20
4.9 - Compressor electrical data
Compressor
I Nom*
I Max**
Mha
lRya
lRDa
Cosine
Cosine
std/Option 119
(Un)
(Un)
(Un)
Phi (max.)**
Phi (nom.)*
06Tsa155
69/64
86
96
170
530
0.90
0.87
06Tsa186
87/80
108
120
170
530
0.89
0.86
06TTa266
128/117
158
176
303
945
0.90
0.86
06TTa301
142/130
173
193
388
1210
0.90
0.89
06TTa356
163/150
198
220
388
1210
0.90
0.89
06TUa483
245/230
280
311
587
1828
0.86
0.84
06TUa554
267/246
329
366
587
1828
0.87
0.85
* Average value for the range (unit at Eurovent conditions)
** Value at maximum capacity and nominal voltage (400 V)
legend
Mha
- Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
lRya
- Locked rotor current for star connection (connection during compressor start-up)
lRDa
- Locked rotor current for delta connection
4.10 - Compressor usage per circuit (a, B, C, D)
30XA
Compressor
252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702
06Tsa155
AB
B
-
B
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
06Tsa186
-
A
AB
-
B
B
-
-
-
-
-
-
-
-
-
-
-
-
-
-
06TTa266
-
-
-
A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
06TTa301
-
-
-
-
A
-
B
-
B
-
-
-
-
B
B
-
-
-
-
-
06TTa356
-
-
-
-
-
A
A
AB
-
B
B
-
-
A
-
B
-
-
-
BD
06TUa483
-
-
-
-
-
-
-
-
A
A
-
AB
-
-
A
-
B
B
-
-
06TUa554
-
-
-
-
-
-
-
-
-
-
A
-
AB
C
C
AC
AC
AC
ABC AC
4.11 - Electrical data, optional hydronic module
30XA
252
302
352
402
452
502
single and dual low-pressure pump
Motor power
kW
2.2
2.2
3
4
4
5.5
Power input
kW
2.8
2.8
3.9
5.1
5.1
7.2
Maximum current draw
A
4.7
4.7
6.4
8.2
8.2
11.7
single and dual high-pressure pump
Motor power
kW
4
5.5
5.5
7.5
11
11
Power input
kW
5.1
7.2
7.2
9.2
13.2
13.2
Maximum current draw
A
8.2
11.7
11.7
15
21.2
21.2
Notes:
1. To obtain the maximum power input for a unit with hydronic module add the maximum unit power input to the pump power input.
2. To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw to the pump current draw.