Comfort Zone Configuration Table
TOGGLE
DESCRIPTION
FACTORY
DEFAULT
RECORD
JOB SETTING
T1
Timeguard Override
OFF
T2
Celsius Temperature Display
OFF
T3
2400 Baud Rate
ON
T4
Error Code Display
ON
T5
Enable Broadcast
ON
T6
Heat Pump Operation
OFF
T7
Outside Air Temp Sensor Attached
OFF
T8
Comfort Trend Setting
ON
T9
Auto Fan Off For Heat
OFF
T10
High/Low Temperature Limits
ON
T11
Installer Switch Lockout
OFF
T12
Force Outside Air Ventilation
OFF
T13
Smart Sensor Attached For Zone 2
OFF
T14
Smart Sensor Attached For Zone 3
OFF
T15
Smart Sensor Attached For Zone 4
OFF
T16
Zone 2 Active
ON
T17
Zone 3 Active
ON
T18
Zone 4 Active
ON
T19
Economizer
OFF
T20
Alternating Display
OFF
T21
Outside Air Damper Attached
OFF
T22
System Mode Reselect
OFF
T23
System Error Checking
OFF
T24
50 Hz Operation
OFF
T25
Ventilation Mode
OFF
T26
Two-Stage Heat Pump
OFF
T27
Dx Sensor For LAT Checking
OFF
T28
Cool Without Fan
OFF
SETTING
S-1
4 Zone Controller Bus Address
04
S-2
Max Cooling Setpoint
85
S-3
Min Heating Setpoint
65
S-4
Max Damper Position
15
S-5
Ventilation Damper Position
00
S-6
High Temp Trip Limit
105
S-7
Dual Fuel Setpoint
00
ROTARY
09
Base Temp Setpoint Scale
08
Calibrate Dx Coil Sensor
07
Calibrate Outside Air Temp Sensor
06
Calibrate Duct Temperature Sensor
05
Calibrate Zone 4 Temp Sensor
04
Calibrate Zone 3 Temp Sensor
03
Calibrate Zone 2 Temp Sensor
02
Calibrate Zone 1 Temp Sensor
01
Damper Service Position
Copyright 1995 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231
zonekt4c
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
1
4
4
Tab
3a 5a 2a 5a
PC 101
Catalog No. 809-568
Printed in U.S.A.
Form ZONEKIT4-1SI
Pg 32
7-95
Replaces: 920415-3SI