Table 3 — 30XA Minimum and Maximum Cooler Flow Rates
* For applications re
q
uiring cooler leaving water temperature operation at less than
40 F (4.4 C), the units re
q
uire the use of antifreeze and application may re
q
uire
one of the special order
b
rine option. Contact your local Carrier representative for
more information.
† For applications re
q
uiring cooler entering water temperature operation at less than
45 F (7.2 C), contact your local Carrier representative for unit selection using the
Carrier electronic catalog.
NOTE: Nominal flow rates re
q
uired at ARI (Air Conditioning and Refrigeration
Institute) conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering
water temperature, 95 F (35 C) am
b
ient. Fouling factor 0.00010 ft
2
-hr-F/Btu
(0.00001
8
m
2
-K/kW).
ITEM
MINIMUM
MAXIMUM
NOMINAL
Cooler Leaving Water Temperature*
40 F (4.4 C)
60 F (15 C)
—
Cooler Entering Water Temperature†
45 F (7.2 C)
70 F (21.1 C)
—
30XA
UNIT SIZE
Cooler
Number of
Passes
Minimum Flow Rate
Maximum Flow Rate
Nominal Flow Rate
(gpm)
(L/s)
(gpm)
(L/s)
(gpm)
(L/s)
080
Standard
2
95
6.0
379
23.9
1
8
0.4
11.4
Plus one pass
3
43
2.7
192
12.1
Minus one pass
1
196
12.4
7
8
2
49.3
090
Standard
2
101
6.4
403
25.4
201.9
12.7
Plus one pass
3
43
2.7
200
12.6
Minus one pass
1
229
14.4
917
57.9
100
Standard
2
101
6.4
403
25.4
225.5
14.2
Plus one pass
3
43
2.7
200
12.6
Minus one pass
1
229
14.4
917
57.9
110
Standard
2
125
7.9
501
31.6
244.9
15.5
Plus one pass
3
61
3.
8
244
15.4
Minus one pass
1
254
16.0
1014
64.0
120
Standard
2
125
7.9
501
31.6
264.
8
16.7
Plus one pass
3
73
4.6
293
1
8
.5
Minus one pass
1
2
8
1
17.7
1124
70.9
140
Standard
2
134
8
.5
53
8
33.9
317.
8
20.1
Plus one pass
3
73
4.6
293
1
8
.5
Minus one pass
1
324
20.4
1296
8
1.
8
160
Standard
2
165
10.4
660
41.6
365.1
23.0
Plus one pass
3
9
8
6.2
391
24.7
Minus one pass
1
354
22.3
141
8
8
9.5
180
Standard
2
202
12.7
8
07
50.9
409.6
25.
8
Plus one pass
3
73
4.6
391
24.7
Minus one pass
1
416
26.2
1662
104.9
200
Standard
2
223
14.1
8
92
56.3
463.9
29.3
Plus one pass
3
9
8
6.2
391
24.7
Minus one pass
1
45
8
2
8
.9
1
8
33
115.6
220
Standard
2
235
14.
8
941
59.4
505.9
31.9
Plus one pass
3
122
7.7
4
8
9
30.9
Minus one pass
1
501
31.6
2004
126.4
240
Standard
2
266
16.
8
1063
67.1
545.
8
34.4
Plus one pass
3
147
9.3
5
8
7
37.0
Minus one pass
1
53
8
33.9
2151
135.7
260
Standard
2
257
16.2
1027
64.
8
600.3
37.9
Plus one pass
3
141
8
.9
562
35.5
Minus one pass
1
5
8
4
36.
8
2334
147.3
280
Standard
2
293
1
8
.5
1173
74.0
642.2
40.5
Plus one pass
3
141
8
.9
562
35.5
Minus one pass
1
620
39.1
24
8
1
156.5
300
Standard
2
327
20.6
130
8
8
2.5
6
8
7.5
43.4
Plus one pass
3
174
11.0
697
44.0
Minus one pass
1
6
8
7
43.3
2750
173.5
325
Standard
2
361
22.
8
1442
91.0
733.4
46.3
Plus one pass
3
211
13.3
8
43
53.2
Minus one pass
1
724
45.7
2
8
97
1
8
2.
8
350
Standard
2
379
23.9
1516
95.6
775.4
4
8
.9
Plus one pass
3
244
15.4
97
8
61.7
Minus one pass
1
767
4
8
.4
306
8
193.6
400
Standard
1
501
31.6
2004
126.4
917.6
57.9
Plus one pass
—
—
—
—
—
Minus one pass
—
—
—
—
—
450
Standard
1
501
2004
1019.3
64.3
Plus one pass
—
—
—
—
—
Minus one pass
—
—
—
—
—
500
Standard
1
501
2004
1092.
8
6
8
.9
Plus one pass
—
—
—
—
—
Minus one pass
—
—
—
—
—