28
Typical piping and wiring
AIR FLOW
FIELD
POWER
SUPPLY
DRAIN
FLOW
GATE
VALVE
VIBRATION
ELIMINATOR
VALVE
PRESSURE
GAGE
SHUT OFF
VALVES
HEAT TAPE INSULATION IS RECOMMENDED ON ALL EXPOSED PIPING
IF AMBIENT TEMPERATURE <32 F (0
°
C) AND NO ANTIFREEZE SOLUTION IS IN SYSTEM
CONTROL
WIRING
TO
EXPANSION
TANK
PUMP
AIR FLOW
FIELD
POWER
SUPPLY
DRAIN
FLOW
GATE
VALVE
VIBRATION
ELIMINATOR
NOTE 5
HEAT TAPE INSULATION IS RECOMMENDED ON ALL EXPOSED PIPING
IF AMBIENT TEMPERATURE <32 F (0
°
C) AND NO ANTIFREEZE SOLUTION IS IN SYSTEM
CONTROL
WIRING
30RA UNITS WITHOUT HYDRONIC PACKAGE
30RA UNITS WITH HYDRONIC PACKAGE
NOTES:
1. Chiller must
b
e installed level to within
1
/
8
in. per foot (10.4 mm per meter) to maintain proper compressor oil return and hydraulics.
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping shown are
for a quick overview of system and are not in accordance with recognized standards.
3. All wiring must comply with applica
b
le local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) hand
b
ook for details.
LEGEND
Airflow Through Condenser
Power Wiring
Chilled Water Piping
LEGEND
Airflow Through Condenser
Power Wiring
Chilled Water Piping
NOTES:
1. Chiller must
b
e installed level to within
1
/
8
in. per foot (10.4 mm per meter) to maintain proper compressor oil return and hydraulics.
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping shown are for a
quick overview of system and are not in accordance with recognized standards.
3. All wiring must comply with applica
b
le local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) hand
b
ook for details.
5. Air separator required as close to chiller as possi
b
le (except primary/secondary systems).