19
80AWX- 80AWH
English
Controller operation
Code
Nr.
Level
Variable Name
DESCRIPTION
VALUE RANGE
DEFAULT
Min
Max
109 Inst.
SlAve Output
COnfIgurAtIOn
use Days button for the selection of below
0
3
0
1
0. 3 way valve
1. Others
1
3
0. zone 1: fan coils do not work when Domestic hot water
valve is activated
1. zone 1: fan coils always working
2. zone 1: fan coils do not work when Domestic hot water
valve is activated, unless the mode is Cool
3. zone 1: Dehumidifier
2
3
0. zone 2: fan coils do not work when Domestic hot
water valve is activated
1. zone 2: fan coils always working
2. zone 2: fan coils do not work when Domestic hot
water valve is activated, unless the mode is Cool
3. zone 2: Dehumidifier
110 Inst.
HuMIDItY lIMIt
this code defines the Humidity threshold limit to enable the
output for the external de-humidifier
20
100
100
111 Inst.
AntIfrOSt t°
this code is defining the temperature below which the
water frost protection will be activated
4°C
10
4°C
Climatic Curve
112 Inst.
HeAt ClIMAtIC
nuMber
use Days button for the selection of Heat climatic curve:
0
6
0
0. - zone 1
0. no predefined climatic curve(Installer has to set climatic
curve)
1 - 6. See manual for climatic curve details
1. - zone 2
0. no predefined Climatic Curve (Installer has to set
climatic curve)
1 - 6. See manual for climatic curve details
113 Inst.
regIOn t° O
Minimum outdoor t° depending on the country where the
system is installed (Heat Climatic Curve Zone 1 and 2)
-20°C 10 °C
-7°C
114 Inst.
StOp H t° O
If outdoor t° is equal or greater then the value of this code,
minimum water tempreature is considered (Heat Climatic
Curve Zone 1 and 2)
15°C
50°C
20°C
115 Inst.
nO HeAt t W1
In Heat mode, minimum water t° going to terminal zone 1
(Heat Climatic Curve Zone 1)
20°C
60°C
20°C
116 Inst.
MAX W t° W1
In Heat mode, maximum water t° in terminal zone 1 (Heat
Climatic Curve Zone 1)
20°C
80°C
35°C
117 Inst.
nO HeAt t W2
In Heat mode, minimum water t° going to terminal zone 2
(Heat Climatic Curve Zone 2)
20°C
60°C
40°C
118 Inst.
MAX W t° W2
In Heat mode, maximum water t° in terminal zone 2 (Heat
Climatic Curve Zone 2)
20°C
80°C
55°C
119 Inst.
COOl ClIMAtIC
nuMber
Days button shall be used for the Selection of Cool climatic
curve:
0
2
0
0. - zone 1
0. no predefined climatic curve(Installer has to draw
climatic curve)
1 - 2. See manual for climatic curve details
1. - zone 2
0. no predefined climatic curve (Installer has to draw
climatic curve)
1 - 2. See manual for climatic curve details
120 Inst.
MAX regIOn t°
Maximum outdoor t° depending on the Country where the
system is installed (Cool climatic Curve Zone 1 and 2)
30°C
50°C
40°C
121 Inst.
COOl StOp t°
If outdoor t° is equal or less then the value of this code,
maximum water tempreature is considered (Cool Climatic
Curve Zone 1 and 2)
0°C
25°C
22°C
122 Inst.
MIn COOl W t°
In Cool mode, minimum water t° going to terminal zone 1
(Cool climatic Curve zone 1)
4°C
20°C
12°C
123 Inst.
MAX COOl W t°
In Cool mode, maximum water t° going to terminal zone 1
(Cool climatic Curve zone 1)
4°C
20°C
18°C
124 Inst.
MIn COOl W t°
In Cool mode, minimum water t° going to terminal zone 2
(Cool climatic Curve zone 2)
4°C
20°C
6°C
125 Inst.
MAX COOl W t°
In Cool mode, maximum water t° going to terminal zone 2
(Cool climatic Curve zone 2)
4°C
20°C
12°C
Содержание 80AWH Series
Страница 1: ...Controlmodule 80AWX 80AWH Installation Manual ...
Страница 2: ...2 80AW1 80AW2 1 2 T 1 T 2 T 3 C C 1 C 2 C 3 1 2 3 7 6 M 4 5 1 2 2 3 4 5 5 ...
Страница 3: ...3 80AW1 80AW2 3 4 i j k l m n o b c d e f g h a b c d e a p ...
Страница 9: ...9 80AW1 80AW2 16 15 1 2 3 4 5 6 7 A B C D 8 2 ...
Страница 10: ...10 80AW1 80AW2 17 18 2 3 2 3 ...
Страница 11: ...11 80AW1 80AW2 20 19 10 50 10 40 b a W C G Y 10 20 21 22 Rc Rh G2 Y2 11 12 7 8 N 13 14 15 4 5 6 1 2 3 N 31 ...
Страница 12: ...12 80AW1 80AW2 21 Y2 G2 Rh Rc Y2 G2 Rh Rc J1 J8 A B J5 C ...