UNIT
ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. [MM]
"A"
CENTER OF GRAVITY
IN. [MM]
lb
kg
X
Y
Z
50JS048
208/230-1-60, 208/230-3-60, 460-3-60
353
160.1
38.98 [990.2]
20.5 [520.7]
20.6 [523.8]
17.0 [431.8]
50JS060
208/230-1-60, 208/230-3-60, 460-3-60
418
189.6
38.98 [990.2]
19.5 [495.3]
19.8 [501.7]
17.0 [431.8]
50JX042
208/230-1-60, 208/230-3-60, 460-3-60
350
158.8
40.98 [1040.9]
21.0 [533.4]
20.5 [520.7]
16.6 [421.6]
50JX048
208/230-1-60, 208/230-3-60, 460-3-60
355
161.0
40.98 [1040.9]
20.0 [508.0]
21.3 [539.8]
18.0 [457.2]
50JX060
208/230-1-60, 208/230-3-60, 460-3-60
428
194.1
42.98 [1091.7]
21.0 [533.4]
20.0 [508.0]
17.6 [447.0]
Fig. 3—50JS048-060/50JX042-060 Unit Dimensions
C99006
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
INCHES [mm]
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
INCHES [mm]
TOP OF UNIT ...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
INCHES [mm]
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
3