59
START-UP
Use the following information and the Start-Up Checklist
on page CL-1 to check unit PRIOR to start-up.
Unit Preparation —
Check that the unit has been in-
stalled in accordance with these installation instructions and all
applicable codes.
Check all fasteners and set screws for tightness. This is
critical for bearings and fan wheels. Also, if dampers are not
motorized, check that they open and close without binding.
Internal Wiring —
Check all electrical connections in the
control box. Tighten as required.
Rain Hoods —
Some ERV units will require the outside
air and/or exhaust hood to be field installed. Caulk coupled
flanges and screw to ERV unit.
NOTE: Units for indoor applications will not have rain hoods.
The outside air hood will include aluminum water entrain-
ment filters, which should be in place prior to starting the unit.
Energy Recovery Wheel
DRIVE BELT — Turn the energy recovery wheel by hand to
verify free operation. Inspect the belt, which drives the energy
wheel rotation. Make sure the belt rides smoothly through the
pulley and over the wheel rim.
AIR SEALS — Check that the air seals, located around the
outside of the wheel and across the center, on both sides of
wheel, are secure and in good condition. Air seals which are
too tight will prevent proper rotation of the energy recovery
wheel. Re-check the air seals for tightness.
Air seal clearance may be checked by placing a sheet of
paper, like a feeler gage, against the wheel face. To adjust the
air seals, loosen all eight seal retaining screws. These screws
are located on the bearing support that spans the length of the
cassette through the wheel center. Tighten the screws so the air
seals tug slightly on the sheet of paper as the wheel is turned.
Replace the access door and apply power. Observe that the
wheel rotates freely. If the wheel does not rotate or is binding,
remove the cassette and adjust.
Blower Rotation —
First, hand-rotate the blower to en-
sure that the wheel is not rubbing against the scroll. If the
blower is rotating in the wrong direction, the ERV unit will
move some air, but will not perform properly.
To change the rotation, turn the power off and use the
following procedure:
•
Single-phase units — Rewire the motor per the instruc-
tions located on the motor.
•
Three-phase units — Interchange any two power leads.
This can be done at the motor starter.
Airflow Settings and Adjustments —
Most ERV
units have factory-installed airflow test ports, which allow the
balancer of the job to easily measure the static pressure across
the ERV wheel, and thus the system airflow cfm levels. The
static is measured on both the supply and return sides of the
wheel. See Fig. 54-56.
To achieve the highest level of effectiveness, the airflow
across the supply and return should be equal.
FACTORY SETTING — The ERV unit is factory set to
achieve the maximum airflow cfm within the cabinet’s range.
For example, a 62M170 unit has a range of 1,400 to 2,000 cfm
airflow, and when shipped will be setup to achieve the
2,000 cfm airflow level. See Fig. 57-80.
CURVE SELECTION — Refer to the fan curve for the ERV
unit being used for the application. See Fig. 57-80. Knowing
the outside air intake cfm required and the external static
pressure on the application, select the fan curve desired. The
fan curve will indicate how to set the blower motor pulley to
achieve the desired cfm level. If the job requirements are the
same as the maximum ERV unit setup, then no blower adjust-
ments are required.
ADJUST THE ERV BLOWER SPEED — If jobsite condi-
tions require blower speeds other than the factory setting, then
the ERV blower(s) will have to be adjusted. The fan curve will
specify the number of turns to be made to the adjustable pulley
on the blower motor. See Fig. 57-80.
Belt Drive Motors — Check pulley alignment and belt tension
prior to set up. To change the speeds of the blowers:
1. Shut off power supply and tag disconnect.
2. Loosen belt tension.
3. Loosen adjustable (movable) pulley flange set screw. See
Fig. 81.
4. Screw adjustable pulley side toward the fixed side to
increase speed or away from fixed side to decrease speed.
Increasing speed increases load on motor. Do not exceed
maximum load for motor.
5. Set adjustable pulley side at nearest keyway of pulley hub
and tighten set screw. See fan curves for speed change for
each turn of the adjustable pulley.
Aligning Blower and Motor Pulleys — It is important that
the pulleys be exactly in line with one another. See Fig. 82.
1. Loosen blower pulley set screw.
2. Align pulleys per illustration. Motor and blower shafts
must be parallel.
3. Tighten pulley set screws.
Adjust Belt Tension — Loosen blower motor mounting nuts.
and slide motor mounting plate away from fan scroll for proper
belt tension (
1
/
2
-in. deflection with 7 to 10 lb of force.)
MEASURE MOTOR VOLTAGE, AMPERAGE AND FAN
RPM — Measure and record the input voltage and motor
amperage(s). To measure the fan rpm, the blower door will
need to be opened. Minimize measurement time because the
motor may over-amp with the door removed. Do not operate
units with access doors/panels open as the motors will over-
load. With the blower door closed, compare measured amps to
the motor nameplate full load amps and correct if the ERV unit
is over-amping.
BELT MAINTENANCE — Premature belt failures are fre-
quently caused by improper belt tension (either too tight or too
loose), or misaligned pulleys. The proper tension for operating
a V-belt is the lowest tension at which the belts will not slip at
peak load conditions. Check belt tension two weeks after start-
up and periodically thereafter. It is very important that the drive
pulleys remain in proper alignment after adjustments are made.
Misalignment of pulleys will result in premature belt wear,
noise, vibration, and power loss. Maintain belts and motors
through the provided access panels. Refer to Fig. 82.
Text continued on page 74.
Do not operate the ERV unit without the filters and bird-
screens installed, which prevent foreign objects from enter-
ing the unit.
Содержание 62MB
Страница 81: ......