16
Table 3 — 50VQP Unit Electrical Data — Standard Unit
LEGEND
NOTES:
1. HACR circuit breaker in U.S.A. only.
2. All fuses Class RK-5.
Table 4 — 50VQP Unit Electrical Data — Dual Point Power Unit
LEGEND
NOTES:
1. HACR circuit breaker in U.S.A. only.
2. All fuses Class RK-5.
50VQP UNIT
SIZE
VOLTAGE
(V-Ph-Hz)
MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR
FAN
MOTOR
FLA
TOTAL UNIT
FLA
MCA
MAX FUSE/
HACR
qty
RLA
LRA
084
380/420-3-50
360/440
A,B,C
1
11.2
75.0
1.8
13.0
15.8
25
E
1
11.2
75.0
2.5
13.7
16.5
25
096
380/420-3-50
360/440
A,B,C
1
12.2
101.0
2.5
14.7
17.8
25
120
380/420-3-50
360/440
A,B,C
1
16.7
111.0
3.6
20.3
24.5
40
E
1
16.7
111.0
4.9
21.6
25.8
40
150
380/420-3-50
360/440
A,B,C
1
18.6
118.0
4.9
23.5
28.2
45
E
1
18.6
118.0
7.8
26.4
31.1
45
168
380/420-3-50
360/440
A,B,C
2
11.2
75.0
3.4
25.8
28.6
35
192
380/420-3-50
360/440
A,B,C
2
12.2
101.0
4.9
29.3
32.3
40
240
380/420-3-50
360/440
A,B,C
2
16.7
111.0
7.8
41.2
45.4
60
300
380/420-3-50
360/440
A,B,C
2
18.6
118.0
7.8
45.0
49.7
60
E
2
18.6
118.0
12.2
49.4
54.0
70
FLA
—
Full Load Amps
HACR —
Heating, Air Conditioning, and Refrigeration
LRA
—
Locked Rotor Amps
MCA —
Minimum Circuit Amps
RLA
—
Rated Load Amps
50VQP
UNIT
SIZE
VOLTAGE
(V-Ph-Hz)
MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR
EMERGENCY POWER SUPPLY
qty RLA LRA
TOTAL
COMP FLA
COMP
MCA
COMP
MAX FUSE
FAN MOTOR
FLA
FAN
MCA
FAN
MAX FUSE
084
380/420-3-50
360/440
A,B,C
1
11.2 75.0
11.2
14.0
25
1.8
2.3
15
E
1
11.2 75.0
11.2
14.0
25
2.5
3.1
15
096
380/420-3-50
360/440
A,B,C
1
12.2 101.0
12.2
15.3
25
2.5
3.1
15
120
380/420-3-50
360/440
A,B,C
1
16.7 111.0
16.7
20.9
35
3.6
4.5
15
E
1
16.7 111.0
16.7
20.9
35
4.9
6.1
15
150
380/420-3-50
360/440
A,B,C
1
18.6 118.0
18.6
23.3
40
4.9
6.1
15
E
1
18.6 118.0
18.6
23.3
40
7.8
9.8
15
168
380/420-3-50
360/440
A,B,C
2
11.2 75.0
22.4
25.2
35
3.4
4.3
15
192
380/420-3-50
360/440
A,B,C
2
12.2 101.0
24.4
27.4
35
4.9
6.1
15
240
380/420-3-50
360/440
A,B,C
2
16.7 111.0
33.4
37.6
50
7.8
9.8
15
300
380/420-3-50
360/440
A,B,C
2
18.6 118.0
37.2
41.9
60
7.8
9.8
15
E
2
18.6 118.0
37.2
41.9
60
12.2
15.3
25
FLA
—
Full Load Amps
HACR —
Heating, Air Conditioning, and Refrigeration
LRA
—
Locked Rotor Amps
MCA —
Minimum Circuit Amps
RLA
—
Rated Load Amps