OVERCHARGING UNIT INCREASES THE RISK OF
NUISANCE HIGH PRESSURE SWITCH TRIPS
CAUTION DO NOT OVERCHARGE UNIT
20 TON HEAT PUMP CHARGING CHART - R410A REFRIGERANT
(COOLING MODE) - CIRCUIT A
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
650
Compressor Discharge Pressure, (psig)
Outdoor Coil Leaving Temperature, (Degrees F)
Add Charge if Above the Curve
Remove Charge if Below the Curve
IN HEATING MODE,
RECLAIM CHARGE AND RECHARGE UNIT PER NAMEPLATE
50HE501616 - A
C12027
Fig. 23 -- Cooling Charging Chart -- 50TCQ--D24 Circuit A
OVERCHARGING UNIT INCREASES THE RISK OF
NUISANCE HIGH PRESSURE SWITCH TRIPS
CAUTION DO NOT OVERCHARGE UNIT
20 TON HEAT PUMP CHARGING CHART - R410A REFRIGERANT
(COOLING CODE) - CIRCUIT B
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
650
Compressor Discharge Pressure, (psig)
Outdoor Coi
l Leavi
n
g Tem
p
erature,
(Degrees F)
Add Charge if Above the Curve
Remove Charge if Below the Curve
IN HEATING MODE,
RECLAIM CHARGE AND RECHARGE UNIT PER NAMEPLATE
50HE501617 - A
C12028
Fig. 24 -- Cooling Charging Chart -- 50TCQ--D24 Circuit B
Содержание 50TCQD17-D24
Страница 36: ...36 C10818 Fig 51 RTU OPEN Control Module 50TCQ ...
Страница 46: ...46 APPENDIX IV WIRING DIAGRAMS cont C150373 Fig 52 50TCQ D17 Power Wiring Diagram 208 230 3 60 ...
Страница 47: ...47 APPENDIX IV WIRING DIAGRAMS cont C12399 Fig 53 50TCQ D17 Power Wiring Diagram 460 3 60 575 3 60 ...
Страница 48: ...48 APPENDIX IV WIRING DIAGRAMS cont C12686 Fig 54 50TCQ D24 Power Wiring Diagram 208 230 3 60 ...
Страница 49: ...49 APPENDIX IV WIRING DIAGRAMS cont C12401 Fig 55 50TCQ D24 Power Wiring Diagram 460 3 60 575 3 60 ...
Страница 51: ...51 APPENDIX IV WIRING DIAGRAMS cont C160005 Fig 57 RTU OPEN Control Diagram ...
Страница 52: ...52 APPENDIX IV WIRING DIAGRAMS cont 50HE500891 F 50HE500751 J Fig 58 PremierLinktWiring Diagram ...