20
NOTES: 1. SEE UNIT
NAMEPLA
TE FOR ELECTRICAL
RA
TING.
2.
ALL
FIELD WIRING MUST
BE IN
ACCORDANCE WITH NEC-NFP
A #70, COPPER CONDUCT
ORS ONL
Y.
3. 208/230V UNITS
ARE F
ACT
OR
Y WIRED FOR 230V OPERA
TION. FOR 208V OPERA
TION, REMOVE LEAD
FROM 240
TERMINAL
AND CONNECT
IT
T
O
208. CAP
ALL
UNUSED
TERMINALS.
4. FOR
AL
TERNA
TIVE EMS COIL
VOL
TAGES CONSUL
T F
ACT
OR
Y.
5. UPM-1 INCLUDES BUIL
T IN: 270-300 SECOND RANDOM ST
AR
T
300 SECOND DELA
Y ON BREAK
120 SECOND LOW PRESSURE BYP
ASS
6. “TEST” DIP
SWITCH REDUCES DELA
YS
TO
10 SEC WHEN SET
T
O
YES. MUST
BE SET
T
O
“NO” FOR NORMAL
OPERA
TION.
7. “FREEZE SENSOR” ON CONDENSER WILL
OPERA
TE
AT
26 F BY
DEF
AUL
T,
IF 15 F OPERA
TION IS REQUIRED JUMPER R30 MUST
BE CUT
.
IF FREEZE SENSOR IS NOT
INST
ALLED
A JUMPER SHALL
BE INST
ALLED BETWEEN
THE FREEZE1 OR FREEZE2 SENSOR
TERMINALS.
8. “ALARM OUTPUT” DIP
SWITCH MUST
BE SET
T
O
“PULSE” IF BLINKING
T-ST
AT
SER
VICE LIGHT
IS DESIRED.
9. DEF
AUL
T SETTINGS FOR DELUXE D BOARD FROM F
ACT
OR
Y SHOWN.
10.
ALARM OUTPUT
IS NORMALL
Y OPEN (NO) DR
Y CONT
ACT
. IF 24 V
AC IS NEEDED, CONNECT
R
TO
ALR-COM
TERMINAL. 24 V
AC WILL
BE SENSED
ON
THE
ALR-OUT
WHEN
THE UNIT
IS IN
ALARM CONDITION. OUTPUT
WILL
BE PULSED IF PULSE IS SELECTED.
11. F
ACT
OR
Y-MOUNTED LOOP
PUMP
OR
TWO-W
AY
W
ATER V
A
LVE. BOTH DEVICES WILL
NOT
BE PRESENT
IN
THE SAME UNIT
.
12. PUMP
MOT
OR IS WIRED BETWEEN LINE
AND NEUTRAL
FOR 380-460V
AC UNITS. FOR 208-230V
AC UNITS PUMP
MOT
OR IS WIRED BETWEEN LINES.
13. EON MOT
OR IS WIRED BETWEEN LINE
AND NEUTRAL
FOR 380-460V
AC UNITS. FOR 208/230V
AC UNITS WON MOT
OR IS WIRED BETWEEN LINES.
14. BCA
CONT
ACTS R-Y
OPEN ON DROP
IN W
ATER
TEMPERA
TURE
AND R-B CLOSE.
DELUXE D
Fig. 17 —
Constant Airflow
ECM Motor, Three Ph
ase/Sing
le Stage Two
Ste
p, Deluxe
D Control