs provided in control box.
E.
Minimum CFM and Motor Speed Selection
Units with or without electric heaters require a minimum CFM. Refer to the unit wiring label to ensure that the fan speed selected is not lower
than the minimum fan speed indicated.
Fan speed selection is done at the fan relay printed-circuit board. To change motor speeds, disconnect fan lead used on relay terminal (SPT) and
replace with motor speed tap desired. (See Fig. 16). Save insulating cap and place on motor lead removed from relay.
NOTE:
In low static applications, lower motor speed tap should be used to reduce possibility of water being blown off coil.
All units have 3 motor speed taps. Low speed (red) is designed for mismatch outdoor unit applications. Medium speed (blue) is designed for
straight matched operations. High speed (black) is used with high external static duct systems of straight matched systems.
Fig. 9—Wiring Layout Air Conditioning Unit
(Cooling Only)
A94058
R
G
W
Y
THERMOSTAT
RED
GRY
WHT
BLU
VIO
BRN
WHT
R
G
W
2
W
3
E
C
FAN COIL
(CONTROL)
C
Y
AIR COND.
Fig. 10—Wiring Layout Air Conditioning Unit
(Cooling and 1-Stage Heat)
A94059
R
G
W
Y
THERMOSTAT
R
G
W
2
W
3
E
C
FAN COIL
(CONTROL)
C
Y
AIR COND.
RED
GRY
WHT
WHT
BLU
VIO
BRN
—8—
→