GB - 9

42HQE009/012/018/022-38YE009/012/018/022  

E N G L I S H

Air purge

Choose purge method from the table:

Models

Connective

Additional amount

Air purging

pipe length

of refrogeratant to

method

be charged

38YE009/012 Less than 5 m ------

38YE018/022

Use

38YE009/012 5~10m

(pipe length-5)x30g

vaccum

38YE018

5~15m

pump

38YE022

5~20m

(pipe length-5)x50g

• For the R407C refrigerant model, make sure the refrigerant added

into air conditioner is liquid form in any cases.

• When relocate the unit to another place, use vacuum pump to

perform evacuation.

CAUTION IN HANDING THE PACKED VALVE:
• Open the valve stem until it hits against the stopper. Do not try to

open it further.

• Securely tighten the valve stem cap with a spanner or the like.

Pipe

Models

size

N.cm

kgf.cm

Gas side

38YE009

Ø 9.52

2940

300

38YE012

Ø 9.52

2940

300

38YE018

Ø 12.7

4900

500

38YE022

Ø 15.88

7350

750

Liquid side

38YE009

Ø 6.35

1570

160

38YE012

Ø 6.35

1570

160

38YE018

Ø 6.35

1570

160

38YE022

Ø 9.52

2940

300

Air purge and test operation

When Using the Vacuum Pump
(For method  of using a  manifold valve, refer to its operation manual.)
1. Completely tighten the flare nuts, A, B, C, D, connect the

manifold valve charge hose to a charge port of the packed valve
on the gas pipe side.

2. Connect the charge hose connection to the  vacuum pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting

evacuation, slightly loose the flare nut of the packed valve on the
gas pipe side and check that the air is entering.(Operation noise
of  the vacuum pump changes  and  a  compound meter
indicates 0 instead of minus)

5. After  the  evacuation is complete, fully close the handle Lo of

the manifold valve and stop the operation of the vacuum pump.
• Make evacuation  for  15  minutes and more and check that

the compound meter indicates  -76cmHg(-1.0x10

5

Pa).

6. Disconnect  the charge hose from the charge connection of  the

packed  valve  at  the  gas  pipe side.

7. Fully open the packed valve stems B and A.
8. Securely tighten the cap of the packed valve.

   

Indoor unit

Outdoor unit

Refrigerant gas

Packed valve

Half union

       

A

B

C

D

X

Y

Ø15.88 mm (38YE022)

Ø12.7 mm (38YE012/018)
Ø 9.52 mm (38YE009)

Ø 9.52 mm (38YE022)

Ø 6.35 mm (38YE009/012/018)

Flare nut

Stopper

Cap

Valve stem

Valve body

GAS LEAK CHECK
Make sure no gas come out from connections
with leak detector or soap water.

Test operatiopn

Perform test operation after completing gas leak check at the flare
nut connections and electrical safety check.

1. Connect the power, push the “ON/OFF” button on the remote

controller to begin testing.

2. Push mode button, select cooling, heating, fan mode to check if

all functions work well.

3. When the ambient temperature is too low (below temperatures

of 17

°

), the unit can't be controlled by the remote controller to

run at cooling mode. At this time, manual operation can be taken
to select cooling mode.

4. Be sure to set the manual switch on OFF after finishing the test

operation. Then installer should explain how to manipulate, fix,
and maintain their air conditioner. Also tell them that regular check
of the installation bracket and maintenance are necessary.
Clients should apply for inspecting to relevant department so as
to ensure the air conditioner can operate normally, safety and
reliably.

Manifold valve

Compound meter
-76cmHg

Pressure gauge

Handle Lo

Handle Hi

Charge hose

Vacuum pump

Packed valve

Auto/cool

Manual switch

Indoor Unit check point
Outdoor unit check point
Cover

E

  D

    C

F                B          A

G

CAUTION
A
: Lo packed valve
B: Hi packed valve
C and D are ends of indoor unit
connection.

Содержание ALLEGRO 38YE009

Страница 1: ...42HQE009 012 018 022 38YE009 012 018 022 INSTALLATION MANUAL...

Страница 2: ...ting installation plate 4 Connective Pipe and Drainage Installation 4 Dimensions and Minimum clearance 5 Wiring connection 6 Connecting Cables 6 Terminal block of indoor unit 6 Outdoor unit installati...

Страница 3: ...The unit complies with low voltage EEC 73 23 and electromagnetic compatibility EEC 89 336 directives Carefully recover refrigerant within this unit before final disposal or when servicing Never vent...

Страница 4: ...its location in a reception range Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment Do not install the remote controller in a place exposed to direct sunlight or...

Страница 5: ...d and rear left hand piping install the piping as shown Bend the connective pipe to be laid at 43 mm height or less from the wall 3 Fix the end of the connective pipe Refer to Tightening Connection in...

Страница 6: ...asily be made by lifting the indoor unit B A C Dimensions and Minimum clearances mm Model 42HQE009 42HQE012 42HQE018 42HQE022 A mm 750 815 906 1080 B mm 250 280 286 330 C mm 188 195 235 222 Upper hook...

Страница 7: ...nditioner takes a grounding leg so clients should use a grounding socket so that the air conditioner can be grounded efficiently If the power cord is damaged replacement should be conducted by qualifi...

Страница 8: ...e If need suspending installation the installation bracket should accord with technique requirement in the installation bracket diagram Outdoor unit installation A B C D E A F Minimum clearances mm Mo...

Страница 9: ...e outdoor unit 2 Connect the connective cables to the terminals as identified with their respective matched numbers on the terminal block of indoor and outdoor units 3 To prevent the ingress of water...

Страница 10: ...ld valve and stop the operation of the vacuum pump Make evacuation for 15 minutes and more and check that the compound meter indicates 76cmHg 1 0x105 Pa 6 Disconnect the charge hose from the charge co...

Страница 11: ...42HQE 38YE IOM Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice December 2004...

Отзывы: