background image

28

9 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA

9.1 - 

Direct-drive twin-screw compressor with 

variable capacity slide valve

 

-

30XAS units use the 06T geared twin-screw compressor 

equipped with a variable capacity slide valve for continuous 

control between 30% and 100% of full load.

 

-

Nominal  capacities  range  from  235  to  484  kW.  The  five 

models used in the 30XAS range are economised.

9.1.1 - 

Oil filter

The 06T screw compressor has an independent oil filter attached 

to the oil separator. This filter is field replaceable.

9.1.2 - Refrigerant

The 30XAS is a water chiller operating only with refrigerant R-134a.

9.1.3 - 

Lubricant

The 06T screw compressor is approved for use with the following 

lubricants:

 

-

Castrol Icematic SW220 (Carrier specification PP47-32)

 

-

Lubrizol Emkarate RL220H (Carrier specification PP47-13)

9.1.4 - Oil supply solenoid valve

An oil supply solenoid valve is installed on the oil return line as 

standard to isolate the compressor from oil flow when the 

compressor is not operating. The oil solenoid valve is field 

replaceable.

9.1.5 - Suction and economizer screens

To increase the reliability of the compressor, a screen has been 

incorporated as a standard feature into suction and economizer 

inlets of the compressor.

9.1.6 - Capacity control system

The 06T screw compressor has an unloading system that is 

standard on all compressors. This unloading system consists of 

slide valve that permits changing the length of the screw used for 

the refrigerant compression. This valve is controlled by the action 

of a piston controlled by two solenoid valves on the oil return line.

9.2 - Pressure vessels

General

Monitoring  during  operation,  re-qualification,  re-testing  and  re-

testing dispensation:

 

-

Follow the regulations on monitoring pressurised equipment.

 

-

It is normally required that the user or operator sets up and 

maintains a monitoring and maintenance file.

 

-

Follow the control programmes of EN 378, annexes A, B, C 

and D.

 

-

If they exist follow local professional recommendations.

 

-

Regularly inspect the condition of the coating (paint) to detect 

blistering resulting from corrosion. To do this, check a non-

insulated section of the container or the rust formation at the 

insulation joints.

 

-

Regularly check for possible presence of impurities (e.g. silica 

grains) in the heat exchange fluids. These impurities maybe 

the cause of the wear or corrosion by puncture.

 

-

Filter the heat exchange fluid check and carry out internal 

inspections as described in EN 378, annex C.

 

-

In case of re-testing please refer to the maximum operating 

pressure given on the unit nameplate.

 

-

The reports of periodical checks by the user or operator must 

be included in the supervision and maintenance file.

Repair

Any repair or modification, including the replacement of moving 

parts:

 

-

must  follow  local  regulations  and  be  made  by  qualified 

operators  and  in  accordance  with  qualified  procedures, 

including changing the heat exchanger tubes.

 

-

must be made in accordance with the instructions of the 

original manufacturer. Repair and modification that 

necessitate  permanent  assembly  (soldering,  welding, 

expanding etc.) must be made using the correct procedures 

and by qualified operators.

 

-

An indication of any modification or repair must be shown in 

the monitoring and maintenance file.

Recycling

The unit is wholly or partly recyclable. After use it contains 

refrigerant vapours and oil residue. It is coated by paint.

Operating life

This unit is designed for:

 

-

prolonged storage of 15 years under nitrogen charge with a 

temperature difference of 20 K per day.

 

-

452000 cycles (start-ups) with a maximum difference of 6 K 

between two neighbouring points in the vessel, based on 6 

start-ups per hour over 15 years at a usage rate of 57%.

Corrosion allowances

Gas side: 0 mm

Heat exchange fluid side: 1 mm for tubular plates in lightly alloyed 

steels, 0 mm for stainless steel plates or plates with copper-nickel 

or stainless steel protection.

9.2.1 - Evaporator

30XAS chillers use a flooded shell-and-tube evaporator. The water 

circulates in the tubes and the refrigerant is on the outside in the 

shell.  The  tubes  are  3/4”  diameter  copper  with  an  enhanced 

surface inside and out. There is just one water circuit with two 

water passes.
The evaporator has a thermal insulation of 19 mm thick 

polyurethane foam, an aluminium sheet (option) and is equipped 

with water drain and purge. It has been tested and stamped in 

accordance with applicable pressure codes for a maximum 

operating pressure of 2100 kPa refrigerant-side and 1000 kPa 

water-side.
The water connection of the heat exchanger is a Victaulic 

connection. As an option the evaporator is available with frost 

protection (evaporator frost protection option).
The products that may be added for thermal insulation of the 

containers during the water piping connection procedure must be 

chemically neutral in relation to the materials and coatings to which 

they are applied. This is also the case for the products originally 

supplied by Carrier.

Содержание Aquaforce 30XAS Series

Страница 1: ...LLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Air Cooled Liquid Chillers 30XAS A Unit with option 279 compressor enclosure Nominal cooling capacity 232 486 kW 5...

Страница 2: ...2...

Страница 3: ...entry 17 5 5 Field control wiring 17 6 APPLICATION DATA 18 6 1 Operating range 18 6 2 Minimum chilled water flow units without hydraulic module 18 6 3 Maximum chilled water flow units without hydrauli...

Страница 4: ...maintenance see note 34 11 2 Level 2 maintenance see note 34 11 3 Level 3 or higher maintenance see note 34 11 4 Tightening torques for the main electrical connections 34 11 5 Tightening torques for...

Страница 5: ...or ice These devices as well as the drain piping must not impair operation and not lead to a pressure drop that is higher than 10 of the control pressure Classification and control In accordance with...

Страница 6: ...ed off the power circuit remains energized unless the unit or circuit disconnect switch is open Refer to the wiring diagram for further details Attach appropriate safety labels Units with option 231 a...

Страница 7: ...f a leak occurs or if the refrigerant becomes contaminated e g by a short circuit in a motor remove the complete charge using a recovery unit and store the refrigerant in mobile containers Repair the...

Страница 8: ...uit Do not attempt to repair or recondition any safety devices when corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the d...

Страница 9: ...e frequency number of phases Maximum current drawn Maximum power input Unit net weight Confirm that all accessories ordered for on site installation have been delivered and are complete and undamaged...

Страница 10: ...than 15 WARNING Never push or lever on any of the enclosure panels of the unit Only the base of the unit frame is designed to withstand such stresses 2 2 3 Checks before system start up Before the st...

Страница 11: ...ional drawings supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings B...

Страница 12: ...or evaporator tube removal Water inlet Water outlet Air outlet do not obstruct Power supply connection C Control circuit connection 3 4 Multiple chiller installation It is recommended to install multi...

Страница 13: ...4798 4798 Width mm 2253 2253 2253 2253 2253 Height mm 2322 2322 2322 2322 2322 Operating weight 4 Standard unit kg 2375 2791 2847 3603 3689 Standard unit option 119 kg 3051 3167 3963 4119 Standard uni...

Страница 14: ...15 7 15 7 15 7 Evaporator Flooded multi pipe type Water content l 53 53 53 75 75 Without hydraulic module Water inlet outlet connections Victaulic Nominal diameter in 5 5 5 5 5 Actual outside diamete...

Страница 15: ...full load and nominal voltage 88 1 89 4 90 1 91 3 1 Nominal efficiency at 75 rated load and nominal voltage 88 88 9 89 7 91 4 1 Nominal efficiency at 50 rated load and nominal voltage 86 1 86 7 87 9 9...

Страница 16: ...60364 Outdoor installation Ambient temperature range from 20 C to 55 C Altitude less than or equal to 2000 m for hydraulic module see paragraph 4 3 in the IOM Presence of hard solids class AE3 no sign...

Страница 17: ...ter the control box from below or from the unit side For 30XAS unit sizes 282 to 482 the control box that includes the power supply cable connection terminal is located in the lower part of the unit I...

Страница 18: ...peration 3 3 15 Note If the leaving water temperature is below 4 C a glycol water solution or the frost protection option must be used Condenser air temperature C Minimum Maximum Storage 20 68 Operati...

Страница 19: ...chieve the required volume The tank must itself be internally baffled in order to ensure proper mixing of the liquid water or brine Refer to the examples below Connection to a buffer tank Bad Bad Good...

Страница 20: ...e eletrolytic pairs and consequently corrosion Verify then the need to install sacrificial anodes In case additives or other fluids than those recommended by Carrier are used ensure that the fluids ar...

Страница 21: ...lable pressure pump 5 Drain valve 6 Flow control valve 7 Evaporator 8 Evaporator defrost heater option 9 Hydraulic module defrost heater option 10 Air vent evaporator 11 Water drain evaporator 12 Expa...

Страница 22: ...in the operating limit table application data 7 5 2 Optional evaporator frost protection 30XAS If it is not possible to apply the recommendations in para graph 7 5 1 the units can be equipped with hea...

Страница 23: ...0 350 400 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 282 3 50 100 150 200 250 300 350 400 5 7 9 11 13 15 17 19 21 23 25 27 29 31 342 442 482 7 7 2 NPSH Net Positive Suction Head required option 116C hyd...

Страница 24: ...installed but supplied with the unit The sealing joints are in the control box The temperature sensors and the condenser flow switch are wired and fixed in the machine They must be installed as descri...

Страница 25: ...r 8 4 Condenser water connections NOTE Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings supplied with the unit or available on request...

Страница 26: ...temperature at start up 12 5 1 55 Water entering temperature during operation 20 55 Water leaving temperature during operation 25 60 Evaporator water temperature C Minimum Maximum Water entering temp...

Страница 27: ...eat exchange at the air condenser to heat exchange at the water condenser and vice versa is ensured by motorised two way valves located upstream of the air and water condensers ATTENTION Mode changes...

Страница 28: ...eat exchange fluid check and carry out internal inspections as described in EN 378 annex C In case of re testing please refer to the maximum operating pressure given on the unit nameplate The reports...

Страница 29: ...6 mm Insert this tool into the opening on the pressure switch and push the reset button in this location These pressure switches are located at the discharge of each compressor 9 3 2 Relief valves 30X...

Страница 30: ...n insufficient charge or non con densables in the system The presence of moisture changes the colour of the indicator paper in the sight glass 9 8 Filter drier The role of the filter drier is to keep...

Страница 31: ...t 1 2 3 4 1 2 4 5 3 1 2 4 5 3 1 2 5 6 3 6 7 4 1 2 5 6 3 7 4 8 x x Start up order Power connection NOTE The values above do not correspond to the fan designation The fan designation and position are gi...

Страница 32: ...ified service and maintenance 30XAS 242 482 Compressor discharge valves 93A Shut off valve on the compressor discharge piping Simplified maintenance 30XAS 242 482 HP dual pump hydraulic module 116C Co...

Страница 33: ...corrosive environments 30XAS 242 482 Super Enviro Shield anti corrosion protection 263 Extremely durable and flexible epoxy polymer coating applied on micro channel heat exchangers by electro coating...

Страница 34: ...replace the mountings Check the water connections Purge the water circuit see chapter Water flow control procedure Clean the water filter see chapter Water flow control procedure Fully clean the conde...

Страница 35: ...with clean water For coils installed in a coastal or industrial environment periodical cleaning by rinsing with water is beneficial It is however essential that rinsing is done with a low speed water...

Страница 36: ...mpressor terminal pin as originally wired For replacement of the compressor a low pressure switch is included with the compressor This low pressure switch should be temporarily installed as a hard saf...

Страница 37: ...of the unit can be recycled for another purpose 12 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 12 4 Ma...

Страница 38: ...otection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is connected properly All air has been vented from the chilled water c...

Страница 39: ...y supply at once and ensure that the chiller is not switched on until corrective measures have been taken Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal...

Страница 40: ...alidity of certificate www eurovent certification com Order No 13467 09 2018 Supersedes order No 13467 12 2016 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any...

Отзывы: