![Carrier AquaForce 30XAV 1050 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/carrier/aquaforce-30xav-1050/aquaforce-30xav-1050_installation-operation-and-maintenance-instructions_2562361014.webp)
14
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XAV UNITS
4.1 - Physical data 30XAV
30XAV
500
600
700
800
950
1050
1150
Sound levels
Standard unit
Sound power level***
dB(A)
102
103
103
103
105
106
106
Sound pressure level at 10 m****
dB(A)
70
70
70
70
72
73
73
Standard unit + option 279*
Sound power level***
dB(A)
99
100
100
100
102
103
103
Sound pressure level at 10 m****
dB(A)
67
68
68
67
69
70
70
Standard unit + option 257*
Sound power level***
dB(A)
96
97
97
97
99
100
100
Sound pressure level at 10 m****
dB(A)
63
65
64
64
66
67
67
Dimensions - Standard unit
Length
mm
6092
6092
7186
8380
9573
10767
11962
Width
mm
2253
2253
2253
2253
2253
2253
2253
Height
mm
2297
2297
2297
2297
2297
2297
2297
Operating Weight**
Standard unit
kg
4831
5219
5767
6420
6806
7687
8076
Compressors
Circuit A
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
Refrigerant**
R134A
Circuit A
kg
50
52
56
64
79
80
84
teqCO
2
71.5
74.4
80.1
91.5
113.0
114.4
120.1
Circuit B
kg
43
54
58
67
71
82
87
teqCO
2
61.5
77.2
82.9
95.8
101.5
117.3
124.4
Capacity control
Touch Pilot control
Minimum capacity*****
%
10
10
10
10
10
10
10
Condensers
All aluminium Micro Channel Heat Exchanger (MCHE)
Fans - Standard unit
Axial FLYING-BIRD IV fans with rotating shroud
Quantity
9
10
12
14
16
18
20
Maximum total air flow
l/s
40608
45120
54144
63168
72192
81216
90240
Maximum rotational speed
rps
15.7
15.7
15.7
15.7
15.7
15.7
15.7
Evaporator
Flooded multi-pipe type
Water volume
l
75
90
90
110
120
134
146
Max water-side operating pressure
1000
1000
1000
1000
1000
1000
1000
Hydronic module
Victaulic type
Diameter
inch
5
6
6
6
6
8
8
Outside tube diameter
mm
141.3
168.3
168.3
168.3
168.3
219.1
219.1
Chassis paint colour
Colour code: RAL7035
*
Options: 257 = low sound level, 279 = compressor enclosure
**
Values are guidelines only. Refer to the unit nameplate.
***
In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO
9614-1 and certified by Eurovent.
**** In dB ref 20 μPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the
sound power level Lw(A).
***** For standard conditions. Depending on operating conditions, unit might have a different minimum capacity or cycle.
Содержание AquaForce 30XAV 1050
Страница 39: ...39 ...