START-UP

Use the following information and the Start-Up Checklist

on page CL-1 to check unit PRIOR to start-up.

Unit Preparation —

Check that the unit has been in-

stalled in accordance with these installation instructions and all
applicable codes.

Check all fasteners and set screws for tightness. This is

critical for bearings and fan wheels. Also, if dampers are not
motorized, check that they open and close without binding.

Internal Wiring —

Check all electrical connections in the

control box. Tighten as required.

Rain Hoods —

Some ERV units will require the outside

air and/or exhaust hood to be field installed. Caulk coupled
flanges and screw to ERV unit.
NOTE: Units for indoor applications will not have rain hoods.

The outside air hood will include aluminum water entrain-

ment filters, which should be in place prior to starting the unit.

Energy Recovery Wheel

DRIVE BELT — Turn the energy recovery wheel by hand to
verify free operation. Inspect the belt, which drives the energy
wheel rotation. Make sure the belt rides smoothly through the
pulley and over the wheel rim.
AIR SEALS — Check that the air seals, located around the
outside of the wheel and across the center, on both sides of
wheel, are secure and in good condition. Air seals which are
too tight will prevent proper rotation of the energy recovery
wheel. Re-check the air seals for tightness.

Air seal clearance may be checked by placing a sheet of

paper, like a feeler gage, against the wheel face. To adjust the
air seals, loosen all eight seal retaining screws. These screws
are located on the bearing support that spans the length of the
cassette through the wheel center. Tighten the screws so the air
seals tug slightly on the sheet of paper as the wheel is turned.

Replace the access door and apply power. Observe that the

wheel rotates freely. If the wheel does not rotate or is binding,
remove the cassette and adjust.

Blower Rotation —

First, hand-rotate the blower to en-

sure that the wheel is not rubbing against the scroll. If the
blower is rotating in the wrong direction, the ERV unit will
move some air, but will not perform properly.

To change the rotation, turn the power off and use the

following procedure:

Single-phase units — Rewire the motor per the instruc-
tions located on the motor.

Three-phase units — Interchange any two power leads.
This can be done at the motor starter.

Airflow Settings and Adjustments —

Most ERV

units have factory-installed airflow test ports, which allow the
balancer of the job to easily measure the static pressure across
the ERV wheel, and thus the system airflow cfm levels. The
static is measured on both the supply and return sides of the
wheel. See Fig. 54-56.

To achieve the highest level of effectiveness, the airflow

across the supply and return should be equal.
FACTORY SETTING — The ERV unit is factory set to
achieve the maximum airflow cfm within the cabinet’s range.
For example, a 62M170 unit has a range of 1,400 to 2,000 cfm
airflow, and when shipped will be setup to achieve the
2,000 cfm airflow level. See Fig. 57-80.
CURVE SELECTION — Refer to the fan curve for the ERV
unit being used for the application. See Fig. 57-80. Knowing
the outside air intake cfm required and the external static
pressure on the application, select the fan curve desired. The
fan curve will indicate how to set the blower motor pulley to
achieve the desired cfm level. If the job requirements are the
same as the maximum ERV unit setup, then no blower adjust-
ments are required.
ADJUST THE ERV BLOWER SPEED — If jobsite condi-
tions require blower speeds other than the factory setting, then
the ERV blower(s) will have to be adjusted. The fan curve will
specify the number of turns to be made to the adjustable pulley
on the blower motor. See Fig. 57-80.
Belt Drive Motors — Check pulley alignment and belt tension
prior to set up. To change the speeds of the blowers:

1. Shut off power supply and tag disconnect.
2. Loosen belt tension.
3. Loosen adjustable (movable) pulley flange set screw. See

Fig. 81.

4. Screw adjustable pulley side toward the fixed side to

increase speed or away from fixed side to decrease speed.
Increasing speed increases load on motor. Do not exceed
maximum load for motor.

5. Set adjustable pulley side at nearest keyway of pulley hub

and tighten set screw. See fan curves for speed change for
each turn of the adjustable pulley.

Aligning Blower and Motor Pulleys — It is important that
the pulleys be exactly in line with one another. See Fig. 82.

1. Loosen blower pulley set screw.
2. Align pulleys per illustration. Motor and blower shafts

must be parallel.

3. Tighten pulley set screws.

Adjust Belt Tension — Loosen blower motor mounting nuts.
and slide motor mounting plate away from fan scroll for proper
belt tension (

1

/

2

-in. deflection with 7 to 10 lb of force.)

MEASURE MOTOR VOLTAGE, AMPERAGE AND FAN
RPM — Measure and record the input voltage and motor
amperage(s). To measure the fan rpm, the blower door will
need to be opened. Minimize measurement time because the
motor may over-amp with the door removed. Do not operate
units with access doors/panels open as the motors will over-
load. With the blower door closed, compare measured amps to
the motor nameplate full load amps and correct if the ERV unit
is over-amping.
BELT MAINTENANCE — Premature belt failures are fre-
quently caused by improper belt tension (either too tight or too
loose), or misaligned pulleys. The proper tension for operating
a V-belt is the lowest tension at which the belts will not slip at
peak load conditions. Check belt tension two weeks after start-
up and periodically thereafter. It is very important that the drive
pulleys remain in proper alignment after adjustments are made.
Misalignment of pulleys will result in premature belt wear,
noise, vibration, and power loss. Maintain belts and motors
through the provided access panels. Refer to Fig. 82.

Text continued on page 74.

Do not operate the ERV unit without the filters and bird-
screens installed, which prevent foreign objects from enter-
ing the unit.

Содержание 62MB

Страница 1: ...formed by trained service personnel When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Fo...

Страница 2: ...ing recommendations COUPLED APPLICATIONS The ERV unit can be in stalled directly coupled to a Carrier rooftop unit The connec tion between the ERV and HVAC Heating Ventilation and Air Conditioning uni...

Страница 3: ...d the top perimeter of the curb and around the supply and return opening Some stand alone curbs will not have duct open ings Gasket strips must fit tightly together leaving no gaps for leakage Install...

Страница 4: ...turn Air S A Supply Air IMPORTANT Insulation on deck pans must face up Fig 3 Roof Curb 62M075 950 for Vertical Stand Alone Applications ERV Curb C B A D 62M075 120 curb is shipped with deckpans insula...

Страница 5: ...ATION GASKETING ROOF CURB 62M UNIT SIZE CURB PART NO DIMENSIONS in A B C D E 075 120 62M A CRB 14MC 30 5 14 27 1 5 19 81 170 285 62M B CRB 14MC 49 63 14 45 5 1 75 37 81 LEGEND NOTE Roof curb shipped u...

Страница 6: ...53 29 98 SUPPLY AIR RETURN AIR HORIZONTAL UNITS ONLY REAR SIDE 45 75 SUPPLY AIR OPTIONAL 4 83 7 13 3 91 11 15 10 50 3 95 5 34 TOP SIDE RETURN AIR OPTIONAL 16 00 OPTIONAL INDOOR PREHEATER ERV WHEEL 19...

Страница 7: ...R OUTSIDE AIR POWER ENTRY 45 75 13 38 11 00 8 97 12 96 SUPPLY AIR OPTIONAL 4 83 7 13 3 91 11 15 10 50 3 95 5 34 OUTSIDE AIR HOOD AND OPTIONAL PREHEATER RETURN AIR OPTIONAL A A VIEW A A ERV WHEEL 16 00...

Страница 8: ...TEST PORTS OPTIONAL PREHEATER INDOOR ACCESS DOOR 18 88 VIEW A A OPTIONAL RETURN AIR BOTTOM RETURN ONLY SUPPLY AIR BOTTOM SUPPLY ONLY OPTIONAL PREHEATER 10 93 6 18 12 98 3 46 9 25 6 65 6 60 10 39 19 04...

Страница 9: ...W TEST PORTS OPTIONAL TOP OF CURB ACCESS DOOR DETAIL A SEE DETAIL A LEFT SIDE ACCESS DOOR RIGHT SIDE OPTIONAL RETURN AIR BOTTOM RETURN ONLY SUPPLY AIR BOTTOM SUPPLY ONLY OPTIONAL PREHEATER OUTDOOR AIR...

Страница 10: ...R EXHAUST AIR ACCESS DOOR POWER ENTRY OPTIONAL DISCONNECT EXHAUST AIR OUTLET RETURN AIR OPENING SUPPLY AIR OPENING TOP SIDE 8 21 15 28 6 10 22 33 15 63 8 20 8 68 13 75 RETURN AIR A A ERV WHEEL VIEW A...

Страница 11: ...D TOP SIDE 8 21 16 19 15 28 6 10 22 33 15 63 8 20 8 68 13 75 26 45 64 OPTIONAL PREHEATER A A ERV WHEEL 14 57 12 50 43 38 14 86 62 03 LEFT SIDE EXHAUST AIR POWER ENTRY OPTIONAL DISCONNECT 14 84 15 96 O...

Страница 12: ...6 11 7 66 6 11 6 61 REAR SIDE SUPPLY AIR RETURN AIR TOP SIDE EXHAUST AIR OUTLET 21 11 RETURN AIR OPENING BOTTOM RETURN ONLY 6 93 25 76 18 62 8 01 15 94 6 88 SUPPLY AIR OPENING BOTTOM SUPPLY ONLY A A V...

Страница 13: ...TTOM SUPPLY ONLY A A 20 00 17 00 49 1 72 63 LEFT SIDE POWER ENTRY OPTIONAL DISCONNECT EXHAUST AIR OPTIONAL AIRFLOW TEST PORTS VIEW A A TOP OF CURB OUTSIDE AIR HOOD 12 52 37 50 19 00 2 87 28 50 37 50 6...

Страница 14: ...EST PORTS OPTIONAL ACCESS DOOR ACCESS DOOR EXHAUST AIR OUTLET RETURN AIR OPENING SUPPLY AIR OPENING 31 67 6 43 34 73 21 88 17 07 6 42 18 75 TOP SIDE 11 02 VIEW A A A A OUTSIDE AIR EXHAUST AIR 40 12 34...

Страница 15: ...25 9 01 48 98 107 75 LEFT SIDE POWER ENTRY OPTIONAL DISCONNECT LOCATION AIRFLOW TEST PORTS OPTIONAL EXHAUST AIR OUTSIDE AIR HOOD RIGHT SIDE FRONT SIDE 49 01 35 75 28 00 16 19 7 69 7 69 13 11 REAR SID...

Страница 16: ...quipmentsupport 35 Side View A A A A Rooftop Unit Curb ERV Unit Support 673 8 37 3 35 Supply Return AccessoryTransition Panelcovering returnchamber Accessdoorto adjustbalancing damper To62M040Unit Bal...

Страница 17: ...673 8 37 3 35 Supply Return To62M040Unit Accessdoorto adjust balancing damper AccessoryTransition Panelcovering returnchamber Balancingdamper 35 Side View A A Rooftop Unit Curb ERV Unit Support Field...

Страница 18: ...orto adjust balancing damper AccessoryTransition Return RooftopUnit 805 16 35 4411 16 Return TopView To62M040Unit 35 Side View A A Rooftop Unit Curb ERV Unit Support 43 8 ROOFTOP UNIT MODEL ROOFTOP SI...

Страница 19: ...rto adjust balancing damper To62M040Unit AccessoryTransition RooftopUnit 805 16 35 4411 16 TopView 35 Side View A A Rooftop Unit Curb ERV Unit Support 43 8 ROOFTOP UNIT MODEL ROOFTOP SIZE TRANSITION P...

Страница 20: ...6 ton rooftop unit 62MA 900 001 Equipment Support 10 4 Equipment Support Roof 14 Standard Roof curb for3 to 6 tonrooftop unit A A SIDE VIEW TOP VIEW A A 62MA 900 001 Supply Air 35 ROOF CURB LAYOUT Fig...

Страница 21: ...TRANSITION P N ERV CURB P N ROOFTOP ECONOMIZER DIMENSIONS in A B 48 50HJ TF TJ TM 004 007 62M ATR HJ36 D 62M A CRB 14MC 62MA 900 004 673 8 373 16 008 009 62M ATR HJ78 D 62M A CRB 14MC 62MA 900 005 781...

Страница 22: ...FTOP SIZE TRANSITION P N ERV CURB P N ROOFTOP ECONOMIZER DIMENSIONS in A B 48 50HJ TF TJ TM 004 007 62M ATR HJ36 H 62M A CRB 14MC 62MA 900 008 673 8 373 16 008 009 62M ATR HJ78 H 62M A CRB 14MC 62MA 9...

Страница 23: ...rb A A Locator pieces included with ERV curb must be watertight ROOFTOP MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 03 07 62M ATR PG26 D 62M A CRB 14MC 805 16 4411 16 08 14 62...

Страница 24: ...ces included with ERV curb must be watertight ROOFTOP MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 03 07 62M ATR PG26 H 62M A CRB 14MC 805 16 4411 16 08 14 62M ATR PG712 H 62M...

Страница 25: ...L ROOFTOP SIZE TRANSITION P N ERV CURB P N ROOFTOP ECONOMIZER DIMENSIONS in A B 48 50HJ TF TJ TM 004 007 62M BTR HJ36 D 62M B CRB 14MC 62MA 900 004 673 8 373 16 008 009 62M BTR HJ78 D 62M B CRB 14MC 6...

Страница 26: ...ODEL ROOFTOP SIZE TRANSITION P N ERV CURB P N ROOFTOP ECONOMIZER DIMENSIONS in A B 48 50HJ TF TJ TM 004 007 62M BTR HJ36 H 62M B CRB 14MC 62MA 900 008 673 8 373 16 008 009 62M BTR HJ78 H 62M B CRB 14M...

Страница 27: ...VIEW A A A A ROOFTOP UNIT MODEL ROOFTOP SIZE TRANSITION P N ERV CURB P N 48 50TJ TM 016 028 62M BTR HJ1525 D 62M B CRB 14S 48 50HJ 015 017 62M BTR HJ1525 D 62M B CRB 14S LEGEND NOTES 1 The 62M ERV un...

Страница 28: ...b Return Locator pieces included with ERV curb must be watertight ROOFTOP MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 03 07 62M BTR PG26 D 62M A CRB 14MC 805 16 4411 16 08 14...

Страница 29: ...r pieces included with ERV curb must be watertight ROOFTOP MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 03 07 62M BTR PG26 H 62M B CRB 14MC 805 16 4411 16 08 14 62M BTR PG712 H...

Страница 30: ...ITION ERV CURB DIMENSIONS in A B 48 50PG 20 28 62M BTR HG1525 H 62M B CRB 14MC 114 4 78 6 48 50HJ 020 028 62M BTR HG1525 H 62M B CRB 14MC 114 4 78 6 LEGEND NOTES 1 The ERV unit can be used with a fact...

Страница 31: ...E 62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 20 28 62M BTR HG1525 D 62M B CRB 14MC 114 4 78 6 48 50HJ 020 028 62M BTR HG1525 D 62M B CRB 14MC 114 4 78 6 LEGEND NOTES 1 The ERV unit can be used...

Страница 32: ...Return Supply Rooftop Unit Curb ERV Unit Curb ERV Curb Return Supply A A ROOFTOP UNIT MODEL ROOFTOP SIZE TRANSITION P N ERV CURB P N ROOFTOP ECONOMIZER 48 50HJ TF TJ TM 012 014 62M CTR HJ1012 D 62M C...

Страница 33: ...Ton Rooftop Unit A A 33 1 2 Side View A A Rooftop Unit Curb ERV Unit Curb ROOFTOP UNIT MODEL ROOFTOP SIZE TRANSITION P N ERV CURB P N ROOFTOP ECONOMIZER 48 50HJ TF TJ TM Without Economizer 012 014 62M...

Страница 34: ...TURN Rooftop Unit Curb ERV Unit Curb Fig 35 62MD ME330 640 Coupled with Carrier 48 50TJ TM016 028 and 48 50HJ015 017 Vertical Discharge Rooftop Unit ROOFTOP UNIT MODEL ROOFTOP SIZE TRANSITION P N ERV...

Страница 35: ...rb ERV Unit Curb CurbDetail Rooftop Unit Curb ROOFTOP UNIT MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B C 48 50PG 08 14 62M CTR PG712 D 62M C CRB 14M 923 4 5315 16 10 LEGEND NOTE When...

Страница 36: ...tail Rooftop Unit Curb A A ROOFTOP UNIT MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B C 48 50PG 08 14 62M CTR PG712 H 62M C CRB 14M 923 4 5315 16 10 LEGEND NOTE When using a 62M ERV uni...

Страница 37: ...ANSITION ERV CURB DIMENSIONS in A B 48 50PG 20 28 62M CTR HG1525 H 62M C CRB 14M 114 4 78 6 48 50HJ 020 028 62M CTR HG1525 H 62M B CRB 14M 114 4 78 6 LEGEND NOTES 1 The ERV unit can be used with a fac...

Страница 38: ...62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 20 28 62M CTR HG1525 D 62M C CRB 14M 114 4 78 6 48 50HJ 020 028 62M CTR HG1525 D 62M B CRB 14M 114 4 78 6 LEGEND NOTES 1 The ERV unit can be used with...

Страница 39: ...rb ERV Curb 62M Unit Accessory Transition ERV Curb Rooftop Unit Curb ROOFTOP UNIT MODEL ROOFTOP SIZE TRANSITION P N ERV CURB P N 48 50A 020 060 62M CTR AJ2060 D 62M C CRB 14M LEGEND NOTES 1 The ERV un...

Страница 40: ...P ECONOMIZER 48 50TJ TM 016 028 62M DTR HJ1525 D 62M D CRB 14M 62MA 900 007 48 50HJ 015 017 62M DTR HJ1525 D 62M D CRB 14M 62MA 900 007 LEGEND NOTES 1 The standard factory economizer cannot be used wh...

Страница 41: ...ransition ROOFTOP MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 20 28 62M DTR HG1525 H 62M D CRB 14M 114 4 78 6 48 50HJ 020 028 62M DTR HG1525 H 62M D CRB 14M 114 4 78 6 LEGEND...

Страница 42: ...ERV Unit Curb Curb Detail Accessory Transition A A ROOFTOP MODEL ROOFTOP SIZE 62M TRANSITION ERV CURB DIMENSIONS in A B 48 50PG 20 28 62M DTR HG1525 D 62M D CRB 14M 114 4 78 6 48 50HJ 020 028 62M DTR...

Страница 43: ...A A Exhaust Hood A A Rooftop Unit Curb ERV Unit Curb Top View ROOFTOP UNIT MODEL ROOFTOP SIZE TRANSITION P N ERV CURB P N 48 50A 020 060 62M DTR AJ2060 D 62M D CRB 14M LEGEND NOTES 1 The standard fac...

Страница 44: ...r blower mounted over supply opening in base Outside air intake hood outside units only Exhaust blower ERV Wheel 2 in pre filters outside air Outside air rainhood ERV wheel Supply air blower Supply du...

Страница 45: ...V unit consider required service clearances See Table 1 for unit weights to determine if building struc ture reinforcements are required Determine a Method for Mounting The method for mount ing and se...

Страница 46: ...x 25 x 2 2 20 x 25 x 2 2 20 x 25 x 2 2 20 x 25 x 2 Outside Air Qty Size L x W x D in 1 12 x 20 x 2 1 18 x 25 x 2 1 18 x 25 x 2 2 20 x 25 x 2 2 20 x 25 x 2 2 20 x 25 x 2 UNIT 62M 330 430 550 640 750 95...

Страница 47: ...2 and 3 for electrical and configuration data ELECTRICAL CONNECTIONS The ERV unit must have its own electrical disconnect box If the disconnect option has not been ordered from the factory it must be...

Страница 48: ...76 4 94 2 01 5 5 7 13 8 53 8 53 5 03 8 120 115 1 60 0 7 16 1 33 09 40 00 52 00 60 50 2 50 48 61 74 69 39 17 39 80 60 5 76 57 94 35 95 48 43 48 200 90 230 1 60 0 3 8 16 66 20 00 26 00 30 25 2 25 36 30...

Страница 49: ...32 10 05 18 330 208 230 3 60 1 2 6 8 2 15 13 18 50 23 30 30 20 8 35 24 43 63 43 63 20 11 60 40 10 40 26 49 91 49 91 25 13 45 15 52 83 65 62 65 62 37 70 80 60 460 3 60 3 4 7 62 10 00 12 25 30 12 8 17...

Страница 50: ...10 71 96 89 54 99 13 25 13 200 90 15 84 53 105 25 111 70 37 70 110 20 97 09 120 95 124 26 50 26 460 3 60 1 2 11 23 36 29 00 36 95 60 35 10 35 93 44 71 49 52 12 57 45 15 42 21 52 56 55 80 18 85 80 50 2...

Страница 51: ...28 17 27 30 15 5 16 28 19 56 22 29 5 03 30 20 8 23 82 28 99 29 83 12 57 40 25 460 3 60 2 6 2 1 5 53 6 51 8 46 30 8 2 8 05 9 65 10 98 2 51 10 5 11 82 14 36 14 75 6 28 12 575 3 60 2 1 1 7 4 41 5 13 6 6...

Страница 52: ...6 12 26 12 12 57 40 25 15 28 00 33 98 33 98 18 85 30 575 3 60 3 6 2 7 7 83 8 97 11 66 30 10 8 15 87 19 03 19 71 8 04 18 10 17 88 21 54 21 72 10 05 20 15 22 91 27 82 27 82 15 08 40 25 430 208 230 3 60...

Страница 53: ...4 91 65 10 84 64 100 80 10 80 05 96 52 109 77 25 13 200 100 15 92 61 112 23 122 33 37 70 110 20 105 18 127 93 134 90 50 26 125 460 3 60 1 2 12 9 11 27 20 32 29 41 98 60 40 10 39 76 48 00 54 55 12 57 8...

Страница 54: ...Brown Black Jumper in plug leave 20 19 18 17 16 15 14 Actuator Motor Economizer End switch Important Remove and re install through end switch 20 19 18 17 16 15 14 Switch Bracket Economizer Gear hub Ec...

Страница 55: ...r is installed and fused disconnect option is selected fusing will be separated ERV and pre heater will have separate fusing 8 DPDT relay may be substituted If so pins 2 5 and 8 will not exist 9 Follo...

Страница 56: ...transformer may substitute internal breaker on secondary for fuse 5 Door switches are optional 6 DPDT relay may be substituted If so pins 2 5 and 8 will not exist Before performing service or mainten...

Страница 57: ...l shock could cause personal injury or death 4 Variable frequency drives are sensitive to the polarity of a 0 to 10 volt DC control signal If the control source is acting properly and the voltage vari...

Страница 58: ...ee Note DISCONNECT FIOP NOTES 1 Thermostat is factory set at 5 degrees Range is 30 to 100 F 2 MInimum airflow is 05 in wg Fig 53 Typical Wiring Schematic Optional Preheat High Voltage and Control Circ...

Страница 59: ...a 62M170 unit has a range of 1 400 to 2 000 cfm airflow and when shipped will be setup to achieve the 2 000 cfm airflow level See Fig 57 80 CURVE SELECTION Refer to the fan curve for the ERV unit bei...

Страница 60: ...00 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 4800 5000 Airflow cfm Pressure Drop in wg 62M170 225 62M285 62M330 430 Fig 55 62M170 430 ERV Wheel Pressure Drop Fig 54 62...

Страница 61: ...000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 10500 11000 Airflow cfm Pressure Drop in wg 62M550 640 62M750 950 Fig 56 62M550 950 ERV Wheel Pressure Drop cont Data based on measurements taken...

Страница 62: ...ply Air High Speed Supply Air Speed Three Supply Air Speed Two Supply Air Low Speed AIirflow cfm External Static Pressure in wg 0 100 200 300 400 500 600 0 00 0 20 0 40 0 60 0 80 1 00 1 20 1 40 1 60 E...

Страница 63: ...000 1200 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1136 rpm 2 turns 1081 rpm 3 turns 1010 rpm 4 turns 946 rpm 5 turns Airflow cfm External Static in wg NOTE Fan data includes pressure drop for 30 efficient...

Страница 64: ...1075 1275 1475 0 2 0 4 0 6 0 8 1 0 1399 rpm 2 turns 1332 rpm 3 turns 1244 rpm 4 turns 1162 rpm 5 turns Airflow cfm External Static in wg NOTE Fan data includes pressure drop for 30 efficient 2 in fil...

Страница 65: ...400 1600 1800 2000 2200 2400 2600 0 2 0 4 0 6 0 8 1 1068 rpm 3 turns 1045 rpm 4 turns 1018 rpm 5 turns 977 rpm 6 turns External Static in wg Airflow cfm NOTE Fan data includes pressure drop for 30 eff...

Страница 66: ...00 0 2 0 4 0 6 0 8 1 1077 rpm 3 turns 1052 rpm 4 turns 1024 rpm 5 turns 964 rpm 6 turns External Static in wg Airflow cfm NOTE Fan data includes pressure drop for 30 efficient 2 in filters NOTE Fan da...

Страница 67: ...3500 0 1 0 3 0 5 0 7 0 9 1 1 1193 rpm 2 turns 1147 rpm 3 turns 1097 rpm 4 turns 1062 rpm 5 turns External Static in wg Airflow cfm 2500 2000 NOTE Fan data includes pressure drop for 30 efficient 2 in...

Страница 68: ...000 3200 3400 3600 3800 4000 0 13 0 20 0 30 0 40 0 50 842 rpm 2 turns 808 rpm 3 turns 770 rpm 4 turns External Static in wg Airflow cfm NOTE Fan data includes pressure drop for 30 efficient 2 in filte...

Страница 69: ...000 3500 4000 4500 5000 5500 0 20 0 40 0 60 0 80 1 00 871 rpm 4 turns 891 rpm 5 turns External Static in wg Airflow cfm NOTE Fan data includes pressure drop for 30 efficient 2 in filters NOTE Fan data...

Страница 70: ...0 3500 4000 4500 5000 5500 6000 6500 0 3 0 4 0 6 0 8 1 0 1 2 1109 rpm 2 turns 1049 rpm 3 turns 998 rpm 4 turns 947 rpm 5 turns Airflow cfm External Static in wg NOTE Fan data includes pressure drop fo...

Страница 71: ...7000 7500 8000 0 4 0 5 0 6 0 7 0 9 1202 rpm 0 turns 1152 rpm 1 turn 1123 rpm 2 turns 1096 rpm 3 turns External Static in wg Airflow cfm NOTE Fan data includes pressure drop for 30 efficient 2 in filt...

Страница 72: ...000 6500 7000 7500 8000 8500 9000 0 3 0 5 0 7 0 9 1 1 923 rpm 0 turns 898 rpm 1 turn 862 rpm 2 turns 844 rpm 3 turns 813 rpm 4 turns External Static in wg Airflow cfm NOTE Fan data includes pressure d...

Страница 73: ...7500 8000 8500 9000 9500 10000 10500 11000 0 3 0 5 0 7 0 9 1 1 1024 rpm 3 turns 962 rpm 4 turns 929 rpm 5 turns Airflow cfm External Static in wg NOTE Fan data includes pressure drop for 30 efficient...

Страница 74: ...eel exceeds the set point When the frost protection option is activated the following will occur ERV wheel turns on Outdoor air blower motor turns off EXH blower motor is on Occupied Mode with the Pre...

Страница 75: ...Option When using the wheel bypass option with the stop jog option this allows free cooling through the wheel limited by the ERV cfm limits With this option the unit can be in free cooling or not depe...

Страница 76: ...ween nose and rim end of segment must face the motor side of the cassette See Fig 88 3 Ease the segment downward until its outer rim clears the inside of the wheel rim Then press the segment inward ag...

Страница 77: ...shaft Fig 91 shows belt partially through the opening 6 Reinstall the bearing onto the wheel shaft being careful to engage the two locating pins into the holes in the bearing support beam Secure the...

Страница 78: ...ample annual washing of energy transfer may be necessary to maintain latent transfer efficiency Proper cleaning of the energy recovery wheel will restore latent effectiveness to near original performa...

Страница 79: ...e adhe sive to prevent loosening Annually confirm setscrew is secure The wheel drive belt is a urethane stretch belt designed to provide constant tension through the life of the belt No adjust ment is...

Страница 80: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 536 220 Printed in U S A Form 62M 1SI Pg 80 1 06 Replaces New Copyright 2006 Carr...

Страница 81: ......

Страница 82: ...Control Option Yes No NOTE Do Not Use With Economizer Option Factory installed Stops the ERV wheel rotation for free cooling Stop Jog Control Option Yes No NOTE Use With Economizer Option Factory ins...

Отзывы: