34
English
80AWX- 80AWH
18
G-Tr short circuit
protection
Inverter over-
current protective
circuit operates.
Short circuit
voltage protection
of main circuit
operates
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check Outdoor unit board for cabling
error
20
Position
Detection Circuit
Error
Position detection
circuit operates
when the
compressor is
operating despite
removal of 3P
connector.
Outdoor unit stops
Domestic water valve OFF if code
127=1
Replace Outdoor unit board
21
Current Sensor
Error
Current detection
circuit error:
• Current value
at AC side is high
when compressor
is OFF
• Phase of power
supply is missing
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check outdoor unit board.
Check 3 phase power voltage and
cables
22
Outdoor Heat
Exchange Sensor
(TE) / (TS)
Value out of range
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check sensor, wiring and electrical
connections
23
Discharge
Temperature
Sensor
(TD)
Value out of range
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check sensor, wiring and electrical
connections
24
Outdoor Fan
Error
Defective
detection of
position
Operation of
outdoor fan over-
current protection
circuit
Outdoor fan
locked
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check outdoor fan
Check outdoor unit board
26
Other Outdoor
Error
Outdoor unit stops
Domestic water valve OFF if code
127=1
27
Compressor Lock
Defective cabling
of compressor
Compressor fault
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check 3 phase compressor power
cables
Replace compressor
28
Discharge
Temperature
Error
Error of discharge
temperature
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check for refrigerant gas leaks
Check PMV operation
Check TD sensor operation
29
Compressor
Breakdown
Abnormal
compressor
operation
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check power supply: AC 220 V +/-10%
Overload operation of refrigerating
cycle
Check current detection circuit at
AC side
30
Other inverter
board error
Outdoor unit stops
Domestic water valve OFF if code
127=1
31
High
Temperature
Release
Outdoor unit stops
Domestic water valve OFF if code
127=1
Check outdoor temperature sensor TE
in the Outdoor unit
Check Outdoor unit board
User interface fault codes
70
Configuration
Code 104 not
equal to 242 or
243 or 244
Communication is disabled
Change setting of code 104.
Error
code
Item
Failure when
Consequences
Diagnostics and solutions
Maintenance
Содержание 80AWH Series
Страница 1: ...Controlmodule 80AWX 80AWH Installation Manual ...
Страница 2: ...2 80AW1 80AW2 1 2 T 1 T 2 T 3 C C 1 C 2 C 3 1 2 3 7 6 M 4 5 1 2 2 3 4 5 5 ...
Страница 3: ...3 80AW1 80AW2 3 4 i j k l m n o b c d e f g h a b c d e a p ...
Страница 9: ...9 80AW1 80AW2 16 15 1 2 3 4 5 6 7 A B C D 8 2 ...
Страница 10: ...10 80AW1 80AW2 17 18 2 3 2 3 ...
Страница 11: ...11 80AW1 80AW2 20 19 10 50 10 40 b a W C G Y 10 20 21 22 Rc Rh G2 Y2 11 12 7 8 N 13 14 15 4 5 6 1 2 3 N 31 ...
Страница 12: ...12 80AW1 80AW2 21 Y2 G2 Rh Rc Y2 G2 Rh Rc J1 J8 A B J5 C ...