SYSTEM DESIGN SUMMARY

1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature without low--ambient operation accessory is 55

_

F (12.8

_

C).

3. Maximum outdoor operating air temperature for cooling mode is 125

_

F (51.7

_

C).

4. Minimum outdoor operating air temperature for heating mode is –30

_

F (–34.4

_

C).

5. Maximum outdoor operating air temperature for heating mode is 66

_

F (18.9

_

C).

6. For reliable operation, unit should be level in all horizontal planes.
7. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or elevation differences between indoor and outdoor units

greater than 20 ft (6.1 m), consult Residential Piping and Longline Guideline and Service Manual available from equipment distribut-
or.

8. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing

lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4

mm).

9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector

provided.

10. Do not apply capillary tube indoor coils to these units.
11. Factory--supplied filter drier must be installed.

25H

C

D

4

Содержание Comfort 25HCD4

Страница 1: ...ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 14 SEER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 69 dB...

Страница 2: ...all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark...

Страница 3: ...Cooling Capacity Losses Puronr Refrigerant 1 Stage Heat Pump Applications Unit Nominal Size Btuh Maximum Liquid Line Diameters In OD Vapor Line Diameters In OD Cooling Capacity Loss Total Equivalent...

Страница 4: ...0 250 250 250 250 24000 HP with Puron 3 8 250 250 250 250 250 250 250 30000 HP with Puron 3 8 250 250 250 250 250 250 250 36000 HP with Puron 3 8 250 250 250 250 250 250 250 42000 HP with Puron 3 8 25...

Страница 5: ...X X X X X KSASH2101COP SOUND BLKT KIT X KSASF0101AAA SPRT FEET KIT X X X X X X KAATD0101TDR TIME DELAY KIT X X X X X X KSATX0201PUR TXV KIT X X X KSATX0301PUR TXV KIT X X KSATX0501PUR TXV KIT X x Acce...

Страница 6: ...mproves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all c...

Страница 7: ...allow for drainage from unit base Usage Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump ins...

Страница 8: ...TE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complies...

Страница 9: ...9 DIMENSIONS ENGLISH 25HCD4...

Страница 10: ...10 DIMENSIONS SI 25HCD4...

Страница 11: ...Y MBTUH 25HCD424A30 FB4CNF030 25HCD442A30 FB4CNF048 25HCD430A30 FB4CNF030 25HCD448A30 FB4CNF060 25HCD436A30 FB4CNF036 25HCD460A30 FX4DNF061 25HCD418A30 FB4CNF018 23 3 17 8 12 2 6 7 1 1 4 4 10 0 15 6 2...

Страница 12: ...2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well or...

Страница 13: ...TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD436 31 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD442 30 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD448 30 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25H...

Страница 14: ...r fan will be direct drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be c...

Страница 15: ...rconnecting refrigerant tube lengths greater than 80 ft 23 4 m and or elevation differences between indoor and outdoor units greater than 20 ft 6 1 m consult Residential Piping and Longline Guideline...

Страница 16: ...rp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 02 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HC...

Отзывы: