HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (L/s) x
TEMP. DIFF. (DEG. C) x
FLUID FACTOR* =
(kW)
SUPERHEAT
= SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
(DEG C)
SUBCOOLING
= DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG C)
*Use 500 for water, 485 for antifreeze.