background image

9

f. Run the FR cable through the 

1

/

2

-in. connector of

the MMV enclosure (do not tighten connector

screws at this time). Connect black wire to MMV

terminal 2 and red wire to MMV terminal 1, 13A,

or 13C (see Table 4). Place 1 small varnish cloth

38C24601 around both cables at the point they

enter the 

1

/

2

-in. connector. Tighten down connector

screws being careful not to damage the cables. 

8. Bundle excess wire and dress harnesses with wire ties.
9. Re-attach control box, MMV enclosure, and cable tray

covers.

48/50P070-100 UNITS — For  48/50P070-075  units,  two

Motormaster controls are used to control two independent out-

door-fan motors (OFM). The refrigerant circuit-A Motormas-

ter

®

 controlled OFM is the no. 3 OFM. The refrigerant circuit-

B Motormaster controlled OFM is the no. 1 OFM (see Fig. 3).

The no. 2 and 4 OFMs are controlled by the 

Comfort

Link™

head pressure control routine.

For 48/50P090-100 units, the two Motormaster controls are

used to control two independent outdoor-fan motors. The re-

frigerant circuit-A Motormaster controlled OFM is the no. 6

OFM. The refrigerant circuit-B Motormaster controlled OFM

is the no. 2 OFM (see Fig. 3). The no. 1, 3, 4, and 5 OFMs are

controlled by the 

Comfort

Link head pressure control routine.

Use the following procedure to mount and connect the

MMV controllers to this unit:

1. Disconnect power to the unit. Lockout and tag power dis-

connect.

2. Remove control box covers.
3. Remove fan decks to gain access to each circuit’s respec-

tive Motormaster controlled OFM, as shown in Fig. 9 and

10.

4. Mount accessory fuse blocks HY11UT035 (label 1 as

MMF-A and the other as MMF-B) and fan relay bases

HN79KK035 (label 1 as FR-A and the other as FR-B) in-

side control box as shown in Fig. 7. Secure components

with ½-in. sheet metal screws. 

a. Insert fuses into fuse blocks and relays into relay

bases.

b. Install harnesses 48EJ402454 from load side of

CCB (control circuit breaker terminals 21, 22, 23)

to line side of MMF-A and MMF-B fuse blocks as

shown in Fig. 11. Note that it may be easier to

pickup the load side of CCB from the ¼-in. male

quick connect terminals on the line side (terminals

11, 12, 13) of the OFC contactors (see power sche-

matic on control box door).

c. For 070 and 075 units:

Connect FR-A coil to OFC3 coil and FR-B coil to

OFC1 coil using the 72 in. long 16 gage white and

gray wires (stripped end goes to FR) as shown in

Fig. 11.

For 090 and 100 units:

Connect FR-A coil to OFC3 coil and FR-B coil to

OFC2 coil using the 72 in. long 16 gage white and

gray wires (stripped end goes to FR) as shown in

Fig. 11.

5. Mount the MMV controller enclosures 30RA500381on

the bulkhead, as shown in Fig. 9 (sizes 070 and 075) and

Fig. 10. (sizes 090 and 100) using the mounting brackets

50EJ500656 installed on the enclosures (label 1 as MMV-

A and the other as MMV-B). Remove the enclosure cov-

ers and install the ½-in. HW60EA001 and 1-in.

HW60HH006 connectors in the holes in the lower right

hand side of the enclosures. 

6. Connect transducers HK05ZZ001 to the liquid line ser-

vice Schrader ports, located under the V-coils of the con-

denser fan sections, of refrigerant circuit A and B. Circuit

A is the one closest to the Indoor Fan Motor section, and

circuit B is the one closest to the control box, (label cir-

cuit A transducer as MMPT-A and circuit B transducer as

MMPT-B).

7. Plug transducer cables 48EJ403240 into transducers (la-

bel stripped end of circuit A cable as MMPT-A and the

stripped end of circuit B cable as MMPT-B). Run cables

along inside of unit base rail and up the corner post to the

MMV enclosures, as shown in Fig. 9 and 10.

8. Run MMPT-A cable through 

1

/

2

-in. connector of MMV-

A enclosure, and MMPT-B cable through 

1

/

2

-in. connec-

tor of MMV-B enclosure (do not tighten connector

screws at this time). Connect red, green, and black wires

to MMV-A and MMV-B terminals 6, 5, and 2 as shown

in Fig. 11. Terminate drain wire of transducer cables un-

der one of the lower MMV mounting screws.

9. Make remaining electrical connections to MMV-A and

MMV-B (see Fig. 11).

a. For 070 and 075 units:

In the main control box, disconnect black, red,

blue, and green wires from load side (terminals 21,

22, 23) of OFC1 and OFC3 contactors (label cable

from OFC1 as OFM1 and cable from OFC3 as

OFM3). Pull wires out through the hole in the bot-

tom of the control box and run them up the corner

post to the opening of the cable tray on the side of

the control box, as shown in Fig. 9. Run the cable

through the wire tray to the MMV enclosures.
Run the OFM1 cable through the 1-in. connector

of the MMV-B enclosure (do not tighten connector

screws at this time). Remove ring terminals from

black, red, and blue wires and strip insulation back

3/8-in. Connect black, red, and blue wires to

MMV-B terminals T1, T2, and T3. Connect green

ground wire to MMV-B ground screw.
Run OFM3 cable through 1-in. connector of

MMV-A enclosure (do not tighten connector

screws at this time). Remove ring terminals from

black, red, and blue wires and strip insulation back

3

/

8

-inch. Connect black, red, and blue wires to

MMV-A terminals T1, T2, and T3. Connect green

ground wire to MMV-B ground screw.

For 090 and 100 units:

In Main Control box, disconnect black, red, blue,

and green wires from load side (terminals 21, 22,

23) of OFC2 and OFC3 contactors (label cable

from OFC2 as OFM2 and cable from OFC3 as

OFM3). Pull wires out through the hole in the bot-

tom of the control box and run them up the corner

post to the opening of the cable tray on the side of

the control box, as shown in Fig. 10. Run the cable

through the wire tray to the MMV enclosures. 
Run the OFM2 cable through the 1-in. connector

of the MMV-B enclosure (do not tighten connector

screws at this time). Remove ring terminals from

black, red, and blue wires and strip insulation back

3

/

8

-in. Connect black, red, and blue wires to MMV-

B terminals T1, T2, and T3. Connect green ground

wire to MMV-B ground screw.
Run OFM6 cable through 1-in. connector of

MMV-A enclosure (do not tighten connector

screws at this time). Remove ring terminals from

black, red, and blue wires and strip insulation back

3/8-in. Connect black, red, and blue wires to

MMV-A terminals T1, T2, and T3. Connect green

ground wire to MMV-B ground screw.

Содержание CRLOWAMB033A00

Страница 1: ...nd permits operation at lower outdoor ambient temperatures To operate these units at very low ambient temperatures Mo tormaster V controls Fig 1 mustbe added Field fabricated and installedwindbaffles...

Страница 2: ...HY10KB151 3 HY10KB151 3 Fuse 20A KTK R Class CC HY10KB200 3 Harness Assembly 48ZZ401971 Harness Assembly 48EJ402454 Harness Assembly 48ZZ402001 Label 48ZZ502002 Transducer HK05ZZ001 Transducer Harness...

Страница 3: ...CRLOWAMB037A00 CRLOWAMB038A00 Connector 1 2 in HW60EA001 2 Connector 1 in HW60HH006 2 Controller 230 V 2 Hp HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30...

Страница 4: ...ils NOTE 48 50P030 035 and 070 100 units do not require baffles UNIT SIZE QUANTITY DIMENSION A in mm 030 035 Not Used 040 060 2 78 125 0 125 1984 3 070 100 Not Used BAFFLE INSTALLATION LOCATION SIZES...

Страница 5: ...wire of transducer cables under one of the lower MMV mounting screws 7 Make remaining electrical connections to MMV see Fig 8 a In main control box disconnect black red blue and green wires from load...

Страница 6: ...outine 090 100 1 Controlled by the ComfortLink head pressure control routine 2 MMV B 3 Controlled by the ComfortLink head pressure control routine 4 5 6 MMV A Control Box 1 2 Control Box 1 2 3 Control...

Страница 7: ...N THE WIRES ALONG THE OUTSIDE OF THE COIL TRAY Fig 5 MMV Control Mounting 48 50P040 Units a48 8563 RUN ELECTRICAL HARNESSES UP THE SIDE OF THE UNIT IN THE SPACE BETWEEN THE CORNER POST AND THE CONTROL...

Страница 8: ...IONS FR A OFC1 13 14 C1 C2 ADD FAN RELAY FR IN PARALLEL WITH OFC1 CCB MM F BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK GRY WHT 11 12 13 22 23 21 FR A Fig 8 Motormaster V Accessory W...

Страница 9: ...liquid line ser vice Schrader ports located under the V coils of the con denser fan sections of refrigerant circuit A and B Circuit A is the one closest to the Indoor Fan Motor section and circuit B...

Страница 10: ...bel the opposite end of this harness as FR A and the other Motormaster VFD harness 48ZZ402001 to the NO contact of FR B label the opposite end of this harness as FR B Run the har nesses along the bott...

Страница 11: ...when the compressor en gages The control will adjust the fan speed to maintain ap proximately 320 psig Above that pressure the fan should op erate at full speed For size 030 060 units the Motormaster...

Страница 12: ...2 T3 B B BLK 1 2 5 6 11 12 2 14 13A 13B 13C 15 5 9 FR A MMPT A 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC 3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC 3 MMF A...

Страница 13: ...ion of observing system operation and VFD display information If the liquid line pressure is above the set point and the VFD is running at full speed this is a normal condition The fan CANNOT go any f...

Страница 14: ...50 P28 Fixed boost 0 5 at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Pres...

Страница 15: ...User data and Carrier defaults in the EPM are corrupted Restore factory defaults by toggling P48 to another mode Then set P48 to desired mode to restore all defaults for that mode See Drive Programmin...

Страница 16: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480070 01 Printed in U S A Form 48 50P 2SI Pg 16 9 09 Replaces New Copy...

Отзывы: