Step 7 — Make Electrical Connections — 

Refer to

the unit rating plate for supply voltage, motor and heater am-

perage, and required circuit ampacities. (See Tables 2 - 4.) The

unit wiring diagram shows all factory and field wiring. Most of

the unit motors are dual voltage that are factory wired for a

specified voltage. The motors should be checked to ensure that

they are wired for the correct voltage and rotation.

Units equipped with factory-installed motor controls and

disconnect will comply with NEC requirements for disconnect,

motor controller and motor overload protection. Separate dis-

connect and motor starter are not required to comply with NEC

requirements.

All field wiring should be done in accordance with all appli-

cable local and national codes. Any factory wiring modifica-

tions without factory authorization will void all factory warran-

ties and nullify any agency listings.

The manufacturer assumes no responsibility for any dam-

age and/or injuries resulting from improperly installed or wired

components.

Install fan switches, thermostats and other accessories in

accordance with accessory manufacturer’s instructions and ap-

plicable wiring diagram.

Table 2 — 42BHE,BVE ELECTRIC HEATER DATA 

AVAILABILITY

LEGEND

NOTES:

1. Stages available:

a. Single phase: 1 to 12 kW, 1 stage only

3 to 12 kW, 1 stage or 2 stage

b. Three phase: 1 to 39.9 kW, 1 stage only

4 to 39.9 kW, 1 or 2 stage
12 to 39.9 kW, 1, 2 or 3 stage

2. Electric Heating Capacities (Btuh) = Heater kW x 3413
3. Electric Heater Amperage for Single-phase Power = (Heater

kW x 1000)/Applied Voltage 
Electric Heater Amp. for 3-phase Power = (Heater kW x 1000)/
(Applied Voltage x 1.73).

Table 3 — 42BHE,BVE ELECTRIC HEATER DATA

Table 4 — MOTOR PERFORMANCE DATA (FULL 

LOAD AMPS)

NOTES:

1. Motor full load amps refer to National Electric Code (NEC)

amps; actual motor nameplate amps may vary.

2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750

rpm rated at continuous duty, 104 F ambient with reversible
rotation.

4. 5HP motors available only on size 40 units.

SERVICE SWITCHES: — The service switch is an On/Off

switch on incoming power supply to unit. Proper amperage
load must be determined before switch can be selected. The

range of the fused or non-fused service switch is 0 to 40
amps.

Amp Load = 

[Motor amps + Heater amps (if required)] x 1.20.

kW

42BHE UNIT SIZE

06

08

10

12

16

20

30

40

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

6.0

7.0

8.0

9.9

12.0

14.0

15.0

16.0

18.0

19.9

25.0

30.0

35.0

39.9

Standard Offering

Not Offered

kW

FULL LOAD AMPS

Single-Phase

Three-Phase

115 V

208 V

240 V

277 V

208 V

240 V

480 V

1.0

8.3

4.8

4.2

3.6

2.8

2.4

1.2

1.5

12.5

7.2

6.3

5.4

4.2

3.6

 1.8

2.0

16.7

9.6

8.3

7.2

5.6

4.8

2.4

2.5

20.8

12.0

10.4

9.0

6.9

6.0

3.0

3.0

25.0

14.4

12.5

10.8

8.3

7.2

3.6

3.5

29.2

16.8

14.6

12.6

9.7

8.4

4.2

4.0

33.3

19.2

16.7

14.4

11.1

9.6

4.8

4.5

37.5

21.6

18.8

16.2

12.5

10.8

5.4

5.0

24.0

20.8

18.1

13.9

12.0

6.0

6.0

28.8

25.0

21.7

16.7

14.4

7.2

7.0

33.7

29.2

25.3

19.4

16.8

8.4

8.0

38.5

33.3

28.9

22.2

19.2

9.6

9.9

35.7

27.5

23.8

11.9

12.0

43.3

33.3

28.9

14.4

14.0

38.9

33.7

16.8

15.0

41.6

36.1

18.0

16.0

38.5

19.2

18.0

21.7

19.9

23.9

25.0

30.1

30.0

36.1

35.0

42.1

39.9

48.0

VOLTAGE

V-Ph-Hz

Nominal HP

1

/

4

1

/

3

1

/

2

3

/

4

1

1

1

/

2

2

3

5

115-1-60

5.2

6.0

8.6

13.3 14.4

208-1-60

3.0

3.6

4.8

6.6

7.4

9.4

11.0

230-1-60

2.5

3.0

4.2

5.1

6.0

9.0

10.9

277-1-60

2.1

2.5

3.6

5.1

5.4

8.5

8.0

208-3-60

2.4

3.6

3.8

6.0

6.5

8.2

14.0

230-3-60

2.2

3.0

3.2

4.8

6.2

8.0

13.2

460-3-60

1.1

1.5

1.9

2.8

3.1

4.0

6.6

Содержание AIRSTREAM 42BHE

Страница 1: ...ty or equip ment use good judgment and follow safe practices as outlined below when installing and operating this equipment INTRODUCTION The following contains general installation instructions for th...

Страница 2: ...ements Refer to job drawings and product dimension drawings as re quired Instruct all trades in the appropriate part of the installa tion For unit component identification refer to Fig 1 For unit dime...

Страница 3: ...side or bottom of the filter rack on horizontal unit 42BHE If side access to filter is desired the minimum clearance required is the width of the filter rack plus 6 inches 6 Protect unit from damage f...

Страница 4: ...g and valves not located over drain pans or drip lips must be insulated to prevent damage from sweating Vent all coils during final preparations See Step 10 section 6 Check interior unit piping for si...

Страница 5: ...3 42BHE BVE ELECTRIC HEATER DATA Table 4 MOTOR PERFORMANCE DATA FULL LOAD AMPS NOTES 1 Motor full load amps refer to National Electric Code NEC amps actual motor nameplate amps may vary 2 NEC data ext...

Страница 6: ...ilter access panel Step 10 Make Final Preparations 1 TURN POWER OFF Open unit electrical disconnect 2 Clean unit thoroughly Remove dirt and debris from unit especially drain pan drain line motor and f...

Страница 7: ...perating conditions specified at the time of order entry Proper belt drive alignment and tension must be maintained when adjusting the unit fan drive speed The drive belt tension should not exceed 3 1...

Страница 8: ...ld be in stalled to shut off the water when the fan stops The following two practices will also help avoid condensa tion problems 1 Continuous fan operation with motorized chilled water valve controll...

Страница 9: ......

Страница 10: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53420006 01 Printed in U S A Form 42B 3SI Pg 10 2 11 Replaces 42B 2SI Cop...

Страница 11: ...valve Yes No 13 Open air vent on top of coil to vent air out of system Yes No 14 Open return ball valve Yes No 15 Engage power only long enough to verify proper blower rotation Yes No 16 Check all du...

Страница 12: ...______________________________________ ________________________________________________________________________________________________________ ________________________________________________________...

Отзывы: