Carrier AIRSTREAM 42BHE Скачать руководство пользователя страница 7

7

7. TURN POWER ON. (Close unit electrical disconnect.)

NOTE: Be sure power is off before making any adjust-

ments inside unit.

8. Check fan and motor operation. Motor to fan wheel rota-

tion must match airflow direction shown in Fig. 2 and 3.
Set unit air delivery for required blower rpm per job sub-

mittals or product data catalog. Adjust fan motor pulley

(Fig. 7) as follows:

a. Loosen setscrew on movable pulley flange.

b. Screw flange toward fixed flange to increase fan

speed and away from fixed flange to decrease speed.

c. Reset setscrew.

d. Check belt tension. The drive belt should be ten-

sioned to allow 

1

/

2

 to 

3

/

4

-in. deflection at the mid-

point between pulleys with moderate pressure.

Inspect the unit for loose wires, correct blower wheel opera-

tion, and loose or missing access panels or doors. Unless other-

wise required for balancing and start-up procedures, units

should not be operated without proper ductwork; supply/return

air grilles, and access panels and/or doors in place.

START-UP

Start-up procedures vary depending upon the time of year

(summer or winter) and building characteristics (new building

or old building, occupied or unoccupied, etc.).

Start-up in the Cooling mode requires that proper care be giv-

en to avoid condensation problems. Condensation forms on sur-

faces that are colder than the dew point of the surrounding air. If a

unit is started and is fed low-temperature chilled water in a hot,

humid setting, condensation will form on many parts of the unit.

In order to avoid excessive condensation, water of higher

temperature should be used, approximately 65 to 70 F. Also, the

building should be as completely enclosed as possible and

outside-air supply fans and toilet and kitchen exhaust fans should

be off.

As the building temperature drops, the chilled water temper-

ature can gradually be reduced until it reaches 50 F. At this

point, the outside-air fans can be turned on. When the chilled

water temperature is reduced to its design point, the exhaust

fans can be turned on.

Air System Balancing — 

All ductwork, air grilles, fil-

ters, and access doors and panels must be complete and con-

nected to establish actual system operating conditions before

air system balancing procedures are started.
NOTE: Units are factory set for system designed operating

conditions specified at the time of order entry.

Proper belt drive alignment and tension must be maintained

when adjusting the unit fan drive speed. The drive belt tension

should not exceed 

3

/

16

-in. deflection midway between the pul-

leys under 8-lb. of force. New belts tend to stretch during their

initial period of use. After 5 days of operation, check and read-

just belt tension and pulley alignment if necessary. Failure to do

so may result in excessive unit noise and/or premature belt/

bearing failure.

SERVICE

Clean Coils

1. Brush between coil fins with a stiff wire brush. Do not

bend fins. Follow up by cleaning with a vacuum cleaner.

If coil is cleaned with an air hose, take care not to drive

dirt and dust into other components.

2. Install clean air filters.

Check Drain — 

Check drain pan, drain line and trap at

start of each cooling season. A standard type pipe cleaner for

3

/

4

-in. ID pipe can ensure removal of obstructions so that con-

densate is carried away. Check the drain line at filter cleaning

time during the cooling season.

Fan and Motor Bearings — 

Fan shaft bearings are

permanently lubricated and sealed, and need no attention.

Check tag on motor for motor bearing lubrication instructions

(if any). Most motors furnished with these units are perma-

nently lubricated.

Align Pulley — 

Loosen pulley setscrew(s). Align pulleys

by using a straight edge as shown in Fig. 7. Retighten set-

screw(s).

Adjust Fan Belt Tension — 

Loosen fan motor base

mounting screws. Reposition the motor so that belt deflection

does not exceed 

3

/

16

-in. at belt midpoint under 8-lb of force.

Retighten motor mounting screws and recheck fan belt tension.

Clean Fan Wheel — 

Use a stiff brush or vacuum to re-

move dirt and debris from scroll. Wipe all fan surfaces with a

damp cloth.

Clean or Replace Air Filters — 

At the start of each

cooling season and after each month of operation (more or less

depending on operating conditions), replace unit filter. 

CAUTION

Do not exceed motor nameplate FLA (full load amps).

Operator must confirm motor current draw before putting

unit into service and again after air balancing the system.

Failure to do so could result in equipment damage.

CAUTION

Follow all safety considerations previously outlined. Fail-

ure to do so could result in personal injury or equipment

damage.

Fig. 7 — Fan Pulley Adjustments

a42-89tf

WARNING

Lock open and tag electrical disconnect before servicing

equipment. Failure to do so could result in personal injury

or death.

Содержание AIRSTREAM 42BHE

Страница 1: ...ty or equip ment use good judgment and follow safe practices as outlined below when installing and operating this equipment INTRODUCTION The following contains general installation instructions for th...

Страница 2: ...ements Refer to job drawings and product dimension drawings as re quired Instruct all trades in the appropriate part of the installa tion For unit component identification refer to Fig 1 For unit dime...

Страница 3: ...side or bottom of the filter rack on horizontal unit 42BHE If side access to filter is desired the minimum clearance required is the width of the filter rack plus 6 inches 6 Protect unit from damage f...

Страница 4: ...g and valves not located over drain pans or drip lips must be insulated to prevent damage from sweating Vent all coils during final preparations See Step 10 section 6 Check interior unit piping for si...

Страница 5: ...3 42BHE BVE ELECTRIC HEATER DATA Table 4 MOTOR PERFORMANCE DATA FULL LOAD AMPS NOTES 1 Motor full load amps refer to National Electric Code NEC amps actual motor nameplate amps may vary 2 NEC data ext...

Страница 6: ...ilter access panel Step 10 Make Final Preparations 1 TURN POWER OFF Open unit electrical disconnect 2 Clean unit thoroughly Remove dirt and debris from unit especially drain pan drain line motor and f...

Страница 7: ...perating conditions specified at the time of order entry Proper belt drive alignment and tension must be maintained when adjusting the unit fan drive speed The drive belt tension should not exceed 3 1...

Страница 8: ...ld be in stalled to shut off the water when the fan stops The following two practices will also help avoid condensa tion problems 1 Continuous fan operation with motorized chilled water valve controll...

Страница 9: ......

Страница 10: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53420006 01 Printed in U S A Form 42B 3SI Pg 10 2 11 Replaces 42B 2SI Cop...

Страница 11: ...valve Yes No 13 Open air vent on top of coil to vent air out of system Yes No 14 Open return ball valve Yes No 15 Engage power only long enough to verify proper blower rotation Yes No 16 Check all du...

Страница 12: ...______________________________________ ________________________________________________________________________________________________________ ________________________________________________________...

Отзывы: