80AWX- 80AWH
Controller operation
Code
Nr.
Level
Variable Name
DESCRIPTION
VALUE RANGE
DEFAULT
Min
Max
106 Inst.
INTERFACE CONFIG
Use Days button and do the selection of below
0
1
0. Domestic hot water input - configuration
0
0: contact close: input is active / contact open: input is
not active
1: contact close: input is not active / contact open: input
is active
1. Space heat/cool ON/OFF input - configuration (no impact
on Domestic Hot Water production)
1
0: contact close: unit produces space htg/clg / contact
open: unit does not produce space htg/clg
1: contact close: unit does not produce space htg/clg /
contact open: unit produces space htg/clg
2. Heat / Cool selection input- configuration
1
0: contact close: unit performs space heating / contact
open: unit performs space cooling
1: contact close: unit performs space cooling / contact
open: unit performs space heating
3. Hi energy rate input - configuration
0
0: contact close: high energy rate / contact open:
normal energy rate
1: contact close: normal energy rate / contact open:
high energy rate
4. External HTG/CLG
1
0: Mode (Heat/Cool) is determined by dry contact
1: Mode (Heat/Cool/OFF/Domestic Hot Water) is
determined by user interface (106.2 is ignored)
5. Cool Z1
0
0: Cool in Zone 1 forbidden
1: Cool in Zone 1 permitted
6. Cool Z2
0
0: Cool in Zone 2 forbidden
1: Cool in Zone 2 permitted
7. System ON / OFF input - configuration
0
0: contact close: system OFF / contact open: system
running
1: contact close: system running / contact open:
system OFF
107 Inst.
FLOW SWITCH
CONFIGURATION
Use Days button and do the selection of below
0
1
1
0
0.
0: Open - flowing / Short: not flowing
1: Short - flowing / Open: not flowing
1.
0: Do not allow water flowing when unit pump is OFF (no
external pump used)
1: Allow water flowing when unit pump is OFF (external
pump used)
108 Inst.
MASTER OUTPUT
CONFIGURATION
Use UP/Down buttons for choosing 1 to 10.
1
16
4
1. Fan Coil - Fan coils do not work when Domestic hot water
valve is activated
2. Fan Coil - Fan coils always working
3. Fan coils do not work when Domestic hot water valve is
activated, unless the mode is Cool
4. Dehumidifier
5. All alarms
6. Alarms stopping the outdoor unit
7. Alarms stopping the entire system
9. Defrost
10. All Defrost
11. Alarms stopping the outdoor unit + Defrost
12. Alarms stopping the entire Defrost
13. Not used
14. Not used
15. Not used
16. Not used
Содержание 80AWH Series
Страница 1: ...Controlmodule 80AWX 80AWH Installation Manual ...
Страница 2: ...2 80AW1 80AW2 1 2 T 1 T 2 T 3 C C 1 C 2 C 3 1 2 3 7 6 M 4 5 1 2 2 3 4 5 5 ...
Страница 3: ...3 80AW1 80AW2 3 4 i j k l m n o b c d e f g h a b c d e a p ...
Страница 9: ...9 80AW1 80AW2 16 15 1 2 3 4 5 6 7 A B C D 8 2 ...
Страница 10: ...10 80AW1 80AW2 17 18 2 3 2 3 ...
Страница 11: ...11 80AW1 80AW2 20 19 10 50 10 40 b a W C G Y 10 20 21 22 Rc Rh G2 Y2 11 12 7 8 N 13 14 15 4 5 6 1 2 3 N 31 ...
Страница 12: ...12 80AW1 80AW2 21 Y2 G2 Rh Rc Y2 G2 Rh Rc J1 J8 A B J5 C ...