background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53420008-01

Printed in U.S.A.

Form 42WKN-7SI

Pg 1

4-13

Replaces: 42WKN-6SI

Installation, Operation and Maintenance 

Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . .1,2

INSPECTION

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2-6

CONTROLS DESCRIPTION

. . . . . . . . . . . . . . . . . . . .  7-18

Microprocessor Control Board

 . . . . . . . . . . . . . . . . . . . 7

Inputs

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Outputs

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

External Connections

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Microprocessor PCB Battery

 . . . . . . . . . . . . . . . . . . . . . 7

Controller

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Optional Pendant

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Infrared Receiver

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Self Diagnostics

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Receiver Indicators

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

PRE-INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Unpack Unit

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Blank Off Pieces

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Positioning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Ceiling Opening Sizes

. . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Positioning the Electro-Mechanical 

Thermostat

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19-31

Hanger Bolts

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Installation Guide

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

• INSTALLATION GUIDE SETUP

Condensate Piping

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Duct Collars

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Piping Installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Piping Insulation

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Terminal Strip Connections

 . . . . . . . . . . . . . . . . . . . . . 21

Fascia Assembly

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Pendant Assembly Installation

 . . . . . . . . . . . . . . . . . . 31

PRE-START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  31-33

Pre-Start Checks

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Control Circuit Checks

 . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Sequence of Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . 33

• ELECTRO-MECHANICAL CONTROLS
• MICROPROCESSOR CONTROLS

OPERATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Cool Only Mode Settings

 . . . . . . . . . . . . . . . . . . . . . . . . 33

Heat Only Mode Settings

 . . . . . . . . . . . . . . . . . . . . . . . . 33

Auto Mode Settings

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Setting the Current Time

 . . . . . . . . . . . . . . . . . . . . . . . . 33

Programming the Unit

. . . . . . . . . . . . . . . . . . . . . . . . . . . 33

• SETTING THE WEEKDAYS TIME PROGRAM  

(Monday through Friday)

• SETTING THE SATURDAY TIME PROGRAM
• SETTING THE SUNDAY TIME PROGRAM

CONTROLS

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Setting Jumper Links

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Software Control

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Main Control Functions

 . . . . . . . . . . . . . . . . . . . . . . . . . 34

Page

• INDOOR FAN OPERATION
• BOOST HEAT
• TEMPERATURE CONTROL
• POWER  FAILURE
• BATTERY BACKUP

Alarms

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

• ELECTRIC HEATER OVERHEAT PROTECTION
• HIGH CONDENSATE LEVEL ALARM

NETWORK OPTION — MICROPROCESSOR

CONTROLLER

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34,35

Master/Slave Operation

 . . . . . . . . . . . . . . . . . . . . . . . . . 34

Network Connection

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

MAINTENANCE

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Maintenance Schedule

 . . . . . . . . . . . . . . . . . . . . . . . . . . 35

• EVERY 3 MONTHS
• EVERY 6 MONTHS
• EVERY 12 MONTHS

Filter Removal and Cleaning

. . . . . . . . . . . . . . . . . . . . . 35

Recommended Spares

 . . . . . . . . . . . . . . . . . . . . . . . . . . 35

DISASSEMBLY PROCEDURE

. . . . . . . . . . . . . . . . . .35,36

Fan Removal

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Condensate Tray Removal

. . . . . . . . . . . . . . . . . . . . . . . 36

Condensate Pump Removal

. . . . . . . . . . . . . . . . . . . . . 36

TROUBLESHOOTING

 . . . . . . . . . . . . . . . . . . . . . . . .  36-38

REPLACEMENT PARTS

 . . . . . . . . . . . . . . . . . . . . . .  39-41

SAFETY CONSIDERATIONS

Installing and servicing air-conditioning equipment can be

hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install and
service air-conditioning equipment.

Untrained personnel can perform basic maintenance, such

as cleaning and replacing filters. All other operations should be
performed by trained service personnel. When working on
air-conditioning equipment, observe safety precautions in liter-
ature and on tags and labels attached to the unit.

1. The equipment has been designed and manufactured to

meet international safety standards but, like any mechani-
cal/electrical equipment, care must be taken to obtain the
best results.

2. Service and maintenance of this equipment should only

be carried out by skilled personnel.

3. When working with any air-conditioning unit, ensure that

the electrical disconnect supplying the unit is switched off
prior to servicing or repair work and that there is no pow-
er to any part of the equipment.

4. Also ensure that there are no other power feeds to the unit

such as fire alarm circuits, building management system
(BMS) circuits, etc.

AIRSTREAM™

42WKN08-36

Hydronic Ceiling Cassettes

Содержание AIRSTREAM 42WKN

Страница 1: ...TEMPERATURE CONTROL POWER FAILURE BATTERY BACKUP Alarms 34 ELECTRIC HEATER OVERHEAT PROTECTION HIGH CONDENSATE LEVEL ALARM NETWORK OPTION MICROPROCESSOR CONTROLLER 34 35 Master Slave Operation 34 Netw...

Страница 2: ...data DANGER Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere WARNING Improper installation adjustment alteration service or maintenance can...

Страница 3: ...ube Quantity 1 1 1 1 1 1 Face Area sq ft 1 8 1 8 2 8 2 8 5 2 5 2 Nominal Airflow cfm High 350 350 630 700 970 1160 Medium 300 300 530 630 890 970 Low 260 260 500 530 785 890 Discharge 4 way 4 way 4 wa...

Страница 4: ...1 8 3 3 4 2 1 16 2 5 8 A A VIEWA A 9 13 16 1 1 8 2 3 4 5 7 8 9 5 10 6 1 CWInlet 2 CWOutlet 3 HWCoil Inlet Optional 4 HWCoil Outlet Optional 5 Branch Duct Opening x3 6 Fresh Air Intake x2 7 Pump Inspe...

Страница 5: ...13 16 8 11 16 1113 16 3 1 8 713 16 23 4 VIEWA A A A 2 5 1 4 10 5 6 7 8 9 3 5 3 8 1 CWCoil Inlet 2 CWCoil Outlet 3 HWCoil Inlet Optional 4 HWCoil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Op...

Страница 6: ...6 4 3 4 7 9 16 913 16 1 5 8 47 8 2 3 4 2 3 4 3 1 8 9 13 16 23 4 5 10 2 5 4 3 1 6 7 9 8 1 CWCoil Inlet 2 CWCoil Outlet 3 HWCoil Inlet Optional 4 HWCoil Outlet Optional 5 Fresh Air Intake x3 6 Branch Du...

Страница 7: ...tments and settings being made from a hand held IR transmitter or optional pendant The controls include the following basic components PCB control board Infrared transmitter or optional pendant Infrar...

Страница 8: ...Wiring Diagram Sizes 08 and 12 a42 4333 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit CW Chilled Water PCB Printed Circuit Board Factory Installed...

Страница 9: ...Diagram Sizes 18 and 20 a42 4336 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit CW Chilled Water PCB Printed Circuit Board VM Vane Motor Factory Ins...

Страница 10: ...Diagram Sizes 33 and 36 a42 4327 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit CW Chilled Water PCB Printed Circuit Board VM Vane Motor Factory Ins...

Страница 11: ...agram Size 08 and 12 a42 4332 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit CW Chilled Water HTR Heat Relay HW Hot Water PCB Printed Circuit Board F...

Страница 12: ...zes 18 and 20 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit CW Chilled Water HTR Heat Relay HW Hot Water PCB Printed Circuit Board VM Vane Motor Fac...

Страница 13: ...izes 33 and 36 a42 4328 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit CW Chilled Water HTR Heat Relay HW Hot Water PCB Printed Circuit Board VM Vane...

Страница 14: ...r Control Wiring Diagram Sizes 08 and 12 A42 4335 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit HW Hot Water PCB Printed Circuit Board VR Valve Rela...

Страница 15: ...Control Wiring Diagram Sizes 18 and 20 A42 4339 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit PCB Printed Circuit Board VM Vane Motor VR Valve Rela...

Страница 16: ...ol Wiring Diagram Sizes 33 and 36 A42 4329 AL Alarm Relay AWG American Wire Gage BAT Battery CPM Condensate Pump CPU Central Processing Unit HW Hot Water PCB Printed Circuit Board VM Vane Motor VR Val...

Страница 17: ...ill operate the air vanes Med Large cassettes only OFF Pressing this button will switch the unit off TRANSMIT INDICATOR This symbol will flash when the system settings are transmitted MODE INDICATOR H...

Страница 18: ...oor fan on cooling off and heating on Unit on timer operation off indoor fan on check main PCB battery Unit on timer operation on indoor fan on cooling and heating off Unit on timer operation on indoo...

Страница 19: ...ble 2 Table 2 Ceiling Opening Dimensions A cardboard template for ceiling cutout and rod positions is included with the unit Positioning the Electro Mechanical Thermo stat In addition to positioning t...

Страница 20: ...lation is pre cut to aid location and removal of the relevant section Rub hand across surface of insula tion to reveal exact location of knockout 3 Remove the metal knockout from the chassis 4 Attach...

Страница 21: ...erminal strip 1 Push a small flat head screwdriver into the square hole on the terminal Press firmly until the screwdriver hits the back stop and opens the terminal See Fig 25 2 Remove approximately 3...

Страница 22: ...Wire Gage CPM Condensate Pump CW Chilled Water Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as a default To change the...

Страница 23: ...age CPM Condensate Pump CW Chilled Water VM Vane Motor Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as a default To cha...

Страница 24: ...age CPM Condensate Pump CW Chilled Water VM Vane Motor Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as a default To cha...

Страница 25: ...AWG American Wire Gage CPM Condensate Pump VR Valve Relay Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as a default To...

Страница 26: ...rican Wire Gage CPM Condensate Pump VM Vane Motor VR Valve Relay Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as a defa...

Страница 27: ...rican Wire Gage CPM Condensate Pump VM Vane Motor VR Valve Relay Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as a defa...

Страница 28: ...ondensate Pump CW Chilled Water HTR Hot Water Relay HW Hot Water Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as a defa...

Страница 29: ...te Pump CW Chilled Water HTR Hot Water Relay HW Hot Water VM Vane Motor Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as...

Страница 30: ...te Pump CW Chilled Water HTR Hot Water Relay HW Hot Water VM Vane Motor Factory Installed Field Installed Terminal Block Component Terminal Connected Path 1 LEGEND NOTE Fan is wired to medium speed as...

Страница 31: ...ither one of the 2 net work terminals marked The pendant connector and network terminal positions are illustrated in Fig 4 PRE START UP See the start up sheet example in Fig 37 A start up sheet is sup...

Страница 32: ...r cooling 8 Where fitted check the operation of the hot water valve or the electrical heat elements by switching the system to the heating mode and forcing a call for heat 9 Allow chilled water to ent...

Страница 33: ...o switch the unit on and transmit the new system settings Setting the Current Time 1 Press CLK TIMER button once CLOCK SET should begin flashing in the time display 2 Press either or button within the...

Страница 34: ...es normal power outag es With no power the battery will last up to three months When the battery requires replacing the cool and heat status LEDs on the IR receiver will flash at 1 second intervals Al...

Страница 35: ...ecommended Spares It is recommended that one complete set of air filters be kept on hand for use as needed DISASSEMBLY PROCEDURE Fan Removal 1 Unclip the grille catches and remove the grille s from th...

Страница 36: ...a suitable container 4 Remove the self tapping screws securing the 2 insulated metal condensate tray support channels and pull the channels away from the condensate tray Pull the conden sate tray com...

Страница 37: ...ities in every section of this trouble shooting guide first Replace the microprocessor only after all other avenues of investigation are exhausted Fans Will Not Run Loose wire Check all fan wire conne...

Страница 38: ...to unit Faulty valve actuator Check actuator by manually opening and closing valve replace if faulty Faulty heater relay Check signals to relay and check action of relay contacts Replace relay or PCB...

Страница 39: ...purchase order number Racine WI 53403 2552 1500 DeKoven Avenue n a n aA kW n a Electric Heat 500 CHARGE 1 QTY Maximum Discharge Temp 125 F Clearance to Combustibles 0 0 5 FIELD FACTORY CHARGE 0 LB TYP...

Страница 40: ...ump Assembly Shown Inverted 9 Fan Motor Assembly 10 Coil Return Air Sensors Microprocessor Only 11 Grille 12 Label DESCRIPTION 13 Air Deflector Vanes 4 14 Filter 15 Fascia Assembly 16 Receiver Micropr...

Страница 41: ...ondensate Tray Support 5 High Level Switch Shown Inverted 6 Condensate Pump Shown Inverted 7 Fan and Motor Assembly 8 Fan Inlet Ring 9 Grille 10 Infrared Receiver DESCRIPTION 11 Vane 12 Vane Motor Ass...

Страница 42: ......

Страница 43: ......

Страница 44: ...ght to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53420008 01 Printed in U S A Form 42WKN 7SI Pg 44 4 13 Replaces 42WKN...

Отзывы: