4.2 - Electrical data 30XAV
30XAV
500
600
700
800
950
1050
1150
Power circuit
Voltage range
V-ph-Hz 400-3-
50±10%
Control circuit supply
24 V via internal transformer
Start-up Current*
Not Applicable (less than the operating current)
Power factor**
-
Maximum***
0.91-0.93
Cosine phi
> 0.98
Total harmonic distortion
***
%
35-45
Maximum unit power input****
Circuit 1
†
kW
223
255
293
186
231
231
255
Circuit 2
†
kW
-
-
-
186
186
231
255
Option 81
kW
-
-
-
373
417
461
510
Nominal unit current draw
††
Circuit 1
†
A
260
306
346
218
264
264
293
Circuit 2
†
A
-
-
-
218
218
264
293
Option 81
A
-
-
-
436
482
528
586
Maximum unit current draw (Un)****
Circuit 1
A
352
400
458
290
362
362
402
Circuit 2
A
-
-
-
290
290
362
402
Option 81
A
-
-
-
580
652
724
804
Maximum unit current draw (Un-10%)***
Circuit 1
†
A
373
424
484
304
387
387
430
Circuit 2
†
A
-
-
-
304
304
387
430
Option 81
A
-
-
-
608
691
774
860
*
Instantaneous start-up current
**
May vary depending on the intensity ratio of short circuit / maximum intensity transformer installation
***
Values obtained at operation with maximum unit power input.
****
Values obtained at operation with maximum unit power input. Values given on the unit nameplate.
†
When the machines are equipped with two power supplies, circuit 1 is intended to supply the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B
††
Values obtained at standard Eurovent operating condition: Air 35 °C, water 12/7 °C.
4.3 - Short-circuit stability current for 30XAV units
Short-circuit stability current (TN system)*
30XAV
500
600
700
800
950
1050
1150
Standard unit
Short-time (1s) assigned current lcw / Peak current lpk
Circuit 1
kA
-
8/37
10/40
7.5/30
13/37
13/37
14/40
Circuit 2
kA
-
-
-
7.5/30
7,5/30
13/37
14/40
Assigned conditional short-circuit current Icc/Icf
Circuit 1
kA
50
-
-
-
-
-
-
With fuses upstream - maximum fuse values assigned (gL/gG)
Circuit 1
A
-
630
630
400
500
500
630
Circuit 2
A
-
-
-
400
400
500
630
With fuses upstream - Assigned conditional short circuit current Icc/Icf
Circuit 1
kA
-
50
50
50
50
50
50
Circuit 2
kA
-
-
-
50
50
50
50
Units with option 81 or 70D
Assigned conditionnal short circuit current Icc/Icf
Circuit 1
kA*
-
50
50
50
50
50
50
Circuit 2
kA*
-
-
-
50
50
50
50
Option 81
kA*
-
-
-
50
50
50
50
*
TN system (earthing system type)