Appendix A: BACnet Points List
Carri
er Connect™ Wi
-Fi Thermostat 33CONNECTSTAT43FX
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
53
Point Name
Point Access
Units
BACnet Point Name
BACnet
Object ID
Indoor Space Temperature
WRITE_WHEN_OOS
DEGREES_FAHRENHEIT
ID_SPACE_TEMP
AI:100
Indoor Space Humidity
WRITE_WHEN_OOS
PERCENT_RELATIVE_HUMIDITY
ID_SPACE_HUM
AI:101
Remote Space Temperature READ_ONLY
DEGREES_FAHRENHEIT
REM_SPACE_TEMP
AV:100
Outdoor Temperature
READ_ONLY
DEGREES_FAHRENHEIT
OD_TEMP
AV:101
Supply Air Temperature
READ_ONLY
DEGREES_FAHRENHEIT
SAT
AV:102
Network Space Temperature READ_WRITE
DEGREES_FAHRENHEIT
NET_SP_TEMP
AV:103
Space Temperature for
Control
READ_ONLY
DEGREES_FAHRENHEIT
SP_TEMP_CTRL
AV:104
Network Space Humidity
READ_WRITE
PERCENT_RELATIVE_HUMIDITY
NET_SP_HUM
AV:105
Space Humidity for Control
READ_ONLY
PERCENT_RELATIVE_HUMIDITY
SP_HUM_CTRL
AV:106
Air Filter Hours Left
READ_ONLY
HOURS
AIR_FLTR_HRS_LFT
AV:300
Override Time Remaining
READ_ONLY
HOURS
OVRD_TIME
AV:301
Occupied Heat Setpoint
READ_WRITE
DEGREES_FAHRENHEIT
OCC_HT_SP
AV:400
Occupied Cool Setpoint
READ_WRITE
DEGREES_FAHRENHEIT
OCC_CL_SP
AV:401
Unoccupied Heat Setpoint
READ_WRITE
DEGREES_FAHRENHEIT
UNOCC_HT_SP
AV:402
Unoccupied Cool Setpoint
READ_WRITE
DEGREES_FAHRENHEIT
UNOCC_CL_SP
AV:403
Dehumidification Setpoint
READ_WRITE
PERCENT_RELATIVE_HUMIDITY
DEHUM_SP
AV:406
Humidification Setpoint
READ_WRITE
PERCENT_RELATIVE_HUMIDITY
HUM_SP
AV:407
Screen Timeout
READ_WRITE
SECONDS
SCRN_TMT
AV:408
Heat Setpoint
READ_WRITE
DEGREES_FAHRENHEIT
HEAT_SP
AV:409
Cool Setpoint
READ_WRITE
DEGREES_FAHRENHEIT
COOL_SP
AV:410
Active Backlight
READ_WRITE
PERCENT
ACTV_BCKLT
AV:411
Dormant Backlight
READ_WRITE
PERCENT
DRMNT_BCKLT
AV:412
Indoor Equip Stages
GATED_WRITE
ID_STAGES
AV:500
Outdoor Equip Stages
GATED_WRITE
OD_STAGES
AV:501
Max Temperature Hold Time GATED_WRITE
HOURS
MAX_HOLD_TIME
AV:502
Auto Changeover Delay
GATED_WRITE
MINUTES
AUTO_XOVR
AV:503
Cool Lockout Temperature
GATED_WRITE
DEGREES_FAHRENHEIT
COOL_LOCKOUT
AV:504
Low Cool Lockout (HP only)
GATED_WRITE
DEGREES_FAHRENHEIT
LO_CL_LCKOUT
AV:505
Low Heat Lockout (HP only)
GATED_WRITE
DEGREES_FAHRENHEIT
LO_HT_LCKOUT
AV:506
Delay Between Fuel (HP
only)
GATED_WRITE
MINUTES
DLY_BW_FUEL
AV:507
Cycles Per Hour
GATED_WRITE
CYCLES_PER_HOUR
CYCLES_HR
AV:508
Max Heat Setpoint
GATED_WRITE
DEGREES_FAHRENHEIT
MAX_HT_SP
AV:509
Min Cool Setpoint
GATED_WRITE
DEGREES_FAHRENHEIT
MIN_CL_SP
AV:510
Aux Heat Lockout (HP only)
GATED_WRITE
DEGREES_FAHRENHEIT
AUX_HT_LCKOUT
AV:511
Heat Pump Lockout
GATED_WRITE
DEGREES_FAHRENHEIT
HP_LCKOUT
AV:512
Stage Delay
GATED_WRITE
MINUTES
STG_DELAY
AV:513
Forced Stage Up Delay
GATED_WRITE
MINUTES
FRCD_STG_UP
AV:514
Stage Change Temp
Differential
GATED_WRITE
DELTA_DEGREES_FAHRENHEIT
DIFFERENTIAL
AV:515
Indoor Temperature Offset
GATED_WRITE
DELTA_DEGREES_FAHRENHEIT
ID_TEMP_OFF
AV:517
Indoor Humidity Offset
GATED_WRITE
PERCENT_RELATIVE_HUMIDITY
ID_HUM_OFF
AV:518
SAT Temp Offset
GATED_WRITE
DELTA_DEGREES_FAHRENHEIT
SAT_OFFSET
AV:519
Air Filter Hours
READ_ONLY
HOURS
AIR_FLT_HRS
AV:520
Appendix A: BACnet Points List
Содержание Connect 33CONNECTSTAT43FX
Страница 4: ......
Страница 68: ......
Страница 69: ......
Страница 70: ...Carrier 2021 Catalog No 11 808 872 01 12 3 2021 ...