42HQE009/012/018/022-38YE009/012/018/022  

GB - 8

Refrigerant piping connection

Flaring

• Cut a pipe with a pipe cutter.
• Insert a flare nut into a pipe and flare the pipe.

Outer diam.

A (mm)

(mm)

Max.

Min.

Ø 6.35

1.3

0.7

Ø 9.53

1.6

1.0

Ø 12.7

1.8

1.0

Ø 15.88

2.4

2.2

Tightening Connection
• Align pipes to be connected.
• Sufficiently tighten  the flare  nut with fingers, and then tighten it

with a spanner and torque wrench as shown.

CAUTION
• Excessive  torque can  break nut depending on installation

conditions.

Outer diam.

Tightening torque

Additional tightening

(N.cm)

torque (N.cm)

Ø 6.35

1570

1960

(160kgf.cm)

(200kgf.cm)

Ø 9.53

2940

3430

(300kgf.cm)

(350kgf.cm)

Ø 12.7

2940

4410

(300kgf.cm)

(450kgf.cm)

Ø 15.88

7360

7850

(750kgf.cm)

(800kgf.cm)

Outdoor unit installation

90

°

C

   

       

Oblique

 Roughness

Burr

A

Wiring connection

1. Remove the  electric parts cover  from the outdoor unit.
2. Connect the connective  cables to the terminals as identified

with their  respective matched  numbers on the terminal block of
indoor and outdoor units.

3. To prevent the ingress of  water, from a loop of the connective

cable as  illustrated in  the  installation diagram of indoor and
outdoor units.

4. Insulate unused cords (conductors) with PVC-tape. Process

them  so they do not  touch any electrical or metal parts.

CAUTION:
Wrong wiring connections may cause some electrical parts to
malfunction. A  disconnection device having an air gap contact
separation in all active conductors should be  incorporated in the
fixed wiring according to the National Wiring Regulation. All wiring
must comply with local and national electrical codes and be
installed by qualified and skilled electrician.


Cover

Screw

Terminal block of outdoor unit

38YE009/012/018

Terminal block of outdoor unit

38YE022

Wire-holding Board

Connective cable
(1, 2, 3, 4, 5)
CDU signal wire
(7, 8)

10 cm

40 cm

Connective cable

(Cooling & heating type)

Содержание ALLEGRO 38YE009

Страница 1: ...42HQE009 012 018 022 38YE009 012 018 022 INSTALLATION MANUAL...

Страница 2: ...ting installation plate 4 Connective Pipe and Drainage Installation 4 Dimensions and Minimum clearance 5 Wiring connection 6 Connecting Cables 6 Terminal block of indoor unit 6 Outdoor unit installati...

Страница 3: ...The unit complies with low voltage EEC 73 23 and electromagnetic compatibility EEC 89 336 directives Carefully recover refrigerant within this unit before final disposal or when servicing Never vent...

Страница 4: ...its location in a reception range Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment Do not install the remote controller in a place exposed to direct sunlight or...

Страница 5: ...d and rear left hand piping install the piping as shown Bend the connective pipe to be laid at 43 mm height or less from the wall 3 Fix the end of the connective pipe Refer to Tightening Connection in...

Страница 6: ...asily be made by lifting the indoor unit B A C Dimensions and Minimum clearances mm Model 42HQE009 42HQE012 42HQE018 42HQE022 A mm 750 815 906 1080 B mm 250 280 286 330 C mm 188 195 235 222 Upper hook...

Страница 7: ...nditioner takes a grounding leg so clients should use a grounding socket so that the air conditioner can be grounded efficiently If the power cord is damaged replacement should be conducted by qualifi...

Страница 8: ...e If need suspending installation the installation bracket should accord with technique requirement in the installation bracket diagram Outdoor unit installation A B C D E A F Minimum clearances mm Mo...

Страница 9: ...e outdoor unit 2 Connect the connective cables to the terminals as identified with their respective matched numbers on the terminal block of indoor and outdoor units 3 To prevent the ingress of water...

Страница 10: ...ld valve and stop the operation of the vacuum pump Make evacuation for 15 minutes and more and check that the compound meter indicates 76cmHg 1 0x105 Pa 6 Disconnect the charge hose from the charge co...

Страница 11: ...42HQE 38YE IOM Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2004...

Отзывы: