46
K. Electrical Requirements:
1. Unit primary electrical power supply shall enter
the unit at a single location.
2. Primary electrical power supply shall be rated to
withstand 120 F (50 C) operating ambient.
3. Unit shall operate on 3-phase power at the volt-
age shown in the equipment schedule.
4. Control points shall be accessed through termi-
nal block.
5. Unit shall be shipped with factory control and
power wiring installed.
6. Accessory storage tank cooler heater requires a
separate power source.
L. Chilled Water Circuit:
1. Chilled water circuit shall be rated for 300 psig
(2068 kPa). Units with optional pump package
are rated for 150 psig (1034 kPa) working
pressure.
2. Solid-state flow monitor with integral relay shall
be factory installed and wired.
3. Brass body strainer with 20 mesh screen and
ball type blow down.
4. Optional hydronic package:
a. Field pipe connections shall be copper FTP
type.
b. Optional single or primary/stand-by opera-
tion pump systems. Dual pump systems shall
have a pump discharge check valve.
c. Pumps shall be single stage design, for instal-
lation in vertical position and capable of
being serviced without disturbing piping
connections.
1) Pump casing shall be of class 30 cast
iron.
2) The impeller shall be of cast bronze,
closed type, dynamically balanced,
keyed to the shaft and secured by lock-
ing cap screw.
3) The hydronic kit will be provided with
a flush line connection to ensure lubrica-
tion at the seal face and allow for
positive venting of the seal chamber.
4) Pump shall be rated for 150 psig
(1034 kPa) working pressure.
5) The pump case shall have gage tappings
at the suction and discharge nozzles and
include drain ports.
6) Motors shall totally enclosed 3-phase
type with grease lubricated ball bearings.
7) Each pump shall be factory tested per
Hydraulic Institute Standards.
d. Fluid expansion tank shall be factory
installed within the chiller cabinet insulates,
pre-charged and rated for a maximum work-
ing pressure of 150 psig (1034 kPa).
e. Water pressure taps (2) shall be factory
installed across the cooler and rated for
150 psig (1034 kPa).
f. Balancing valve shall be factory installed to
set flow gage ports shall be factory installed
and rated for 300 psig (2068 kPa).
g. Hydronic assembly shall have factory
supplied electric freeze protection to –20 F
(–29 C) when optional heaters are used.
h. Piping shall be type-L seamless copper
tubing.
M. Special Features:
Certain standard features are not applicable when
the features designated by * are specified. For assis-
tance in amending the specifications, contact your
Carrier representative.
* 1. Low-Ambient Operation:
Unit shall be capable of operating down to
–20 F (–29 C) with the addition of the field or
factory-installed solid-state Motormaster
®
V
control with condenser coil temperature sensor.
In addition, adequate field-supplied antifreeze
with suitable corrosion inhibitor protection shall
be field-installed in the evaporator circuit. Addi-
tional components shall be required and used in
conjunction with the low ambient device. Com-
ponents include field-installed wind baffles, min-
imum load control, and accessory liquid line
solenoid.
2. Non-Fused Disconnect:
Unit shall be supplied with factory-installed,
non-fused electrical disconnect for main power
supply.
3. Optional Condenser Coil Materials:
a. Pre-coated aluminum-fin coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
coastal environments. Coating shall be
applied to the aluminum fin stock prior to
the fin stamping process to create an inert
barrier between the aluminum fin and cop-
per tube. Epoxy-phenolic barrier shall mini-
mize galvanic action between dissimilar
metals.
b. Copper-fin coils:
Shall be constructed of copper fins mechani-
cally bonded to copper tubes and copper
tube sheets. Galvanized steel tube sheets
shall not be acceptable. A polymer strip shall
prevent coil assembly from contacting sheet
metal coil pan to minimize potential for gal-
vanic corrosion between the coil and pan.
All copper construction shall provide protec-
tion in moderate coastal applications.
c. E-coated aluminum-fin coils:
Shall have a flexible epoxy polymer coating
uniformly applied to all coil surface areas
Guide specifications (cont)
Содержание AQUASNAP JUNIOR 30RA015
Страница 16: ...16 Dimensions storage tank 30RA010 018 a30 4603 ...
Страница 17: ...17 Dimensions storage tank 30RA022 030 a30 4604 ...
Страница 18: ...18 Dimensions storage tank 30RA035 055 a30 4605 ...
Страница 37: ...37 Typical control wiring schematic storage tank FIELD POWER SUPPLY 230 1 60 ...