4
Table 1 —
Physical Data
007-024
50PS UNIT SIZE
007
009
012
015
018
024
Compressor Type
Rotary
Scroll
Maximum Water Working Pressure (psig)
400
a
NOTE(S):
a. 300 psig when unit is built with the 2-way solenoid valve option.
Standard Fan Motor and Blower
Fan Motor Type
PSC
ECM Constant Torque
Fan Motor (hp)
1/10
1/10
1/10
1/3
1/3
1/2
b
/ 1/3
b. 2 ton units at 460v and Constant Torque ECM motor will have a 1/2 HP fan motor rather than a 1/3 HP motor.
Blower Wheel Size (Diameter x Width) (in.)
4.5 x 4.5
4.5 x 4.5
5.5 x 5.5
5.5 x 4.5
9 x 7
9 x 7
ECM Const CFM Fan Motor
Fan Motor Type
NA
NA
NA
ECM Constant CFM
Fan Motor (hp)
NA
NA
NA
1/3
1/3
1/3
Water Connection Size
FPT (in.)
3/4
3/4
3/4
3/4
3/4
3/4
Coaxial Coil Volume (gal.)
0.15
0.15
0.31
0.31
0.31
0.48
Vertical Cabinet
Refrigeration Charge (oz)
31
31
30
46
34
65
Air Coil Dimensions (H x L) (in.)
12 x 16.5
12 x 16.5
16 x 16.5
16.5 x 20
16.5 x 20
24 x 21
Standard Filter - 1-in. Throwaway (H x L) (in.)
15 x 20
15 x 20
18 x 20
20 x 20
20 x 20
24 x 24
Operating Weight (lb)
140
154
166
191
195
229
Shipping Weight (lb)
160
174
186
208
212
242
Horizontal Cabinet
Refrigeration Charge (oz)
31
31
35
35
35
65
Air Coil Dimensions (H x L) (in.)
12 x 16.5
12 x 16.5
16 x 16.5
18 x 18.5
18 x 18.5
18 x 28
Standard Filter - 1-in. Throwaway (H x L) (in.)
15 x 20
15 x 20
18 x 20
18 x 20
18 x 20
20 x 30
Operating Weight (lb)
165
172
173
190
198
307
Shipping Weight (lb)
185
192
205
218
222
340
030-070
50PS UNIT SIZE
030
036
042
048
060
070
Compressor Type
Scroll
Maximum Water Working Pressure (psig)
400
Standard Fan Motor and Blower
Fan Motor Type
ECM Constant Torque
Fan Motor (hp)
1/2
3/4
3/4
3/4
1
1
Blower Wheel Size (Diameter x Width) (in.)
9 x 7
9 x 7
10 x 8
10 x 8
11 x 9
11 x 9
ECM Const CFM Fan Motor
Fan Motor Type
ECM Constant CFM
Fan Motor (hp)
1/2
3/4
3/4
3/4
1
1
Water Connection Size
FPT (in.)
1
1
1
1
1
1
Coaxial Coil Volume (gal.)
0.39
0.62
0.62
0.62
0.62
0.85
Vertical Cabinet
Refrigeration Charge (oz)
71
65 Cu / 68 CuNi 83 Cu / 86 CuNi 83 Cu / 86 CuNi 90 Cu / 93 CuNi
127
Air Coil Dimensions (H x L) (in.)
24 x 27
24 x 27
32 x 27
32 x 27
40 x 27
40 x 27
Standard Filter - 1-in. Throwaway (H x L) (in.)
24 x 30
24 x 30
16 x 30 (2)
16 x 30 (2)
20 x 30 (2)
20 x 30 (2)
Operating Weight (lb)
269
281
334
340
396
444
Shipping Weight (lb)
292
304
360
366
422
470
Horizontal Cabinet
Refrigeration Charge (oz)
71
65 Cu / 68 CuNi 83 Cu / 86 CuNi 83 Cu / 86 CuNi 90 Cu / 93 CuNi
127
Air Coil Dimensions (H x L) (in.)
20 x 32.5
20 x 32.5
20 x 43.25
20 x 43.25
20 x 54
20 x 54
Standard Filter - 1-in. Throwaway (H x L) (in.)
20 x 34.5
20 x 34.5
20 x 24 (2)
20 x 24 (2)
20 x 28 (2)
20 x 28 (2)
Operating Weight (lb)
358
369
400
405
452
494
Shipping Weight (lb)
404
415
465
470
520
562
LEGEND
ECM
— Electronically Commutated Motor
NA
— Not Applicable
PSC
— Permanent Split Capacitor
Содержание AQUAZONE 50PSH
Страница 17: ...17 Fig 15 PSC Motor Single Phase Single Stage WSHP Open Control ...
Страница 20: ...20 Fig 18 Constant Torque Motor Single Phase Single Stage WSHP Open Control ...
Страница 23: ...23 Fig 21 Constant Airflow Single Phase WSHP Open ...
Страница 26: ...26 Fig 24 PSC Motor Three Phase Single Stage WSHP Open ...
Страница 29: ...29 Fig 27 Constant Torque Motor Three Phase Single Stage WSHP Open ...
Страница 32: ...32 Fig 30 Constant Airflow Motor Three Phase Single Stage WSHP Open ...