31
8 - fREE-COOlING OPTION
8.1 - Characteristics
30Xa with Option 118a
252
302
352
402
452
502
602
702
752
802
852
902
1002
Operating weight*
kg
3840
3880
3920
4780
4850
5330
6260
6410
6710
7010 7560
7860
8440
Refrigerant charge
kg
Circuit A
36
37
37
54
56
64
64
64
72
76
79
76
83
Circuit B
38
38
39
37
39
39
64
68
64
67
70
79
87
Refrigerant charge, option 254 kg
Circuit A
60
64
**
87
87
104
104
102
**
**
133
**
143
Circuit B
64
64
**
56
56
56
90
97
**
**
97
**
132
* Standard unit and option 119
** Option 118A (free cooling) is not compatible with these units.
8.2 - Operating limits
Cooling mode
Evaporator
Minimum
Maximum
Entering water temperature at start-up
°C -
45
Entering water temperature during operation
°C 6.8
21
Leaving water temperature during operation
°C 3.3
26
Condenser (air)
Minimum
Maximum
Outdoor ambient operating temperature
°C -10
55*
With winter operation option (option 28)
°C -20
55*
free-cooling mode
Evaporator
Minimum
Maximum
Entering water temperature at start-up
°C -
45
Leaving water temperature during operation
°C 3,3
26*
Condenser (air)
Minimum
Maximum
Outdoor ambient operating temperature
°C -10
20
With winter operation option (option 28)
°C -20
20
* Maximum configurable set-point
8.3 - Operation
legend
1 Evaporator
2 Air condenser (coils)
3 Motorised two-way valve, discharge side
4 Compressor and oil separator
5 Principal electronic expansion valve (EXV)
6 Pressure and temperature measurement to calculate the sub-cooling upstream
of the pump
7 Motorised two-way bypass valve
8 Free-cooling expansion device (EXV)
9 Refrigerant pump
The change-over between the cooling and free-cooling
modes is automatically controlled (it is possible to block the
change-over to free-cooling by reconfiguring the machine -
see Controls IOM). The configurable parameters permitting
change-over are the outside air temperature and the leaving
water temperature set-point. As soon as the temperature
difference LWTstp - OAT is above 8 K the current capacity
in cooling mode is calculated and compared with the theo-
retical free-cooling capacity. This comparison authorizes/
stops the change-over to free-cooling.
After change-over to free-cooling all compressors are
stopped, the two (or four) two-way valves change to the free-
cooling position (the compressor functions are bypassed).
As soon as the valves open, the free-cooling pump is started.
This change-over logic takes around 4 minutes. Taking this
timing into consideration two cooling - free-cooling change-
overs are authorized per hour.
If the capacity supplied in the free-cooling mode is insuffi-
cient (set-point not reached), the unit automatically changes
over to cooling mode.
To optimize operation in free-cooling mode we strongly
recommend to use the set-point offset function. This favours
the change-over to free-cooling and increases the capacity
in free-cooling mode.
3
4
5
2
2
6
6
7
7
4
5
3
8
1
8
9
9