background image

4

ALTERNATIVE

B

MODELS:  T036, T042, 
T048, AND T060 ONLY

ALTERNATIVE

A

ALTERNATIVE

C

WRONG

Field
Fabricated
Block-off
Plate

2 1/4” (57)

A08337

Fig. 4 -- Alternative Coil Mounting Positions

A

(Inside Opening)

Furnace Outlet

Front Bracket

Rear Bracket

Coil Casing Width

Side Bracket

Side Bracket

NOTE:

 Weld 3 places 

in 4 corners

2 1/4” (57)

19 1/2” (495)

(Outside)

3/4” (19)
Flanges
(Where Shown)

B

A97232

Fig. 5 -- Recommended Transition

Table 2 – Recommended Transitions

DIMENSIONS INCHES (mm)

A

B

12---3/4 (324)

17---1/2 (445)

16---1/16 (408)

21 (533)

19---9/16 (497)

24---1/2 (622)

STANDARD MODEL COIL APPLIED DIRECTLY ON TOP
AND OFFSET TO THE LEFT ON NARROW FURNACE

1. Notch support rail on underside of coil cabinet to provide

clearances for gas furnace flange. This rail is not visible

from front of coil. To locate position of notch, place coil dir-
ectly on top of gas furnace with overhanging portion en-
tirely on left side as in Fig. 4, Alternative C. Mark location

of gas furnace flange on coil casing. Remove coil from top
of furnace. Using tin snips, make a notch in rail large

enough to allow clearance for gas flow furnace flange.

2. Place coil on top of gas furnace. Make sure coil is shifted

completely to left side, and notch is sufficient so coil rests

on top of furnace cabinet.

3. Prepare and install block--off plate. See Fig. 4, Alternative

C. Using field--supplied sheet metal, cut a block--off plate to

be attached to bottom left side of coil casing. This plate pre-
vents air leakage from overhanging portion of coil. Attach

plate using sheet metal screws.

4. Continue with normal installation practices. See Connect

Refrigerant Piping.

Downflow Cased Coil Installation

1. Place N--coil on supply duct opening.
2. When coil width matches furnace width, furnace can be

placed directly on the cased coil.

NOTE

:

In downflow installation with a 4--way multipoise

furnace, break off perforated duct flanges on furnace. See Furnace
Installation Instructions.

CNP

VP

/CNR

VP

Содержание CNPVP, CNRVP

Страница 1: ...G signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation IMPORTANT Nitrogen can leak out through the hole that the needle pierced in the plugs This does not indicate ...

Страница 2: ...e coil or lack of air to a slab in the coil It is recommended that on this type of application a field supplied adapter be placed between the coil and furnace to allow air to distribute properly between all slabs of the coil To install cased coils in upflow applications follow the instructions below Upflow Cased Coil Installation To install cased coils in downflow applications follow the instructi...

Страница 3: ...ock off plates at casing base by removing 2 screws per plate from side of casing See Fig 3 Block Off Plates A05412 Fig 3 Block Off Plate Removal TRANSITION MODEL COILS APPLIED CENTERED OVER NARROW FURNACE 1 There is no transition required for this application 2 Remove coil from packaging and place on top of furnace with 1 5 8 41 mm overhang on both sides See Fig 4 Alternative A 3 Continue with nor...

Страница 4: ...on en tirely on left side as in Fig 4 Alternative C Mark location of gas furnace flange on coil casing Remove coil from top of furnace Using tin snips make a notch in rail large enough to allow clearance for gas flow furnace flange 2 Place coil on top of gas furnace Make sure coil is shifted completely to left side and notch is sufficient so coil rests on top of furnace cabinet 3 Prepare and insta...

Страница 5: ...ctions The coil can be connected to outdoor units using accessory tubing packages or field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line SUCTION LINE Suction line is designed for field sweat connection Line is plugged to keep out moisture and dirt Remove thes...

Страница 6: ...t for leaks and insulate traps and lines if located above a living area Consult local codes for additional restrictions or precautions Humidifier Application When installing a humidifier in a system which contains an N coil consideration must be given to location of coil slabs See Fig 9 1 Care must be taken to prevent damage of N coil when at taching humidifier to coil casing or plenum 2 The model...

Отзывы: