94
inducer motor speed gets within 15% of the required inter-
mediate-heat RPM the furnace control CPU will start a 5
second blower airflow change delay. After the 5 second
blower airflow change delay is completed the blower air-
flow will transition to minimum-heat airflow. At this point
the furnace control CPU will energize the PSR relay to open
the NC contact and slowly decrease the inducer motor
speed to the required minimum-heat RPM. When the
PSR relay is energized and the NC contact opens the fur-
nace control CPU will reduce the gas rate to minimum-heat
RPM.
Two-Stage Thermostat and Two-Stage Intermediate/
Maximum Heating
See Fig. 34 and 35 for thermostat connections
NOTE
: In this mode the intermediate-heat only switch SW4-2
must be ON to select the intermediate-heat only operation mode in
response to closing the thermostat R to W1 circuit. Closing the
thermostat
R
to
W1-and-W2
circuits
always
causes
maximum-heat operation, regardless of the setting of the
intermediate-heat only switch.
The wall thermostat ”calls for heat”, closing the R to W1 circuit for
intermediate-heat or closing the R to W1-and-W2 circuits for
maximum-heat. The furnace control performs a self-check, and
verifies the low, medium and high pressure switch contacts LPS,
MPS and HPS are open , then de-energizes the PSR relay to close
the NC contact.
The start up and shut down functions and delays described above
apply to the 2-stage intermediate/maximum heating mode as well,
except for switching from maximum- to intermediate-heat.
1.
Switching from Maximum- to Intermediate-Heat
—
If
the thermostat R to W2 circuit opens, and the R to W1 cir-
cuit remains closed, the furnace control CPU will gradually
decrease the inducer motor speed to the required interme-
diate-heat RPM. When the inducer motor IDM reduces
pressure sufficiently, the high pressure switch HPS will
open and the gas rate will be changed to intermediate-heat.
When the inducer motor speed gets within 15% of the re-
quired intermediate-heat RPM the furnace control CPU will
start a 5 second blower airflow change delay. After the 5
second blower airflow change delay is completed the
blower airflow will transition to intermediate-heat airflow.
Cooling Mode
The thermostat “calls for cooling.”
1.
Single-Speed Cooling
See Fig. 34 and 35 for thermostat connections.
The thermostat closes the R to G-and-Y circuits. The R to Y circuit
starts the outdoor unit, and the R to G-and-Y/Y2 circuits start the
furnace blower motor BLWM on cooling airflow. Cooling airflow
is based on the A/C selection shown in Fig. 56.
The electronic air cleaner terminal EAC-1 is energized with 115
vac when the blower motor BLWM is operating. When the
thermostat is satisfied, the R to G-and-Y circuits are opened. The
outdoor unit will stop, and the furnace blower motor BLWM will
continue operating at cooling airflow for an additional 90 seconds.
Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5
seconds. See Fig. 34.
2.
Single-Stage Thermostat and Two-Speed Cooling
(Ad-
aptive Mode)
See Fig. 34 and 35 for thermostat connections.
This furnace can operate a two-speed cooling unit with a
single-stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled operation, which
selects low-cooling or high-cooling operation. This selection is
based upon the stored history of the length of previous cooling
period of the single-stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must be
connected to enable the adaptive cooling mode in response to a call
for cooling. See Fig. 34. When in place the furnace control CPU
can turn on the air conditioning relay ACR to energize the Y/Y2
terminal and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either
low- or high-cooling. If starting up in low-cooling, the furnace
control CPU determines the low-cooling on-time (from 0 to 20
minutes) which is permitted before switching to high-cooling.
If the power is interrupted, the stored history is erased and the
furnace control CPU will select low-cooling for up to 20 minutes
and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high-cooling, as long
as the thermostat continues to call for cooling. Subsequent
selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G and- Y
circuits. The R to Y1 circuit starts the outdoor unit on low-cooling
speed, and the R to G-and-Y1 circuits starts the furnace blower
motor BLWM at low-cooling airflow which is the true on-board
CF selection as shown in Fig. 56.
If the furnace control CPU switches from low-cooling to high
cooling, the furnace control CPU will energize the air conditioning
relay ACR. When the air conditioning relay ACR is energized the
R to Y1-and-Y2 circuits switch the outdoor unit to high-cooling
speed, and the R to G-and-Y1- and-Y/Y2 circuits transition the
furnace blower motor BLWM to high-cooling airflow.
High-cooling airflow is based on the A/C selection shown in Fig.
56.
NOTE
: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the
furnace blower motor BLWM transitions to run at high-cooling
airflow.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuit are
opened. The outdoor unit stops, and the furnace blower BLWM
and electronic air cleaner terminal EAC-1 will remain energized for
an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off-delay to 5 seconds. See Fig. 34.
3.
Two Stage Thermostat and Two-Speed Cooling
See Fig. 34 and 35 for thermostat connections.
NOTE
: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit
staging. See Fig. 34.
The thermostat closes the R to G-and-Y1 circuits for low cooling
or closes the R to G-and-Y1-and-Y2 circuits for high cooling. The
R to Y1 circuit starts the outdoor unit on low cooling speed, and
the R to G-and-Y1 circuit starts the furnace blower motor BLWM
at low-cooling airflow which is the true on-board CF selection as
shown in Fig. 56. The R to Y1-and-Y2 circuits start the outdoor
unit on high-cooling speed, and the R to G-and-Y/Y2 circuits start
the furnace blower motor BLWM at high-cooling airflow.
High-cooling airflow is based on the A/C selection shown in Fig.
56.
The electronic air cleaner terminal EAC-1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y1 or R to
G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, and
the furnace blower BLWM and electronic air cleaner terminal
EAC-1 will remain energized for an additional 90 seconds. Jumper
Y1 to DHUM to reduce the cooling off-delay to 5 seconds. See
Fig. 56.
4.
Dehumidification Mode
See Fig. 34 and 35 for thermostat connections.
The dehumidification output, D or DHUM on the Thermostat
should be connected to the furnace control thermostat terminal
59MN
7A