32
AFTER 20 SECOND
IGNITER WARM UP, GAS
VALVE IS ENERGIZED
VALVE LIGHT ON.
1 SECOND LATER POWER
IS REMOVED FROM
IGNITER/SENSOR
POWER LIGHT IS OFF.
DOES MAIN BURNER LIGHT?
TROUBLESHOOTING CHART 4
CHART 3
YES
IGNITER/SENSOR WARMS
UP AND GLOWS YELLOW/
ORANGE DURING 20
SECOND WARM UP
CHECK FOR 120 VAC
BETWEEN TERMINALS 1
AND 2 AT CONNECTOR
CN1 ON IBC (DURING
IGNITER WARM UP)
CHECK FOR 120 VAC AT
IGNITER/SENSOR LEADS
ON WIRING HARNESS
(DURING IGNITER
WARM UP)
CHECK FOR 24 VAC
ACROSS TERMINALS MV
ON THE GAS
CONTROL. WHILE VALVE/
FLAME INDICATOR LIGHT
IS ON
REPLACE IBC
REPAIR/REPLACE WIRING
FROM IBC TO IGNITER/
SENSOR
REPLACE IGNITER/SENSOR
CHECK FOR 24 VAC
ACROSS TERMINALS
CN6-Z AND CN6-5 ON
IBC, WHILE THE VALVE/
FLAME LED IS LIT
REPAIR/REPLACE WIRING
BETWEEN IBC AND
GAS CONTROL
REPLACE IBC
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
CHART 5
CHART 5
YES
YES
YES
CHECK IF IGNITER/
SENSOR POSITION IS OK?
TIP SHOULD BE SLANTED
TOWARDS BURNER
RESTORE IGNITER/SENSOR
TO CORRECT POSITION
DO NOT RELOCATE
CHECK GAS SUPPLY
PRESSURE AT INLET
PRESSURE TAPPING ON
GAS CONTROL. IS GAS
PRESSURE GREATER
THAN 4.0" W.C.?
ARE ALL MANUAL SHUT-
OFFS IN THE GAS
SUPPLY LINE AND ON
THE GAS CONTROL IN
THE OPEN OR ON
POSITION?
CONTACT THE GAS
UTILITY TO TURN THE
GAS ON
OPEN OR TURN ON ALL
MANUAL SHUTOFFS
TROUBLESHOOTING
A04072
Fig. 30
---
Troubleshooting Chart No. 4