P89 – De-ice in heat – cut-in temperature (AC only!)
Range: -9.5…+8°C / 15...46°F
Default: 0°C / 32°F
P90 – De-ice in heat – cut-out temperature (AC only!)
Range: 2...20°C / 35...68°F
Default: 16°C / 61°F
P91 – Compressor delay (AC only!)
Range: 0...360 Seconds
Default: 240 Seconds
P99 – One or Two setpoints (for cool and for heat)
“00” - One setpoint for cooling and heating
“01” - two setpoints – one for cool and one for heat
One
setpoint
Two
setpoints
P98 – Display setpoint only (hide room temperature)
“00” - Display both setpoint and room temperatures
“01” - Display only the setpoint temperature
Hide room
temperature
Compressor
delay
De-ice in heat
(°F)
(°C)
De-ice in heat
(°F)
(°C)
Show room
temperature
The outdoor unit coil temperature in which de-icing will stop.
The outdoor unit coil temperature in which de-icing will start.
DIP Switch SW3.5 must be in “OFF” position – compressor delay enabled!
- 57 -
Technician Settings (cont.)