background image

then temperature at which first stage will be shut down will be
offset 5°F above limit value (110°F to 114°F). If limit temperature
is between 110°F and 155°F, then temperature at which first stage
will shut down will be offset 20°F above limit value (130°F to
175°F). For Cooling modes the temperature is fixed at 50°F (10°C)
for starting the control and 45°F (7.2°C) for turning off first-stage
cooling.

The heating value must be set given the type of heater used in the
system. This is for the final heat source. So a heat pump with
strip heat would use a temperature appropriate for strip heaters. A
furnace application may have a setting in the 130°F to 155°F
range. Strip heaters may fall into a 115°F to 130°F range. Heat
pump only systems may use 105°F to 115°F. Check equipment
manufacturer recommendations and verify setting is in accordance
with UL, NFPA, or any applicable Local or State Building Codes.
If there is any question about what may be an appropriate
temperature setting, use conservative (low) temperatures.

Dx Coil Sensor For Leaving Air Temperature (Rotary Position
T-27) allows Comfort Zone to use a Dx Coil Sensor in addition to
Remote Duct Sensor for Leaving Air Temperature Checking. The
Dx Coil Sensor is used in heat pumps with fan coil applications
and will be located after the Dx coil and before any strip heaters.
This sensor is only active during heat pump operation. The
temperature setting for this sensor is fixed at 105°F for initiating
the control option and 110°F for shutting down first stage.

Heat Pump-Strip Heat Economy Feature (Smart Start). This is
an automatic control within Comfort Zone and not a selectable
option. The Smart Start feature is used whenever primary source of
heat is a heat pump. As such, the Heat Pump toggle (Rotary
Position T-6) must be turned ON. Smart Start is designed to help
minimize use of strip heat or emergency heat whenever a large
heating demand occurs due to a scheduled setpoint change. Smart
Start looks at scheduled comfort setpoints for the next hour. If
scheduled setpoints will make system provide heat, Smart Start
will start heat pump an hour early. Smart Start will operate until
zone demand is brought within 0.5°F (0.28°C) of the next hour’s
heat setpoint or setpoints change due to the schedule (the hour
expires).

Smart Start assumes auxiliary heat is more expensive to operate
when compared to heat pump and it assumes that heat pump is a
relatively "slow" source of heat. Smart Start allows a zone to
recover from a setback or unoccupied period and use the most
economic source of heat in doing so. The idea of using a setback
or unoccupied schedule is to save money in operating costs. There
is little incentive to use schedules if zone is heated with most
expensive source of heat available.

Step 11—Configuring Four Zone Controller

PROGRAMMABLE OPTIONS-SETTINGS

Turn zone selector dial to position S. (See Fig. 18.) The controller
display shows setting number and its value.

The upper 2 digits show the setting’s number and the lower 2 digits
show the value of setting.

Press the COOL up or down setpoint buttons to change setting
number and the HEAT up or down setpoint buttons to change
value. Refer to Table 6 for settings and their definitions.

1. Zone Controller Bus Address (S-1)

This setting establishes the identity of the 4 zone controller on
the Carrier communication bus.

NOTE:

Remote room sensors do not require addressing.

If using optional Smart Sensors, they must be addressed as
follows:

ZONE 1 Address of 4 zone controller
ZONE 2 Address must be 1 less than zone 1
ZONE 3 Address must be 2 less than zone 1
ZONE 4 Address must be 3 less than zone 1

To set address of a Smart Sensor, rotary switch position 1 on
Smart Sensor must be selected first.

2. Maximum Cooling Setpoint (S-2)

This is the highest temperature value to which cooling setpoint
can be adjusted. All zones will use same value. The maximum
cooling setpoint can be programmed from 80°F to 95°F. This
allows cooling setpoints to be programmed above normal
range.

Example: Maximum cooling setpoint is programmed at 92°
F. The temperature range for cooling setpoint is 70° F to 84°F.
When the COOL setpoint up button is pressed to adjust
cooling setpoint above 84°F, setpoint will jump to 92°F.

3. Minimum Heating Setpoint (S-3)

This is the lowest temperature value to which heating setpoint
can be adjusted. All zones will use same value. The minimum
heating setpoint can be programmed from 34°F to 64°F. This
allows heating setpoints to be programmed below normal
range.

Example: Minimum heating setpoint is programmed at 56°
F. The temperature range for heating setpoint is 66° F to 80°F.
When the HEAT setpoint down button is pressed to adjust
heating setpoint below 66°F, setpoint will jump to 56°F.

4. Maximum Damper Position (S-4)

This is the highest open position to which a damper will
change. Full open is designated as position 15. Maximum
open damper position can be programmed between 8 (half
open) and 15, in increments of 1. All zone dampers will use
the same programmed maximum value.

5. Ventilation/Minimum Damper Position (S-5)

When there is no demand for cooling or heating, this is the
minimum position that every zone damper will maintain as
long as air temperature in duct work is between 65°F and
80°F. Full closed is designated as position 00. Minimum open
damper position can be programmed between 7 (half-open)
and 00, in increments of 1. All zone dampers will use the same
programmed ventilation value.

6. High Temperature Trip Limit (S-6)

The trip temperatures limits are duct temperatures used to turn
HVAC equipment off to prevent damage to equipment.
Temperature values are measured by duct temperature sen-
sors.

The low temperature trip limits are 50°F (turn off second-stage
cooling) and 45°F (turn off first-stage cooling) and cannot be
changed.

The second-stage high temperature trip limit can be pro-
grammed from 105°F to 155°F.

Table 6—Programmable Options-Settings

SETTING

NO.

SETTING NAME

VALUE

FACTORY

DEFAULT

S-1

4 Zone Controller Bus Address

4-64

4

S-2

Maximum Cooling Setpoint

80-95

85

S-3

Minimum Heating Setpoint

34-64

65

S-4

Maximum Damper Position

8-15

15

S-5

Ventilation/Minimum Damper Position

0-7

0

S-6

High Temperature Trip Limit

105-155

105

S-7

Dual Fuel Setpoint

0 or 10-60

0

12

Содержание COMFORT ZONE ZONEKIT4ZCAR

Страница 1: ...r Table 21 Wiring Diagrams 22 31 Configuration Table 32 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause fire electrical shock or other conditions...

Страница 2: ...to COM BUS a 3 wire cable must be separate from the 5 wire cable The thermostats should be located approximately 5 ft above floor and must be located within 200 ft of Comfort Zone Center SHIELDED CABL...

Страница 3: ...Level back plate and tighten screws Step 4 Install Zone Dampers IMPORTANT If conditions exist for possible condensing motor must be positioned for adequate draining See Fig 6 NOTE If a multi damper en...

Страница 4: ...All zone dampers and duct work must be properly supported according to local codes or SMACNA standards RECTANGULAR METAL DUCT WORK 1 Make connections using S lock and drives See Fig 10 2 Properly seal...

Страница 5: ...Installation Instructions packaged with barometric bypass Failure to properly install bypass damper can cause perma nent damage to the HVAC equipment For single speed furnace applications bypass air m...

Страница 6: ...ensor on room sensors Do not locate on an outside wall or next to a return air grill 1 Separate the 2 parts of sensor and mount back plate with provided flat head screw 2 Pull a 2 wire conductor throu...

Страница 7: ...HEAT 1 W1 HEAT 2 W2 FAN G RV COOL 0 OR RV HEAT B Power CHR 06 Communication Bus COMFORT ZONE I O R G W R G COMM BUS CONTROLLER COMM BUS HAM R W R W R W R W R W R W OAT LAT ZT4 ZT3 ZT2 SHIELD GROUND W...

Страница 8: ...TION OF A REFERENCE ZONE IN THE SYSTEM The first step in any heating or cooling cycle requires Comfort Zone to evaluate zones determine if heating or cooling is needed and select a Reference Zone The...

Страница 9: ...open The factory default is 15 The only time zone dampers will exceed this position is if system fan is off or zone dampers are being calibrated 2 The Minimum Damper Position rotary position number S...

Страница 10: ...4 are shown in Table 4 Under no circumstances may the W1 and Y1 contacts on the relay pack be jumpered together This is a common practice for many heat pump installations but will cause improper opera...

Страница 11: ...y may vary widely For residen tial application the need for System Mode Reselect is normally not frequent unless the building has unusual architectural features or problems with HVAC system High Low T...

Страница 12: ...the value of setting Press the COOL up or down setpoint buttons to change setting number and the HEAT up or down setpoint buttons to change value Refer to Table 6 for settings and their definitions 1...

Страница 13: ...L up or down setpoint buttons to change toggle number and the HEAT up or down setpoint buttons to change status of toggle See Table 11 Step 12 Wiring Diagrams Refer to Tables 7 and 8 for wiring diagra...

Страница 14: ...one at different times during the day and week See Fig 18 to become familiar with various parts of the 4 zone controller SYSTEM SWITCHES System switches select desired equipment operation Heat Switch...

Страница 15: ...ay whenever system is in this mode Set vacation mode setpoints Setting The Clock The clock display will normally show hour minutes AM or PM and day 1 Set minutes Press SELECT MIN HR DAY button once Pr...

Страница 16: ...eature can verify that each zone damper is operating properly by manually opening and closing each zone When rotary switch dial is moved onto another position Damper Service Mode will be cleared and c...

Страница 17: ...omfort Zone con troller detects and replaces faulty data contained within its memory with factory selected default values Transparent Errors Occur when Comfort Zone controller de tects a system or zon...

Страница 18: ...e and set points for zone 2 via the 3 wire communication bus at 1 ad dress below controller The system reads zone 2 temperature via the remote room sensor OFF T14 Smart Sensor Attached For Zone 3 The...

Страница 19: ...LEDs on the CHR06 relay pack are indicating the correct relay is closed If not check for a bad relay 2 Measure voltage across common red and any de energized relay Voltage should be 24 vac 3 Apply 24...

Страница 20: ...2 Configuration Error 1 Turn selection dial to position T2 T11 T12 T18 T20 T22 and T24 2 Check and correct the configuration 3 Return selection dial to any run mode position 13 Configuration Error 1 T...

Страница 21: ...ed or open 1 Check wiring and sensor 2 Replace failed sensor if necessary Valid temperature range 30 180 F 47 Bus Access Error Controller can not communicate on bus 1 Check 3 wire bus between controll...

Страница 22: ...296 UNIT 24 VAC R C 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE CENTER G W2 E...

Страница 23: ...itioner Continued A94034 E UNIT 24 VAC R 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFO...

Страница 24: ...ONER Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER W2 R C C Y Y2 W W1 G NOTE Locking furnace into low...

Страница 25: ...TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER G Y2 H R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK...

Страница 26: ...one Center to W2 on the furnace control board UNIT 24 VAC R C R Y1 L 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O...

Страница 27: ...T ZONE SYSTEM G C R Y W2 O W2 R C L B W3 E O Y1 Y Y2 A93243 UNIT 24 VAC R C 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL...

Страница 28: ...mp Continued UNIT 24 VAC R 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE SYSTEM G C R...

Страница 29: ...N position up when using Two Stage Relay Kit KGATT0101VSP Accessory Optional A93298 UNIT 24 VAC R Y W2 STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y...

Страница 30: ...OOL O RV HEAT O OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G Y1 R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK324 or Equivalent C F W2 O W Y RELAY COIL G r e e n P5 CONNECTION AT CONTROL BOARD Blac...

Страница 31: ...Configure the 4 Zone controller to act as if it were controlling a single speed heat pump Turn T 6 ON Turn T 9 T 26 OFF Set S 7 to 0 Let the 38YD perform the dual fuel optimization R W2 O W2 R G C W3...

Страница 32: ...Hz Operation OFF T25 Ventilation Mode OFF T26 Two Stage Heat Pump OFF T27 Dx Sensor For LAT Checking OFF T28 Cool Without Fan OFF SETTING S 1 4 Zone Controller Bus Address 04 S 2 Max Cooling Setpoint...

Отзывы: