background image

11

Step 3 — Configure Motormaster

®

 V Con-

trol — 

The Motormaster V control is configured for propor-

tional integral (PI) control mode. The Motormaster V varies

the condenser fan motor speedto maintain a set point of

320 psig liquid line pressure in response to a 0 to 5 vdc feed-

back signal from the liquid line pressure transducer. No addi-

tional programming is required. See Table 4. Note that the

pressure transducer must be attached for proper configuration.

Table 4 — Configuration Table

The following 

Comfort

Link control configurations must be

set when using a Motormaster V device:

Configuration

COOL

M.M.

 = YES

Configuration

COOL

LLAG

 = CIRCUIT A (size

030-060 units only)

Step 4 — Test Motormaster V Control — 

To test the

control and motor in the test mode, run compressor no. 1.  The

Motormaster V electronic control adjusts the fan speed based

on the liquid line pressure input. Ensure that fans are rotating

clockwise (as viewed from above). If rotation is backward,

lock out all power then swap 2 leads AFTER the Motormaster

V control.

START-UP

The Motormaster V electronic control will be powered up

as long as unit voltage is present. When the system calls for

cooling, the fan relay will be energized to initiate the start-up

sequence for the Motormaster V electronic control. The LED

(light-emitting diode) will display the speed of the motor. The

display range will be 8 to 60 Hz. The Motormaster V electronic

control will start the condenser fan when the compressor en-

gages. The control will adjust the fan speed to maintain ap-

proximately 320 psig. Above that pressure, the fan should op-

erate at full speed.

For size 030-060 units, the Motormaster V control uses a 0

to 5 vdc signal input from a pressure transducer attached to the

liquid line service valve gage port on circuit A.

For size 070-100 units, two Motormaster V devices are

used, one for each circuit. The circuit A Motormaster V control

uses a 0 to 5 vdc signal input from a pressure transducer at-

tached to the liquid line service valve gage port on circuit A.

The circuit B Motormaster V control uses a 0 to 5 vdc signal

input from a pressure transducer attached to the liquid line ser-

vice valve gage port on circuit B.

The pressure transducer(s) are connected to terminals 2, 5

and 6 on the controller. The controller is configured by jumper

wires and sensor input types. No field programming is re-

quired. If controller does not function properly, the information

provided below can be used to program and troubleshoot the

drive.

REMOVE TWO FAN DECK

S

TO

GAIN ACCE

SS

TO ROUTE WIRING TO

OFM 2 AND OFM 6

ROUTE THROUGH

S

NAP BU

S

HING

MOTORMA

S

TER A

CONTROL

MOTORMA

S

TER B

CONTROL

TRAN

S

DUCER A

TRAN

S

DUCER B

RUN ELECTRICAL HARNE

SS

E

S

UP THE

S

IDE OF THE UNIT

IN THE

S

PACE BETWEEN THE

CORNER PO

S

T AND THE

CONTROL BOX. ROUTE WIRE

S

INTO WIRE TRAY AND RUN
TO MMV A/B AND OFM 6/2

REMOVE PANEL

Fig. 10 — MMV Control Mounting — 48/50P090,100 Units

a48-8568

NOMINAL

VOLTAGE

(V-Ph-Hz)

MODE

CONTROL INPUT

(Pin 5)

START

CONTACTS

230-3-60
460-3-60
575-3-60

1

Internal PI control,

 0-5V feedback

TB 1,2

208-3-60
380-3-60

2

TB 13A,2

400-3-50

4

TB 13C,2

Содержание CRLOWAMB033A00

Страница 1: ...nd permits operation at lower outdoor ambient temperatures To operate these units at very low ambient temperatures Mo tormaster V controls Fig 1 mustbe added Field fabricated and installedwindbaffles...

Страница 2: ...HY10KB151 3 HY10KB151 3 Fuse 20A KTK R Class CC HY10KB200 3 Harness Assembly 48ZZ401971 Harness Assembly 48EJ402454 Harness Assembly 48ZZ402001 Label 48ZZ502002 Transducer HK05ZZ001 Transducer Harness...

Страница 3: ...CRLOWAMB037A00 CRLOWAMB038A00 Connector 1 2 in HW60EA001 2 Connector 1 in HW60HH006 2 Controller 230 V 2 Hp HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30...

Страница 4: ...ils NOTE 48 50P030 035 and 070 100 units do not require baffles UNIT SIZE QUANTITY DIMENSION A in mm 030 035 Not Used 040 060 2 78 125 0 125 1984 3 070 100 Not Used BAFFLE INSTALLATION LOCATION SIZES...

Страница 5: ...wire of transducer cables under one of the lower MMV mounting screws 7 Make remaining electrical connections to MMV see Fig 8 a In main control box disconnect black red blue and green wires from load...

Страница 6: ...outine 090 100 1 Controlled by the ComfortLink head pressure control routine 2 MMV B 3 Controlled by the ComfortLink head pressure control routine 4 5 6 MMV A Control Box 1 2 Control Box 1 2 3 Control...

Страница 7: ...N THE WIRES ALONG THE OUTSIDE OF THE COIL TRAY Fig 5 MMV Control Mounting 48 50P040 Units a48 8563 RUN ELECTRICAL HARNESSES UP THE SIDE OF THE UNIT IN THE SPACE BETWEEN THE CORNER POST AND THE CONTROL...

Страница 8: ...IONS FR A OFC1 13 14 C1 C2 ADD FAN RELAY FR IN PARALLEL WITH OFC1 CCB MM F BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK GRY WHT 11 12 13 22 23 21 FR A Fig 8 Motormaster V Accessory W...

Страница 9: ...liquid line ser vice Schrader ports located under the V coils of the con denser fan sections of refrigerant circuit A and B Circuit A is the one closest to the Indoor Fan Motor section and circuit B...

Страница 10: ...bel the opposite end of this harness as FR A and the other Motormaster VFD harness 48ZZ402001 to the NO contact of FR B label the opposite end of this harness as FR B Run the har nesses along the bott...

Страница 11: ...when the compressor en gages The control will adjust the fan speed to maintain ap proximately 320 psig Above that pressure the fan should op erate at full speed For size 030 060 units the Motormaster...

Страница 12: ...2 T3 B B BLK 1 2 5 6 11 12 2 14 13A 13B 13C 15 5 9 FR A MMPT A 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC 3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC 3 MMF A...

Страница 13: ...ion of observing system operation and VFD display information If the liquid line pressure is above the set point and the VFD is running at full speed this is a normal condition The fan CANNOT go any f...

Страница 14: ...50 P28 Fixed boost 0 5 at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Pres...

Страница 15: ...User data and Carrier defaults in the EPM are corrupted Restore factory defaults by toggling P48 to another mode Then set P48 to desired mode to restore all defaults for that mode See Drive Programmin...

Страница 16: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480070 01 Printed in U S A Form 48 50P 2SI Pg 16 9 09 Replaces New Copy...

Отзывы: