Carrier FA4ANF Скачать руководство пользователя страница 33

NOTE:

If applied to two-speed unit, do not select continuous fan

as high since LO speed cooling will also run at HIGH airflow and
insufficient dehumidification may result.

Step 13—Troubleshooting PCB

Use Fig. 25 and 26 and Tables 7 and 8 as guides in troubleshooting
PCB unless otherwise noted.

IF FAN WILL NOT TURN ON FROM THERMOSTAT:

If There Is No High Voltage To Motor:

1. Check connection of 12-pin plug from heaters to receptacle.

This supplies power to transformer and motor. Be sure plug is
connected properly.

2. Check power leads L1 and L2. If these are not receiving

power, system cannot function.

If Motor Has High Voltage Applied To It:

1. Check low-voltage transformer leads (red and brown). Be sure

they are wired to correct locations. (See Fig. 24 and 26.)

2. Check low-voltage fuse shown in Fig. 24. If fuse is blown,

replace it. The transformer cannot supply power to board with
fuse blown or loose. If fuse blows when unit has power
applied to it, the system most likely has 1 of the following
problems:

a. Check control circuit for a short or miswiring problem.

b. The maximum load on transformer is 40 VA. If load on

transformer is excessive, the low-voltage 5-amp fuse will
blow to protect transformer. If load exceeds VA rating of
transformer, a larger VA rated transformer needs to be
installed.

c. Check sequencers for excessive current draw.

d. Check wiring of heaters. If a heater is miswired, fuse may

blow. If a heater is miswired, correct miswiring.

3. Check yellow and black wire connections on primary side of

transformer. If they are not connected properly, low-voltage
transformer cannot supply 24-v signal to energize fan motor.
If transformer is receiving correct primary voltage but is not
putting out correct secondary voltage, transformer needs to be
replaced.

IF ELECTRIC HEAT STAGES WILL NOT TURN ON BUT
FAN WILL TURN ON:

1. Check wiring of sequencers. Pay particular attention to high-

and low-voltage wiring of sequencers.

2. Check plug wiring to make sure that it is wired correctly.

3. Check voltage to sequencer. Sequencer number 1 receives a

24-vac signal. If it is receiving correct voltage, check to see if
sequencer is closing. If sequencer is not closing but is
receiving correct voltage, replace sequencer. If sequencer is
closing, check high-voltage wiring as discussed in items 1 and
2.

If Traces Are Overheated on Back of PCB:

Usually whenever there is a trace blown on PCB, it means either
there has been a high-voltage short or high voltage has been
applied to low-voltage circuit. This can be prevented by making
sure PCB is wired correctly before fan coil has power applied to it.

IF PCB FUSE KEEPS BLOWING:

When low-voltage fuse blows, it means transformer would have
blown if fuse had not been in circuit to protect it. The fuse usually
blows when there is a high current drawn on transformer, high
voltage applied to low-voltage circuit, or a direct secondary short.
When there is a high current drawn on transformer, it is most likely
because transformer has been shorted or system is trying to draw

more va than transformer rating allows. When fuse blows because
of high voltage, the system has mixed high- and low-voltage
signals.

1. Check transformer and thermostat wiring. (See Fig. 24 and

26.) Be sure transformer is not shorting out because thermostat
wires are miswired.

2. Check wiring of sequencers. (See Fig. 24 and 26.) Be sure

low-voltage and high-voltage wiring are connected to proper
sequencers.

3. Check VA draw on transformer. If VA draw is more than VA

rating of transformer, fuse will blow. If this is the case, replace
transformer with one that has a higher VA rating.

Step 14—Troubleshooting ICM2 Fan Motor

IF MOTOR DOES NOT RUN:

1. With power turned off, check all plugs and receptacles on

circuit board and at motor for any deformation that may cause
a bad connection. Be sure all plugs are placed fully seated.

2. Verify that there is approximately 230v.

3. Verify that there is a low-voltage control signal to motor. The

motor receives its control signals through the 12-pin motor
plug PL1. The voltage output of each pin in plug will be
different for each mode of operation. Table 9 lists circuit
board screw terminals that have 24 vac present (powered by
thermostat) and lists voltage that is present at each pin of
12-pin plug for each operating mode. Tests should be taken
between points listed and common (C screw terminal). If all
values of any 1 of operating modes check OK and motor fails
to run, then motor is defective and should be replaced.

IF MOTOR DOES NOT RUN SMOOTHLY:

First verify that the cause is not an out-of-balance or damaged
blower wheel. If it is not blower wheel, motor is defective and
should be replaced.

IF MOTOR SHAFT DOES NOT ROTATE SMOOTHLY:

When manually turning shaft of ICM, the shaft does not rotate
smoothly. The shaft has steps during rotation referred to as motor
cogging. The cogging is caused by permanent magnets passing
each pole of motor. However, shaft should not require excessive
force to turn. If shaft is VERY difficult to turn, motor control or
bearings have failed and motor must be replaced.

IF MOTOR DOES NOT STOP RUNNING

1. Check for good ground between motor ground lead and

transformer common lead.

2. If motor continues to run, remove all thermostat wires. If

motor stops, check thermostat wiring to thermostat or outdoor
unit for shorts or miswire.

Step 15—Condensed Version of Troubleshooting FK4C,
FV4A, and 40FKA Motor and Controls

This section provides a quick summary of how to troubleshoot the
FK4C, FV4A, and 40FKA. If more information is needed, refer to
appropriate sections of this service manual.

+ MOTOR

- If motor is hard to turn manually, replace motor.

- If motor does not run, check the components listed below

according to their instructions.

- If motor runs in some operation modes and not in others,

check for a good ground connection between motor ground lead
and circuit board screw marked "ground screw" and check the
room thermostat and wiring harness according to instructions
listed below.

33

Содержание FA4ANF

Страница 1: ...ing FK4C FV4A 40FKA Motor and Controls 33 Accessories 35 THERMOSTATIC EXPANSION VALVES TXV 36 Problems Affecting TXV 36 PISTON BODY CLEANING OR REPLACEMENT 36 LIQUID TUBE STRAINER 37 FA FB FC FK COIL...

Страница 2: ...1 The low voltage stripped leads are used to connect the 24 v side of transformer to indoor thermostat and outdoor section 2 A 5 amp fuse is used to protect the low voltage transformer secondary 3 The...

Страница 3: ...w 2 Downflow 3 Horizontal 4 Multipoise 5 Upflow Downflow Airflow 018 1 1 2 Ton 024 2 Ton 001 Multi Tons 002 Multi Tons Etc Cooling Size 10th 11th 12th Positions Fan Coil 005 010 Etc Heating Size KW 6t...

Страница 4: ...gether If independent staging is desired consult outdoor ther mostat installation instructions or corporate thermostat instruc tions Step 3 Troubleshooting the Printed Circuit Board Use wiring schemat...

Страница 5: ...itch Black wire should be connected to pin number 7 of plug and to sequencer relay number 1 3 Check incoming high voltage power leads If these are not receiving power system cannot function If Transfo...

Страница 6: ...de DC power for the fan relay and the first stage of electric heat W2 W3 or E Fig 3B FF1D Typical Wiring Diagram A98229 SEE NOTE 7 F 1 NO NC SPT OUTDOOR UNIT G PCB BLK C INDOOR THERMOSTAT BARRIER C T...

Страница 7: ...primary or high side of the transformer The blue wire is connected to T3 for 208 v applications The red wire is connected to T3 for 230 v applications Units are factory wired at 230v The T2 terminal i...

Страница 8: ...EWER ELEMENTS AND COMPONENTS 9 1 PHASE HEATERS ARE SHOWN WIRED FOR SINGLE SUPPLY CIRCUIT 10 USE 60 AMP CLASS K FUSES ONLY FOR REPLACEMENT 11 3 SPEED MOTOR SHOWN OPTIONAL 2 SPEED MOTOR USES HI BLK AND...

Страница 9: ...4 Replace low voltage fuse with no greater than 5 amp fuse 5 Use 60 amp class K fuses only for replacement 6 3 speed motor shown Optional 2 speed motor uses HI BLK and LOW BLU or RED 7 Connect R to R...

Страница 10: ...Fig 10 shows proper connection for latent capacity control kit Note that it is connected in the same manner as 2 speed fan relay kit but with relay connected to humidistat orange wires c Time delay of...

Страница 11: ...ck sequencer number 1 and the plug s wiring the yellow wire should be connected to pin number 9 of the plug and the limit switch A black wire should be connected to pin number 7 of the plug and to seq...

Страница 12: ...FUSE MAX FAN TDB YEL LS 5 HTR5 BLK BLK 10 9 YEL FU5 FU6 SEQ 3 LS 6 HTR6 BLK BLK 12 11 YEL LS 5 HTR5 BLK BLK 6 5 YEL FU3 FU4 SEQ 2 LS 4 HTR4 BLK BLK 8 7 YEL LS 1 HTR1 BLK BLK BLU MED BLU MED RED LO RED...

Страница 13: ...G RED FR LOW MTR SPD HI MTR SPD FAN COMMON UNUSED LEAD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O N C O M M O N D U M M Y T 3 L 2 L 1 F 1 F 2 F 3 F...

Страница 14: ...LD POWER WIRING AUX 1 AUX 2 F4 24 VDC RED FR LOW MTR SPD HI MTR SPD FAN COMMON UNUSED LEAD BLK 208 240 VAC NO C HST ORG ORG COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M...

Страница 15: ...WIRING FIELD POWER WIRING AUX 1 AUX 2 F4 24 VDC TDR YEL FAN COMMON UNUSED LEAD UNUSED LEAD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O N C O M M O...

Страница 16: ...NG AUX 1 AUX 2 F4 24 VDC TDR FR ORG ORG RED YEL FAN COMMON UNUSED LEAD LOW MTR SPD HI MTR SPD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R COM NO NC T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O...

Страница 17: ...MAX AUX2 L1 EAC1 FAN R L G E C O Y W2 INDOOR THERMOSTAT YEL YEL BLK LS 3 HTR3 BLK BLK 6 5 YEL FU1 FU2 FU3 FU4 SEQ 2 LS 4 HTR4 BLK BLK 8 7 YEL LS 1 HTR1 BLK BLK 2 1 YEL SEQ 1 LS 2 HTR2 BLK BLK 4 3 SEQ...

Страница 18: ...incoming high voltage power leads If these are not receiving power the system cannot function If the PCB has high voltage applied to it 1 Check the low voltage transformer leads R and C Make sure they...

Страница 19: ...ensure that it is replaced with a limit switch of identical opening temperature and closing differential Limits switches are typically color coded to identify their range KFA AND KFB SEQUENCER The seq...

Страница 20: ...ters or undersized duct 2 Check blower motor and wheel for proper operation Exces sive current draw of motor will cause internal overload to trip 3 The fan speed may be low FAN COIL DESCRIPTION AND TR...

Страница 21: ...eed A circuit from R to Y1 is also required for 2 speed high The Y Y2 signal is sent directly to ICM2 COOLING MODE TWO SPEED LOW Thermostat closes circuits R to Y1 and R to O heat pump only The Y1 sig...

Страница 22: ...or erratic motor operation can result TRANSFORMER MOTOR AND ELECTRIC HEATER POWER CONNECTIONS The high voltage 230 vac power input to board is provided through electric heater connector pins 7 and 9...

Страница 23: ...or heat pump size is largest unit meant for application with model of fan coil purchased The installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within p...

Страница 24: ...UX2 Low voltage output for auxiliary option 24 vdc 0 187 X 0 032 M1 Common connection to blower motor T1 Common connection for transformer RED Common to R screw terminal and SEC2 Table 4 Connections o...

Страница 25: ...Blown Diodes If diodes are blown it is probable that electric heater plug is miswired Correct miswiring NOTE Board will need to be replaced if diode is bad If Traces Are Overheated on Back of PCB Usua...

Страница 26: ...L RECP 3 RECP 4 ICM BRN YEL RED VIO RED ORN BRN VIO ORN GRY BLU BLK BLK 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 PLUG 2 BLK YEL ORN GRN RED BRN VIO SEE NOTE 3 SEE NOTE 2 HPTB E Y1 Y0 W2 O L R NOTES 1 Us...

Страница 27: ...g and turn on power Check for 24v between pin 1 and pin 12 on the 16 pin plug See Fig 19 If no voltage is present replace wiring harness If voltage is present jumper screw terminal R Y Y2 on circuit b...

Страница 28: ...uct Data for static pressure limits The ICM2 is pre programmed and contains airflow tables for all modes of operation Blower characteristics requested airflow torque and speed are known from laborator...

Страница 29: ...let Wire AC HP Size Blue Wire Type Orange Wire AC HP CFM Adjust Black Wire AC HP Time Delay Grey Wire Continous Fan Yellow Wire Step 11 Sequence of Operation CONTINUOUS FAN MODE The thermostat closes...

Страница 30: ...R to Y1 is also required for 2 speed high Y Y2 and Y1 signal is sent to ICM2 Thermidistat call for Comfort Heat will occur between 10 and 40 F outdoors and opens circuit from R to G ICM adjusts airfl...

Страница 31: ...rness to motor The C side of low voltage control power circuit is connected by printed circuit runs to motor connector pins 9 10 and 11 then through motor control harness to motor LOW VOLTAGE CIRCUIT...

Страница 32: ...urchased The installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for size of unit installed in all operational modes See Fig 24 SYSTE...

Страница 33: ...When there is a high current drawn on transformer it is most likely because transformer has been shorted or system is trying to draw more va than transformer rating allows When fuse blows because of h...

Страница 34: ...BLK WHT PLUG 3 230V 208V Com YEL BLK BLK YEL ICM RECP 4 RECP 3 GRY 1 BRN 12 11 10 9 8 7 6 5 4 3 2 1 5 4 3 2 1 G R N Y E L B L K W H T RED VIO V I O R E D B R N O R N BRN PLUG 1 G R Y 16 15 14 13 12 11...

Страница 35: ...air cleaner when G or W are present See Fig 28 FK4C FV4A AND 40FKA DE HUMIDIFY MODE NOTE Humidistat must open on humidity rise Latent capacities for systems using the FK4C FV4A and 40FKA fan coils ar...

Страница 36: ...m with which the pin carrier spring pressure closes valve The refrigerant flow is effectively stabilized to load demand with negligible change in superheat The bi flow TXV is used on split system heat...

Страница 37: ...ndensate drain pan Remove fitting panel 7 Remove any shipping clips including horizontal pan clip and slide coil condensate pan assembly out of unit 8 Upflow or Horizontal Applications Only Remove hor...

Страница 38: ...nditioners and Heat Pumps Service Manual for further information FX4A AND FV4A COIL CONDENSATE PAN REMOVAL AND REPLACEMENT PURON REFRIGERANT Step 1 A Coil Units If it is determined that system does no...

Страница 39: ...12 Remove coil top seal See Fig 32 13 Install new coil into condensate pan using 2 original screws and 2 support columns NOTE Correct coil position in condensate pan is essential to reliable operatio...

Страница 40: ...bolts Make sure mount or motor is grounded to blower housing 4 Locate blower wheel setscrew over flat on motor shaft Rotate wheel in housing It should not rub housing and should be centered in inlet o...

Страница 41: ...LK BLK HTR LS YEL VIO BLK BLK RED BLU TRANS DISCONNECT SEE RATING PLATE FOR VOLTS HZ FIELD POWER SUPPLY CHASSIS GROUND RED VIO ORN BRN BRN CHASSIS GROUND RED ORN T A P2 B BRN BRN 5 6 SEQ CHASSIS GROUN...

Страница 42: ...hanical equipment personal injury can result from sharp metal edges Be careful when removing parts AIR FILTER To clean or replace air filter grasp it at bottom and lift it out of unit Clean filter usi...

Страница 43: ...n lead is yellow NOTE Unused fan speed leads must be tapped off to prevent direct short to cabinet surface The motor is turned on through 2 different routes The first occurs when thermostat calls for...

Страница 44: ...SFORMER PIGTAILS BLUE 208V RED 230V INSULATE UNUSED LEAD 2 FAN MOTOR PIGTAILS RED LOW BLACK HIGH INSULATE UNUSED LEAD 3 FAN MOTOR THERMALLY PROTECTED 4 SUITABLE FOR USE WITH COPPER OR COPPER CLAD ALUM...

Страница 45: ...edges Be careful when removing parts The minimum maintenance requirements for this equipment are as follows 1 Inspect and clean or replace field supplied air filter each month or as required 2 Inspec...

Страница 46: ...can result from sharp metal edges Be careful when removing parts RETURN AIR FILTER To clean or replace air filter remove screws and filter access door Slide out filter For washable type filters clean...

Страница 47: ...ally connected to equip ment ground Step 2 Unit Functions TRANSFORMER NOTE Terminals T1 T2 if used and T3 are wired to primary or high side of transformer The 208 v terminal or blue wire if transforme...

Страница 48: ...elements For troubleshooting a service LED indicates condition of PCB See Table 11 for LED flash codes Step 4 Electrical Operating Sequences and Troubleshooting NOTE Refer to Table 12 for proper inpu...

Страница 49: ...ergized control energizes fan motor It may run on high or low speed depending on its operation in previous cycle Compressor operation in current cycle is monitored by the smart control to determine wh...

Страница 50: ...ircuit of sequencer relay place voltmeter leads across sequencer relay terminal 4 of sequencer relay 1 and terminal 4 of limit switch 3 The reading should be 208 230v and heater should be energized If...

Страница 51: ...uld be designed to detect HFC refrigerant Puron R 410A as other HFC s is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated wo...

Страница 52: ...YEL COM CAP BRN FM BRN GRN YEL GND BLK HI BLU MED BRN RED TRAN MOTOR SPEED AT 20 KW FAN COIL SIZE MINIMUM MOTOR LO SPEED TAP SELECTION NOTES LS2 LS1 RED SEQ3 SEQ2 SEQ 2 9 10 BLK 7 LS2 YEL 8 BLK HTR2...

Отзывы: