Carrier CNPVP, CNRVP Скачать руководство пользователя страница 2

2

Airflow

Airflow amount and distribution are vital to adequate system

performance. Problems that can be experienced with incorrect
airflow include:

S

low system performance

S

restricted TXV

S

frosted coil

S

poor humidity control

S

water blow--off

When attaching the coil and building the plenum, pay special

attention to the effect these details will have on airflow. After
system start--up, check the cfm to insure that it is correct.

(Generally, the cfm should be 350 to 400 cfm/ton during normal
cooling operation.)

TXV

A thermal expansion valve is utilized in this coil design to optimize

performance and comfort throughout the entire operating range of
the system. Special attention needs to be taken to the TXV when

installing the coil

S

Do not overheat valve. Temperatures that exceed 212

_

F (100

_

C)

can harm valve performance. Use a wet cloth or heat sink when
brazing.

S

Place liquid filter dryer near ID unit to reduce the risk of debris
clogging the valve.

S

Make sure TXV bulb is securely fastened and wrapped in the
indentation on vapor line tube.

CNPVP Models:
These coils have a factory--installed hard--shutoff TXV designed

only for use with R--410A refrigerant. Use only with outdoor units

designed for R--410A.

CNRVP Models:
These coils have a factory--installed hard--shutoff TXV designed

only for use with R--22 refrigerant. Use only with outdoor units
designed for R--22.

NOTE

: All TXV’S have preset superheat settings and are not

field--adjustable.

Cabinet Sweating

If this unit is installed in a garage, attic, or other unconditioned

space, special attention needs to be given to the potential of cabinet
sweating. A 6” (152 mm) wide piece of insulation should be

wrapped around the coil casing and supply duct connection point.

Inspect Equipment

File claim with shipper if equipment is damaged.

Select Installation Procedure

NOTE

: Installing coils rotated 90

_

from the front of the furnace,

in upflow or downflow applications, can cause water blow--off or
coil freeze--up due to the concentration of air on one slab of the coil
or lack of air to a slab in the coil. It is recommended that on this
type of application, a field--supplied adapter be placed between the
coil and furnace to allow air to distribute properly between all slabs
of the coil.
To install cased coils in upflow applications, follow the instructions

below,

Upflow Cased Coil Installation.

To install cased coils in downflow applications, follow the
instructions below,

Downflow Cased Coil Installation.

To install uncased coils in upflow applications, follow the
instructions below,

Upflow Uncased Coil Installation.

See Table 1 for dimensions and overhang options. Refer to

instructions for placement of coil casing on furnace

.

Table 1 – CNPVP/CNRVP CASED COIL INFORMATION

MODEL NUMBER

TONS

FLUSH FIT

TO FURNACE

WIDTH IN. (mm)

COIL

CONNECTION

TUBE SIZE

IN.

SHELF WIDTH

(See Fig. 1,

Dim. A)

IN. (mm)

FITS NEXT SMALLER FURNACE

Equal

Overhang

Overhang with

Transition

Offset Left

Liquid

Suction

*CN(P,R)VP1814A(C,T)A

1---1/2

14---3/16 (360)

3/8

5/8

12---7/8 (327)

---

---

---

*CN(P,R)VP2414A(C,T)A

2

14---3/16 (360)

3/8

5/8

12---7/8 (327)

---

---

---

CN(P,R)VP2417A(C,T)A

2

17---1/2 (445)

3/8

5/8

16---3/16 (411)

---

X

X

*CN(P,R)VP3014A(C,T)A

2---1/2

14---3/16 (360)

3/8

3/4

12---7/8 (327)

---

---

---

CN(P,R)VP3017A(C,T)A

2---1/2

17---1/2 (445)

3/8

3/4

16---3/16 (411)

---

X

X

*CN(P,R)VP3617A(C,T)A

3

17---1/2 (445)

3/8

3/4

16---3/16 (411)

---

X

X

*CN(P,R)VT3617A(C,T)A

3

17---1/2 (445)

3/8

3/4

16---3/16 (411)

X

---

---

CN(P,R)VP3621A(C,T)A

3

21 (533)

3/8

3/4

19---5/8 (498)

---

X

X

*CN(P,R)VP4221A(C,T)A

3---1/2

21 (533)

3/8

7/8

19---5/8 (498)

---

X

X

*CN(P,R)VT4221A(C,T)A

3---1/2

21 (533)

3/8

7/8

19---5/8 (498)

X

---

---

*CN(P,R)VP4821A(C,T)A

4

21 (533)

3/8

7/8

19---5/8 (498)

---

X

X

*CN(P,R)VT4821A(C,T)A

4

21 (533)

3/8

7/8

19---5/8 (498)

X

---

---

CN(P,R)VP4824A(C,T)A

4

24---1/2 (622)

3/8

7/8

23---1/8 (587)

---

X

X

*CN(P,R)VP6024A(C,T)A

5

24---1/2 (622)

3/8

7/8

23---1/8 (587)

---

X

X

*CN(P,R)VT6024A(C,T)A

5

24---1/2 (622)

3/8

7/8

23---1/8 (587)

X

---

---

* In these models the coil can be removed from the casing and installed as an uncased coil without needing to field fabricate the coil enclosure to prevent air bypass.

NOTES

:

For the 3rd digit position in the model number; P = Puron (R---410A) refrigerant and R=R---22
For the 5th digit position in the model number; P = painted cabinet, T = transition coil
For the 11th digit position in the model number; C = standard copper and T= tin plated copper

CNP

VP

/CNR

VP

Содержание CNPVP, CNRVP

Страница 1: ...G signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation IMPORTANT Nitrogen can leak out through the hole that the needle pierced in the plugs This does not indicate ...

Страница 2: ...e coil or lack of air to a slab in the coil It is recommended that on this type of application a field supplied adapter be placed between the coil and furnace to allow air to distribute properly between all slabs of the coil To install cased coils in upflow applications follow the instructions below Upflow Cased Coil Installation To install cased coils in downflow applications follow the instructi...

Страница 3: ...ock off plates at casing base by removing 2 screws per plate from side of casing See Fig 3 Block Off Plates A05412 Fig 3 Block Off Plate Removal TRANSITION MODEL COILS APPLIED CENTERED OVER NARROW FURNACE 1 There is no transition required for this application 2 Remove coil from packaging and place on top of furnace with 1 5 8 41 mm overhang on both sides See Fig 4 Alternative A 3 Continue with nor...

Страница 4: ...on en tirely on left side as in Fig 4 Alternative C Mark location of gas furnace flange on coil casing Remove coil from top of furnace Using tin snips make a notch in rail large enough to allow clearance for gas flow furnace flange 2 Place coil on top of gas furnace Make sure coil is shifted completely to left side and notch is sufficient so coil rests on top of furnace cabinet 3 Prepare and insta...

Страница 5: ...ctions The coil can be connected to outdoor units using accessory tubing packages or field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line SUCTION LINE Suction line is designed for field sweat connection Line is plugged to keep out moisture and dirt Remove thes...

Страница 6: ...t for leaks and insulate traps and lines if located above a living area Consult local codes for additional restrictions or precautions Humidifier Application When installing a humidifier in a system which contains an N coil consideration must be given to location of coil slabs See Fig 9 1 Care must be taken to prevent damage of N coil when at taching humidifier to coil casing or plenum 2 The model...

Отзывы: