24
8 - HEAT RECLAIM CONDENSER OPTION (OPTION 50)
8.1 -
Technical data, 30XAS units with heat reclaim condenser option
30XAS heat reclaim mode
282
342
442
482
Operating weight*
kg
3256
3316
4186
4276
Refrigerant charge
kg
73
78
90
95
Heat reclaim condenser
Flooded multi-pipe condenser
Water volume
l
55
55
68
68
Water connections
Type Victaulic
Nominal diameter
in
4
4
4
4
Actual outside diameter
mm
114,3
114,3
114,3
114,3
*
Weights are for guidance only
8.2 - Dimensions, clearances
8.2.1 - 30XAS 282- 342 – heat reclaim option (option 50)
Legend:
All dimensions are given in mm.
ATTENTION: The condenser connection sleeves are not
installed, but supplied with the unit. The sealing joints are in
the control box. The temperature sensors and the condenser
flow switch are wired and fixed in the machine. They must be
installed as described in chapter 8.4 “Condenser water
connections”.
NOTE: Drawings are not contractually binding. Before
designing an installation, consult the certified dimensional
drawings supplied with the unit or available on request.
For the positioning of the fixing points, weight distribution
and centre of gravity coordinates please refer to the
dimensional drawings.
Specific elements for option 50
B
Required clearances for maintenance and air flow
C
Recommended space for evaporator tube removal
Water inlet
Water outlet
Air outlet - do not obstruct
Power supply connection
C
Control circuit connection
A
Heat reclaim condenser