![Carrier AQUAZONE 50HQL072-120 Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/carrier/aquazone-50hql072-120/aquazone-50hql072-120_installation-start-up-and-service-instructions-manual_2563393029.webp)
29
Table 14 — 50VQL240 Blower Performance Data
LEGEND
NOTES:
1. Bold numbers require 3 horsepower motor.
2. Values are per blower and motor; 2 blower and motors required.
3. Due to alternate sheaves, ‘Turns Open’ may vary within ±0.5 turn from the posi-
tion shown above.
4. Units factory shipped with standard static sheave and drive at 2.5 turns open
(8000 cfm at 0.5 in. wg ESP Wet Coil). Other speeds require field selection.
5. ISO/ARI rating point with standard static sheave and drive at 2 turns open
(8000 cfm at 0.6 in. wg ESP Wet Coil). Other speeds require field selection.
6. For applications requiring higher static pressures, contact your local
representative.
7. Performance data does not include drive losses and is based on sea level
conditions.
8. Do not operate in gray region.
9. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v for
208-230-v units.
10. For wet coil performance first calculate the face velocity of the air coil (Face
Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for velocities of 200 fpm
reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by
0.12 in. wg and 500 fpm by 0.16 in. wg.
Table 15 — 50VQL300 Blower Performance Data
LEGEND
NOTES:
1. Values are per blower and motor; 2 blower and motors required.
2. Due to alternate sheaves, ‘Turns Open’ may vary within ±0.5 turn from the posi-
tion shown above.
3. Units factory shipped with standard static sheave and drive at 2.5 turns open
(9000 cfm at 0.4 in. wg ESP Wet Coil). Other speeds require field selection.
4. ISO/ARI rating point with standard static sheave and drive at 2 turns open
(9000 cfm at 0.42 in. wg ESP Wet Coil). Other speeds require field selection.
5. For applications requiring higher static pressures, contact your local representative.
6. Performance data does not include drive losses and is based on sea level
conditions.
7. Do not operate in gray region.
8. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v for
208-230-v units.
9. For wet coil performance first calculate the face velocity of the air coil (Face
Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for velocities of 200 fpm
reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by
0.12 in. wg and 500 fpm by 0.16 in. wg.
RATED
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
5600
BHP
0.53
0.60
0.67
0.74
0.81
0.87
0.94
1.01
1.08
1.15
1.21
1.28
1.35
RPM
569
606
642
676
709
741
771
801
830
857
884
910
936
Turns Open
4
3
2.5
1.5
4.5
4
3.5
2.5
2
1.5
1
0.5
0
6000
BHP
0.54
0.60
0.67
0.74
0.82
0.89
0.98
1.06
1.16
1.22
1.29
1.36
1.43
1.50
RPM
546
583
619
654
687
719
750
780
809
837
864
891
916
941
Turns Open
4.5
4
3
2
1
4.5
4
3
2.5
2
1.5
1
0.5
0
6400
BHP
0.62
0.68
0.75
0.82
0.90
0.98
1.06
1.15
1.24
1.34
1.43
1.51
1.58
1.65
RPM
561
597
632
666
698
729
759
789
817
844
871
897
922
947
Turns Open
4.5
3.5
2.5
1.5
1
4
3.5
3
2.5
2
1.5
1
0.5
0
6800
BHP
0.70
0.77
0.84
0.91
0.99
1.07
1.16
1.24
1.33
1.42
1.50
1.58
1.67
1.75
RPM
576
611
645
677
709
739
769
797
825
852
878
904
929
953
Turns Open
4
3
2
1.5
4.5
4
3.5
3
2.5
1.5
1
0.5
0
2
7200
BHP
0.73
0.80
0.87
0.94
1.01
1.09
1.17
1.26
1.35
1.44
1.53
1.63
1.69
1.74
1.80
RPM
557
592
625
658
689
720
750
778
806
833
860
886
911
935
959
Turns Open
4.5
3.5
2.5
2
1
4.5
4
3
2.5
2
1.5
1
0.5
0
2
7600
BHP
0.83
0.90
0.97
1.05
1.12
1.20
1.29
1.37
1.46
1.55
1.65
1.75
1.85
1.95
2.06
RPM
575
608
640
672
702
732
760
788
816
842
868
894
918
943
966
Turns Open
4
3
2.5
1.5
4.5
4
3.5
3
2.5
2
1.5
1
0.5
2
1.5
8000
BHP
0.87
0.94
1.01
1.09
1.16
1.24
1.33
1.41
1.50
1.59
1.68
1.78
1.88
1.98
2.08
2.19
RPM
560
593
624
656
686
715
744
772
799
826
852
878
902
927
951
974
Turns Open
4.5
3.5
2.5
2
1
4.5
4
3.5
3
2
1.5
1
0.5
2.5
2
1.5
8400
BHP
0.99
1.07
1.14
1.22
1.29
1.38
1.46
1.55
1.63
1.73
1.82
1.92
2.02
2.12
2.23
2.34
RPM
580
611
642
672
701
729
757
785
811
837
863
888
912
936
960
983
Turns Open
4
3
2.5
1.5
4.5
4
3.5
3
2.5
2
1.5
1
2.5
2
2
1.5
8800
BHP
1.13
1.20
1.28
1.36
1.44
1.52
1.61
1.69
1.79
1.88
1.98
2.07
2.17
2.28
2.39
2.49
RPM
601
631
660
689
717
745
772
798
824
850
875
899
923
947
970
993
Turns Open
3.5
2.5
2
1
4.5
4
3.5
3
2.5
2
3.5
3
2.5
2
1.5
1
9200
BHP
1.27
1.35
1.43
1.51
1.59
1.68
1.77
1.86
1.95
2.05
2.14
2.25
2.35
2.45
2.56
2.67
RPM
623
652
680
707
734
761
787
813
839
864
888
912
936
959
981
1003
Turns Open
2.5
2
1.5
4.5
4
3.5
3
2.5
4
3.5
3
2.5
2
2
1.5
1
A
—
Standard Static Sheave/Standard Motor
B
—
Low-Static Sheave/Standard Motor
C
—
High-Static Sheave/Standard Motor
E
—
High-Static Sheave/Large Motor
ARI
—
Air Conditioning and Refrigeration Institute
BHP
—
Brake Horsepower
ESP
—
External Static Pressure
ISO
—
International Organization for Standardization
RPM
—
Revolutions Per Minute
RATED
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
7,400
BHP
1.25
1.33
1.42
1.52
1.61
1.71
1.81
1.92
2.03
2.14
2.25
RPM
761
789
817
843
869
895
920
944
968
991
1014
Turns Open
4.5
3.5
3
2.5
2
1.5
0.5
0
2.5
2
1.5
7,800
BHP
1.31
1.40
1.49
1.58
1.67
1.77
1.87
1.97
2.08
2.19
2.30
2.42
RPM
755
783
810
837
862
888
913
937
961
984
1007
1029
Turns Open
4.5
4
3
2.5
2
1.5
1
0.5
0
2.5
1.5
1
8,200
BHP
1.39
1.47
1.56
1.65
1.74
1.84
1.94
2.04
2.15
2.25
2.37
2.48
2.60
RPM
749
777
804
830
856
881
906
930
954
977
1000
1022
1044
Turns Open
4.5
4
3.5
3
2
1.5
1
0.5
0
2.5
2
1.5
1
8,600
BHP
1.55
1.64
1.73
1.82
1.92
2.02
2.12
2.22
2.33
2.44
2.55
2.67
2.78
RPM
771
798
824
849
875
899
923
947
970
993
1015
1037
1058
Turns Open
4
3.5
3
2.5
2
1
0.5
0
2.5
2
1.5
1
0.5
9,000
BHP
1.64
1.73
1.82
1.91 2.01
2.11
2.21
2.31
2.41
2.52
2.63
2.75
RPM
766
792
818
843
868
893
917
941
964
986
1008
1030
Turns Open
4.5
3.5
3
2.5
2
1.5
1
0.5
2.5
2
1.5
1
9,400
BHP
1.74
1.83
1.92
2.01
2.10
2.20
2.30
2.41
2.51
2.62
2.73
2.84
RPM
761
787
813
838
863
887
911
935
958
980
1002
1024
Turns Open
4.5
4
3
2.5
2
1.5
1
0.5
0
2.5
2
1.5
9,800
BHP
1.84
1.93
2.02
2.12
2.21
2.31
2.41
2.51
2.62
2.72
2.83
RPM
757
783
808
833
858
882
906
929
952
974
996
Turns Open
4.5
4
3.5
2.5
2
1.5
1
0.5
0
2.5
2
10,200
BHP
2.04
2.14
2.23
2.33
2.43
2.53
2.63
2.73
RPM
779
804
829
853
877
901
924
947
Turns Open
4
3.5
3
2.5
1.5
1
0.5
0
10,600
BHP
2.26
2.36
2.45
2.55
2.65
2.76
2.86
RPM
801
825
849
873
896
919
942
Turns Open
3.5
3
2.5
2
1.5
1
0
A
—
Standard Static Sheave/Standard Motor
C
—
High-Static Sheave/Large Motor
ARI
—
Air Conditioning and Refrigeration Institute
BHP
—
Brake Horsepower
ESP
—
External Static Pressure
ISO
—
International Organization for Standardization
RPM
—
Revolutions Per Minute
B
A
C
A
E
C