5 - ELECTRICAL DATA
61AF - Standard unit (without hydraulic module)
022
030
035
045
055
075
105
Power circuit
Nominal power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V, via internal transformer
Maximum start-up current (Un)
(1)
Standard unit
A
104
102
130
170
201
157
241
Unit with electronic starter option
A
56
55
70
91
101
101
142
Unit power factor at maximum capacity
(2)
0,82
0,82
0,82
0,82
0,82
0,82
0,82
Maximum unit power input
(2)
kW
9
12
15
19
23
30
46
Nominal unit current draw
(3)
A
14
16
20
23
28
40
55
Maximum unit current draw (Un)
(4)
A
16
20
26
32
38
53
76
Maximum unit current draw (Un-10%)*
A
18
22
29
35
42
57
83
Customer-side unit power reserve
Customer reserve at the 24 V control power circuit
Short-circuit stability and protection
See table on the next page
(1) Maximum instantaneous start-up current (maximum operating current of the comp fan c locked rotor current of the compressor).
(2) Power input, compressor and fan, at the unit operating limits (saturated suction temperature 10 °C, saturated condensing temperature 65 °C) and nominal voltage of
400V (data given on the unit nameplate).
(3) Standardised Eurovent conditions: evaporator entering/leaving water temperature 40 °C/45 °C, outside air temperature db/wb = 7 °C/6 °C.
(4) Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate).
*
Maximum unit operating current at maximum unit power input and 360 V.
5.1 - Compressor usage and electrical data for standard units
Compressor
I Nom
I Max
I Max
LRA
(1)
LRA
(2)
Cosine
22
30
35
45
55
75
105
(Un)
(Un-10 %)
A
A
phi max
ZH18KVE
10,8
14,0
15,6
101
53
0,84
1
-
-
-
-
-
-
ZH24KVE
13,6
18,3
20,3
99
51
0,85
-
1
-
-
-
-
-
ZH33KVE
17,3
24,2
26,9
127
66
0,85
-
-
1
-
-
2
-
ZH40KVE
20,4
30,0
33,2
167
87
0,89
-
-
-
1
-
-
-
ZH48KVE
24,9
36,0
40,0
198
97
0,89
-
-
-
-
1
-
2
Legend
I Nom
Nominal current draw at Eurovent conditions (see definition of conditions under nominal unit current draw), A
I Max
Maximum operating current at 360 V, A
(1)
Locked rotor current at nominal voltage, A
(2
Locked rotor current at nominal voltage, electronic starter
5.2 - Short-circuit stability current (TN system
(1)
) - standard unit (with main disconnect without
fuse)
61AF
022
030
035
045
055
075
105
Value without upstream protection
Short-term current at 1 s - Icw - kA rms
0.6
0.6
0.6
1.26
1.26
1.26
2
Admissible peak current - Ipk - kA pk
4.5
4.5
4.5
6
6
6
10
Maximum value with upstream protection by circuit
breaker
Conditional short-circuit current Icc - kA rms
5.4
7
7
7.7
7.7
6.1
10
Circuit breaker - Compact range
32
40
40
50
63
80
100
Reference number
(2)
5SY6332-7 5SY6340-7 5SY6340-7 5SY4350-7 5SY4363-8 5SP4380-7 5SP4391-7
Value with upstream protection (fuses)
Conditional short-circuit current Icc - kA rms
17
50
50
50
50
14.5
22
Fuse (gL/gG)
40
40
40
63
63
80
125
(1) Earthing system type
(2) If another current limitation protection system is used, its time-current and thermal constraints (l²t) trip characteristics must be at least equivalent to those of the
recommended circuit breaker.
The short circuit stability current values above are suitable with TN system.