50
Table 2 — Electrical Data Without VAV Option (cont)
LEGEND
*Fused disconnect only.
†Exhaust and supply fan motors are 230-1-60.
UNIT SIZE
62M
VOLTAGE
(V-Ph-Hz)
ERV WHEEL
FLA
EXHAUST AND SUPPLY MOTOR
HEATER
SIZE
(kW)
POWER SUPPLY
PRE-HEATER
(Optional)
FLA
DISCONNECT
(Optional)
NEC - FLA
Hp
FLA
MCA
MOCP
Amps
Fuse Size†
Amps
640
208/230-3-60
1.2
22
7.5
—
45.53
56.50
72.70
—
100
70
8
65.64
81.63
92.81
20.11
200
90
10
70.66
87.91
97.83
25.13
15
83.23 103.62 110.40
37.70
110
460-3-60
11
—
22.82
29.00
36.95
—
60
35
8
32.87
41.57
47.00
10.05
45
10
35.38
44.71
49.52
12.57
60
15
41.66
52.56
55.80
18.85
80
50
575-3-60
9
—
18.65
24.00
30.45
—
40
30
8
26.69
34.05
38.49
8.04
60
35
10
28.70
36.57
40.50
10.05
40
15
33.73
42.85
45.53
15.08
45
750
208/230-3-60
2.5
22
—
46.83
58.13
74.00
—
100
70
10
71.96
89.54
99.13
25.13
200
90
15
84.53 105.25 111.70
37.70
110
20
97.09 120.95 124.26
50.26
460-3-60
1.2
11
—
23.36
29.00
36.95
—
60
35
10
35.93
44.71
49.52
12.57
45
15
42.21
52.56
55.80
18.85
80
50
20
48.49
60.41
62.08
25.13
80
60
575-3-60
1.4
9
—
19.53
24.25
30.65
—
40
30
10
29.58
36.82
40.70
10.05
60
40
15
34.61
43.10
45.73
15.08
45
20
39.64
49.38
50.76
20.11
50
950
208/230-3-60
2.5
30.8
10
—
64.46
80.13 102.60
—
200
100
10
92.25 114.86 130.39
27.79
125
15
106.15 132.23 144.29
41.69
20
120.04 149.60 158.18
55.58
N/A
460-3-60
1.2
14
—
29.36
36.50
46.70
—
60
45
10
41.93
52.21
59.27
12.57
80
50
15
48.21
60.06
65.55
18.85
80
60
20
54.49
67.91
71.83
25.13
100
70
575-3-60
1.4
11
—
23.53
29.25
37.15
—
60
35
10
33.58
41.82
47.20
10.05
45
15
38.61
48.10
52.23
15.08
80
50
20
43.64
54.38
57.26
20.11
ERV
—
Energy Recovery Ventilator
FLA
—
Full Load Amps
Hp
—
Horsepower
MCA
—
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection
NEC
—
National Electric Code
N/A
—
Not Applicable