Carrier Comfort 25HCD4 Скачать руководство пользователя страница 8

8

ELECTRICAL DATA

UNIT

SIZE

V/PH

OPER VOLTS*

COMPR

FAN

MCA

MIN

WIRE

SIZE†

MIN

WIRE

SIZE†

MAX

LENGTH

ft (m)‡

MAX

LENGTH

ft (m)‡

MAX

FUSE**

or CKT

BRK

AMPS

MAX

MIN

LRA

RLA

FLA

60° C

75° C

60° C

75° C

18

208/230/1

253

197

48.0

9.0

0.50

11.8

14

14

67

64

20

24

58.3

13.5

0.75

17.7

14

14

45

42

25

30

77.0

16.0

0.75

20.8

12

12

60

57

30

36

70.0

15.4

1.10

20.4

12

12

61

58

35

42

109.0

19.9

0.75

25.7

10

10

78

74

40

48

60

134.0

26.3

1.20

34.1

8

10

91

56

50

*

Permissible limits of the voltage range at which the unit will operate satisfactorily

{

If wire is applied at ambient greater than 30

_

C, consult table 310---16 of the NEC (NFPA 70). The ampacity of non---metallic---sheathed cable (NM),

trade name ROMEX, shall be that of 60

_

C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75

_

C

insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).

}

Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.

** Time---Delay fuse.

FLA

--- Full Load Amps

LRA

--- Locked Rotor Amps

MCA ---

Minimum Circuit Amps

RLA

--- Rated Load Amps

NOTE

: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.

All motors/compressors contain internal overload protection.

Complies with 2007 requirements of ASHRAE Standards 90.1

A--WEIGHTED SOUND POWER

UNIT SIZE

STANDARD

RATING

(dBA)

TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)

125

250

500

1000

2000

4000

8000

18

69

45.0

48.0

56.0

62.0

54.5

52.5

47.0

24

76

51.5

57.0

63.0

69.5

63.0

59.5

53.5

30

78

45.0

55.0

61.5

70.5

62.0

58.5

52.5

36

72

52.5

55.5

61.5

63.0

60.0

59.0

52.0

42

78

61.0

67.5

72.5

73.5

71.0

67.5

62.0

48
60

77

55.0

63.0

67.5

71.5

68.0

64.0

60.5

NOTE

: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

A--WEIGHTED SOUND POWER WITH SOUND HOOD

UNIT SIZE

STANDARD

RATING

(dBA)

TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)

125

250

500

1000

2000

4000

8000

18

68

46.5

48.0

56.0

60.5

54.5

51.5

45.5

24

76

52.0

57.5

63.0

68.0

62.5

58.5

52.5

30

76

45.5

54.5

61.0

68.5

60.5

57.5

52.0

36

72

52.5

54.0

61.5

62.0

59.0

57.5

51.5

42

78

60.5

68.0

72.5

73.0

71.0

67.5

61.5

48
60

74

55.0

63.5

67.0

69.0

66.5

62.0

57.0

NOTE

: Tested in accordance with AHRI Standard 270---08 (not listed in AHRI).

CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)

UNIT SIZE---SERIES

REQUIRED SUBCOOLING ° F (° C)

18

11 (6.1)

24

11 (6.1)

30

10 (5.6)

36

10 (5.6)

42

11 (6.1)

48
60

15 (8.3)

25H

C

D

4

Содержание Comfort 25HCD4

Страница 1: ...ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 14 SEER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 69 dB...

Страница 2: ...all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark...

Страница 3: ...Cooling Capacity Losses Puronr Refrigerant 1 Stage Heat Pump Applications Unit Nominal Size Btuh Maximum Liquid Line Diameters In OD Vapor Line Diameters In OD Cooling Capacity Loss Total Equivalent...

Страница 4: ...0 250 250 250 250 24000 HP with Puron 3 8 250 250 250 250 250 250 250 30000 HP with Puron 3 8 250 250 250 250 250 250 250 36000 HP with Puron 3 8 250 250 250 250 250 250 250 42000 HP with Puron 3 8 25...

Страница 5: ...X X X X X KSASH2101COP SOUND BLKT KIT X KSASF0101AAA SPRT FEET KIT X X X X X X KAATD0101TDR TIME DELAY KIT X X X X X X KSATX0201PUR TXV KIT X X X KSATX0301PUR TXV KIT X X KSATX0501PUR TXV KIT X x Acce...

Страница 6: ...mproves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all c...

Страница 7: ...allow for drainage from unit base Usage Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump ins...

Страница 8: ...TE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complies...

Страница 9: ...9 DIMENSIONS ENGLISH 25HCD4...

Страница 10: ...10 DIMENSIONS SI 25HCD4...

Страница 11: ...Y MBTUH 25HCD424A30 FB4CNF030 25HCD442A30 FB4CNF048 25HCD430A30 FB4CNF030 25HCD448A30 FB4CNF060 25HCD436A30 FB4CNF036 25HCD460A30 FX4DNF061 25HCD418A30 FB4CNF018 23 3 17 8 12 2 6 7 1 1 4 4 10 0 15 6 2...

Страница 12: ...2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well or...

Страница 13: ...TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD436 31 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD442 30 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD448 30 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25H...

Страница 14: ...r fan will be direct drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be c...

Страница 15: ...rconnecting refrigerant tube lengths greater than 80 ft 23 4 m and or elevation differences between indoor and outdoor units greater than 20 ft 6 1 m consult Residential Piping and Longline Guideline...

Страница 16: ...rp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 02 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HC...

Отзывы: