minutes. If super dehumidification call continues, lower CFM and
outdoor section operation will again resume for another 10
minutes.
ELECTRIC HEAT HEATING MODE
Thermostat closes circuit R to W1 & W2.
The terminal block positions W1 and W2 are tied together by
jumper. J2 is provided for field staging of electric heater banks
through use of thermostats. When staging is a requirement, remove
J2 jumper and wire in thermostats as is the common practice with
other fan coils. To ensure motor operation if any 1 of the inputs is
energized, motor will sense input W1 or W2 and run.
HEAT PUMP HEATING MODE—SINGLE SPEED OR
2-SPEED HIGH
Thermostat closes circuit R to Y/Y2 for single speed. A circuit
from R to Y1 is also required for 2-speed high. The Y/Y2 &Y1
signal is sent to ICM2.
HEAT PUMP HEATING MODE—COMFORT HEAT WITH
40FKA
Thermidistat closes circuit R to Y/Y2. A circuit from R to Y1 is
also required for 2-speed high. Y/Y2 and Y1 signal is sent to
ICM2. Thermidistat call for Comfort Heat will occur between 10
and 40°F outdoors and opens circuit from R to G. ICM adjusts
airflow down to a lower CFM for higher discharge air temperature
and comfort.
HEAT PUMP HEATING MODE—TWO-SPEED LOW
Thermostat closes R to Y1. The Y1 signal is sent to ICM2.
HEAT PUMP HEATING WITH AUXILIARY ELECTRIC
HEAT
Thermostat closes circuits R to Y/Y2 and/or R to Y1 with R to W1
or W2 (and R to O in the case of defrost).
The terminal block positions W1 and W2 are tied together by
jumper. J2 is provided for field staging of electric heater banks
Fig. 24—Easy Select Board
A96430
YYWWX
AUX/HEAT KW/CFM
AC/HP SIZE
AC/HP CFM ADJUST
ON/OFF DELAY
CONTINUOUS FAN
HEATER/MOTOR
AUX1
HUM1
AUX2
24VAC
HUM2
LO
MED
HI
YEL
SYSTEM TYPE
SEC1
®
®
EASY SELECT
SEC2
J1
5 AMP.
MAX.
F1
D4
D5
D2
D3
D1
R1
R2
CES0130035-00
5
STI
J2
YEL
PL1
GRY
WHT
BLK
ORN
BLU
VIO
0-30
1075
0-20
875
0-10
725
0-5
625
036
030
024
018
AC
HP-COMFORT HP-EFF
NOM
LO
HI
0
90
30
90
0
0
ENH
D
H
R
W
1
W
2
Y
1
Y/Y
2
G
O
C
1
30