
39
START--UP, PREMIERLINK
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit must be electrically grounded in accordance
with local codes and NEC ANSI/NFPA 70 (American
National Standards Institute/National Fire Protection
Association.)
!
WARNING
Use the Carrier Communication Network (CCN) software
to start up and configure the PremierLink controller.
Changes can be made using the ComfortWORKS
r
software, ComfortVIEW
t
software, Network Service
Tool, System Pilot
t
device, or Touch Pilot
t
device. The
System Pilot and Touch Pilot are portable interface
devices that allow the user to change system set--up and
setpoints from a zone sensor or terminal control module.
During start--up, the Carrier software can also be used to
verify communication with PremierLink controller.
SET--UP INSTRUCTIONS
All set--up and set point configurations are factory set
and field--adjustable.
Refer to
PremierLink
t
Installation, Start--Up and
Configuration Instructions .
for specific operating
instructions for the controller. Have a copy of this
manual available at unit start--up.
NOTICE
Perform System Check--Out
1. Check all power and communication connections
ensuring the are properly connected and securely
tightened.
2. At the unit, check fan and system controls for proper
operation.
3. At the unit, check electrical system and connections
of any optional electric reheat coil.
4. Ensure all area around the unit is clear of construction
dirt and debris.
5. Ensure final filters are installed in the unit. Dust and
debris can adversely affect system operation.
6. Verify the PremierLink controls are properly
connected to the CCN bus.
START--UP, RTU--OPEN
SET--UP INSTRUCTIONS
Refer to the following manuals for additional
installation, wiring and troubleshooting information
for the RTU--OPEN Controller.:
“Controls, Start--up,
Operation and Troubleshooting Instructions,” “RTU
Open
Installation
and
Start--up
Guide” and
“RTU--Open Integration Guide”
. Have a copy of these
manuals available at unit start--up.
NOTICE
FASTENER TORQUE VALUES
Table 2 – Torque Values
Supply fan motor mounting
120
¦
12 in---lbs
13.6
¦
1.4 Nm
Supply fan motor adjustment plate
120
¦
12 in---lbs
13.6
¦
1.4 Nm
Motor pulley setscrew
72
¦
5 in---lbs
8.1
¦
0.6 Nm
Fan pulley setscrew
72
¦
5 in---lbs
8.1
¦
0.6 Nm
Blower wheel hub setscrew
72
¦
5 in---lbs
8.1
¦
0.6 Nm
Bearing locking collar setscrew
55 to60 in---lbs
6.2 to 6.8 Nm
Compressor mounting bolts
65 to75 in---lbs
7.3 to 7.9 Nm
Condenser fan motor mounting bolts
65 to75 in---lbs
7.3 to 7.9 Nm
Condenser fan motor mounting bolts
20
¦
2 in---lbs
2.3
¦
0.2 Nm
Condenser fan hub setscrew
84
¦
12 in---lbs
9.5
¦
1.4 Nm
50TC
Q
Содержание 50TCQD17-D24
Страница 36: ...36 C10818 Fig 51 RTU OPEN Control Module 50TCQ ...
Страница 46: ...46 APPENDIX IV WIRING DIAGRAMS cont C150373 Fig 52 50TCQ D17 Power Wiring Diagram 208 230 3 60 ...
Страница 47: ...47 APPENDIX IV WIRING DIAGRAMS cont C12399 Fig 53 50TCQ D17 Power Wiring Diagram 460 3 60 575 3 60 ...
Страница 48: ...48 APPENDIX IV WIRING DIAGRAMS cont C12686 Fig 54 50TCQ D24 Power Wiring Diagram 208 230 3 60 ...
Страница 49: ...49 APPENDIX IV WIRING DIAGRAMS cont C12401 Fig 55 50TCQ D24 Power Wiring Diagram 460 3 60 575 3 60 ...
Страница 51: ...51 APPENDIX IV WIRING DIAGRAMS cont C160005 Fig 57 RTU OPEN Control Diagram ...
Страница 52: ...52 APPENDIX IV WIRING DIAGRAMS cont 50HE500891 F 50HE500751 J Fig 58 PremierLinktWiring Diagram ...