Installation Instructions
CONTENTS
PACKAGE CONTENTS . . . . . . . . . . . . . . . . . . . . . .1
PACKAGE USAGE . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SENSOR USAGE . . . . . . . . . . . . . . . . . . . . . . . . . .
2
ACCESSORIES LIST . . . . . . . . . . . . . . . . . . . . . . .
3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . .5-9
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or service
air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of
replacing filters. All other operations should be performed by trained
service personnel. When working on air-conditioning equipment, observe
precautions in the literature, tags, and labels attached to the unit, and
other safety precautions that may apply. Follow all safety codes. Wear
safety glasses and work gloves.
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the unit and in instructions or manuals, be
alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury or
death. WARNING signifies a hazard which could result in personal
injury or death. CAUTION is used to identify unsafe practices which may
result in minor personal injury or product and property damage. NOTE is
used to highlight suggestions which will result in enhanced installation,
reliability, or operation.
GENERAL
The EconoMi$er2 system utilizes the latest technology available
for
integrating the use of free cooling with mechanical cooling for rooftop
units.
This system utilizes gear-drive technology with a direct mount spring
return actuator that will close upon loss of power. The EconoMi$er2
system comes standard with an outdoor air temperature sensor. Field-
installed CO
2
sensors are available.
Standard barometric relief dampers provide natural building pressurization
control. An optional power exhaust system is available for applications
requiring even greater exhaust capabilities.
EconoMi$er2 accessories have a 4 to 20 mA actuator signal control.
These accessories do not include the EconoMi$er2 controller. The
EconoMi$er2 actuator is operated by a 4 to 20 mA signal from an existing
field-supplied controller (such as PremierLink
TM
controller). See Table
3 for sensor usage.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury and/or
death.
Disconnect power supply and install lockout tag before attempting to
install the accessory.
!
Table 2 - Package Usage
Table 1 - Package Contents
UNIT SIZE
PART NUMBER
Small Cabinet,
Footprint size: 46 3/4” x 74 3/8”
CRECOMZR022A01
Large Cabinet,
Footprint size: 58 1/2” x 88 1/8”
CRECOMZR023A01
Extra-Large Cabinet,
Footprint size: 63 3/8” x 115 7/8”
CRECOMZR063A00
PACKAGE NO.
QTY
CONTENTS
CRECOMZR022A01,
CRECOMZR023A01
1
1
1
18
1
1
Hood Top and Sides
Hood Divider
Aluminum Filter
Screws
EconoMi$er2 Assembly
Supply Air Temperature Sensor
CRECOMZR063A00
1
1
1
2
1
1
1
Hood Top and Sides
Hood Divider
Hood Filter Divider
Aluminum Filters
Hardware Bag
EconoMi$er2 Assembly
Supply Air Temp Sensor
Small Rooftop Units
Accessory Vertical EconoMi$er2
2 to 12 1/2 Tons
CRECOMZR022A01
CRECOMZR023A01
CRECOMZR063A00
!
IMPORTANT:
Read these instructions completely before attempting to
install the Vertical EconoMi$er2 Accessory.
Содержание CRECOMZR022A01
Страница 6: ...6 Fig 10 EconoMi er2 Connection to PremierLinkTM Electric Heating Cooling Controls...
Страница 7: ...7 Fig 11 EconoMi er2 Connection to PremierLinkTM Gas Heat Electric Cooling Controls...
Страница 8: ...8 Fig 12 EconoMi er2 Connection to RTU MP Electric Heating Cooling Controls...
Страница 9: ...9 Fig 13 EconoMi er2 Connection to RTU MP Gas Heat Electric Cooling Controls...