48
PARAMETER
DESCRIPTION
VALUE
VALUE
FACTORY
SET
RANGE
ACCESS
LEVEL
DISPLAYED
MESSAGE
Hydraulic
configuration
0 = combi and flowswitch
1 = combi and flowmeter
2 = heating only with tank thermostat
3 = heating only with tank sensor and sliding outlet
4 = heating only with tank sensor and fixed outlet
BWC = 1
BWH = 2
[0:4]
INSTALLER HYDR. CFG
Gas Type
0 = Natural gas
1 = LP gas
0
[0:1]
INSTALLER GAS TYPE
Heating timer
0 = Active Timers
1 = Timers disabled
0
[0:1]
INSTALLER HEAT TIMER
DHW Thermostat
0 = Correlated Thermostat
1 = Absolute Thermostat
1
[0:1]
INSTALLER DHW
THERMO
System
0 = High Temperature
1 = Low Temperature
0
[0:1]
INSTALLER SYSTEM
Pre-Heating
0 = disabled
1 = enabled
0
[0:1]
USER
PREHEAT.
Combustion analysis 0 = disabled
1 = enabled (15 min)
0
[0:1]
INSTALLER -ACO-
Min DHW fan speed
see technical data table
[min:max]
INSTALLER MIN
Max DHW fan speed see technical data table
[min:max]
INSTALLER MAX
Max CH fan speed
see technical data table
[min:max]
INSTALLER MAX CH
MAX CH ADJ
see technical data table
[min:max]
INSTALLER RANGE RATE
Night Comp
0 = enabled
1 = disabled
0
[0:1]
INSTALLER NIGHT COMP
Outdoor reset
2
2
[1:3] High Temp
INSTALLER OTD CURVES
0.4
[0.2:0.8] Low Temp
Minimum DHW
Setpoint
100°F (37°C)
100°F
[100:120]
INSTALLER MINDHWSET
Maximum DHW
Setpoint
120°F (49°C)
120°F
[120:140]
INSTALLER MAXDHWSET
Minimum CH
Setpoint
68°F (20°C) High Temp
68°F (20°C) Low Temp
68°F
[68:180] High Temp
[68:113] Low Temp INSTALLER MINCHSET
Maximum
CH
Setpoint
180°F (82°C) High Temp
113°F (45°C) Low Temp
180°F
[68:180] High Temp
[68:113] Low Temp INSTALLER MAXCHSET
Reset flue hour
counter
0 = disabled
1 = enable (reset)
0
[0:1]
INSTALLER HOUR COUNT
Auxiliary output
0 = jumper X21.1-2 presence: W-R input active when
OT presence, jumper not present: second pump
handling enable.
1 = zone valve handling is enabled
2 = secondary pump handling is enabled
0
[0:2]
INSTALLER DO_AUX1
PARAMETER list
NOTICE:
Parameters should be verified for the application and boiler configuration if a PCB was replaced. See PCB replacement instructions.”
PARAMETER list for SERVICE
PARAMETER
DESCRIPTION
VALUE
VALUE
FACTORY SET
RANGE ACCESS
LEVEL
DISPLAYED
MESSAGE
Combustion Power
0 = 120 kBTU (32 kW)
150 kBTU or 120
kBTU (p
er rating
plate)
[0:2]
SERVICE
BOIL TYPE
1 = none
2 = 150 kBTU (42 kW)
Restore Combustion Offset Curve
0 = default
0
[0:1]
SERVICE
SET OFFS
1 = Enable Action
Reset Combustion Offset Curve
0 = default
0
[0:1]
SERVICE CLEAR OFFS
1 = Enable Action
Water flow switch type
0 = On-Off
0
[0:1]
SERVICE
LWCO
1 = Frequency
Filling Type
0 = manual
0
[0:1]
SERVICE
FILL TYPE
1 = semi-automatic
Force Automatic Calibration (*)
0 = disabled
0
[0:2]
SERVICE
FORCE CAL.
1 = enabled with offset restored
2 =
enabled with offset resetted
Call for service
0=1=disabled
2
[0:2]
SERVICE
CALL SRV
2=enabled
Service expire
Number of weeks
52
[0:255]
SERVICE
SRV EXPIRY
(*) reset = original curve (factory set) - restore= current curve. We suggest to set this parameter, first commissioning done, to 1 in case of gas valve, electrode and main PCB substitution