12
PURON (R-410A) REFRIGERANT
This unit is designed for use with Puron
®
(R-410A) refrigerant.
Do not use any other refrigerant in this system.
Puron (R-410A) refrigerant is provided in pink (rose) colored
cylinders. These cylinders are available with and without dip
tubes; cylinders with dip tubes will have a label indicating this
feature. For a cylinder with a dip tube, place the cylinder in the
upright position (access valve at the top) when removing liquid
refrigerant for charging. For a cylinder without a dip tube, in
-
vert the cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R-410A) refrigerant is a blend, it is strongly
recommended that refrigerant always be removed from the cyl
-
inder as a liquid. Admit liquid refrigerant into the system in the
discharge line. If adding refrigerant into the suction line, use a
commercial metering/expansion device at the gage manifold;
remove liquid from the cylinder, pass it through the metering
device at the gage set and then pass it into the suction line as a
vapor. Do not remove Puron (R-410A) refrigerant from the
cylinder as a vapor.
Refrigerant Charge
Amount of refrigerant charge is listed on the unit’s nameplate.
Refer to
Carrier GTAC2-5 Charging, Recovery, Recycling and
Reclamation
training manual and the following procedures.
Unit panels must be in place when unit is operating during the
charging procedure.
NO CHARGE
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant.
LOW-CHARGE COOLING
Using Cooling Charging Charts, Fig. 19-24, vary refrigerant
until the conditions of the appropriate chart are met. Note the
charging charts are different from type normally used. Charts
are based on charging the units to the correct sub-cooling for
the various operating conditions. Accurate pressure gage and
temperature sensing device are required. Connect the pressure
gage to the service port on the liquid line. Mount the tempera
-
ture sensing device on the liquid line and insulate it so that out
-
door ambient temperature does not affect the reading. Indoor-
air cfm must be within the normal operating range of the unit.
USING COOLING CHARGING CHARTS
Refer to the charging charts to determine what the outdoor coil
leaving temperature should be. If the outdoor coil leaving tem
-
perature is above the curve add refrigerant. If outdoor coil
leaving temperature is below the curve, carefully recover some
of the charge. Recheck the outdoor coil leaving pressure as
charge is adjusted.
COOLING CHARGING CHARTS
Fig. 19 —
Cooling Charging Chart - 3 Ton
Fig. 20 —
Cooling Charging Chart - 3 Ton with Hot
Gas Reheat (Humidi-MiZer
®
System) Option
50JC SIZE DESIGNATION
NOMINAL TONS REFERENCE
04
3
05
4
06
5
Outdoor Coil
Leav
ing
Temperature, [°C/°F]
1034
1379
1723
2068
2413
2758
3102
3447
3792
4136
-6.6
4.5
15.6
26.7
37.8
48.9
60.0
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure, [psig/Kpa]
48TC004277 REV -
Add Charge if Above the Curve
3 Ton JC
R410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Cooling test
compressor speed to 4400)
Remove Charge if Below the
Curve
1034
1379
1723
2068
2413
2758
3102
3447
3792
4136
-6.6
4.5
15.6
26.7
37.8
48.9
60.0
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure, [psig/Kpa]
3 Ton JC Humidimizer
R410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Humidimizer test
compressor speed to 4400)
Remove Charge if Below the
Curve
48TC004274 REV -
Add Charge if Above the Curve
Outdoor Coil
Leav
ing
Temperature, [°C/°F]
Содержание 50JC04-06
Страница 54: ...54 APPENDIX D WIRING DIAGRAMS Fig B 50JC 04 06 Control Wiring Diagram...
Страница 55: ...55 APPENDIX D WIRING DIAGRAMS Fig C 50JC 04 06 Power Wiring Diagram 208 230 460 3 60...
Страница 56: ...56 APPENDIX D WIRING DIAGRAMS Fig D 50JC 04 06 Power Wiring Diagram 575 3 60...
Страница 57: ......