36
Condensate Tray Removal
1. Unclip the grille catches and remove the grille(s) from the
fascia.
2. Remove the fascia by loosening the fascia mounting bolts
and then slide the fascia horizontally until it releases from
the chassis. If the unit is microprocessor controlled, re-
move the display panel cable from within the electrical
panel before removing the fascia.
3. Drain the condensate tray by removing the small black
rubber drain plug, catching any condensate in a suitable
container.
4. Remove the self-tapping screws securing the 2 insulated
metal condensate tray support channels and pull the
channels away from the condensate tray. Pull the conden-
sate tray, complete with inlet ring (inlet ring on unit sizes
18-36 only) downward away from the chassis.
Condensate Pump Removal
1. Disconnect the condensate pump and float switch wires
from inside the electrical panel.
2. Unscrew the 3 M4 screws holding the pump inspection
plate in place and pull the pump and mounting bracket
away from the chassis while feeding the pump wires be-
tween condensate tray and insulation.
TROUBLESHOOTING
See Table 6 for troubleshooting information.