background image

13

Step 9 — Install External Condensate Trap

and Line

The unit has one

3

/

4

-in. condensate drain connection on

the end of the condensate pan and an alternate connection

on the bottom. See Fig. 17. Unit airflow configuration

does not determine which drain connection to use. Either

drain connection can be used with vertical or horizontal

applications.
When using the standard side drain connection, ensure the

red plug in the alternate bottom connection is tight. Do

this before setting the unit in place. The red drain pan can

be tightened with a

1

/

2

--in. square socket drive extension.

To use the alternate bottom drain connection, remove the

red drain plug from the bottom connection (use a

1

/

2

--in.

square socket drive extension) and install it in the side

drain connection.
The piping for the condensate drain and external trap can

be completed after the unit is in place. See Fig. 18.

DRAIN

(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARD

SIDE DRAIN

ALTERNATE

BOTTOM DRAIN

C08021

Fig. 17 -- Condensate Drain Pan (Side View)

NOTE:  Trap should be deep enough to offset maximum unit static

difference.  A 4” (102) trap is recommended

.

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE 

BASE RAIL

OPEN

VENT

TO ROOF

DRAIN

DRAIN PLUG

ROOF

CURB

SEE NOTE

2

˝

 (51) MIN

C08022

Fig. 18 -- Condensate Drain Piping Details

All units must have an external trap for condensate

drainage. Install a trap at least 4-in. (102 mm) deep and

protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away

from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do

not use a pipe size smaller than the unit connection

(

3

/

4

-in.).

Step 10 — Make Electrical Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Unit cabinet must have an uninterrupted, unbroken

electrical ground to minimize the possibility of

personal injury if an electrical fault should occur. This

ground may consist of electrical wire connected to

unit ground lug in control compartment, or conduit

approved for electrical ground when installed in

accordance with NEC; ANSI/NFPA 70, latest edition

(in Canada, Canadian Electrical Code CSA [Canadian

Standards Association] C22.1), and local electrical

codes.

!

WARNING

NOTE

: Check all factory and field electrical connections

for tightness. Field--supplied wiring shall conform with
the limitations of 63

_

F (33

_

C) rise.

Field Power Supply —

If equipped with optional Powered Convenience Outlet:

The power source leads to the convenience outlet’s

transformer primary are not factory connected. Installer

must connect these leads according to required operation

of the convenience outlet. If an always--energized

convenience outlet operation is desired, connect the

source leads to the line side of the unit--mounted

disconnect. (Check with local codes to ensure this method

is acceptable in your area.) If a de--energize via unit

disconnect switch operation of the convenience outlet is

desired, connect the source leads to the load side of the

unit disconnect. On a unit without a unit--mounted

disconnect, connect the source leads to compressor

contactor C and indoor fan contactor IFC pressure lugs

with unit field power leads.

Refer to Fig. 23 for power transformer connections and

the discussion on connecting the convenience outlet on

page 15.
Field power wires are connected to the unit at line--side

pressure lugs on compressor contactor C and indoor fan

contactor IFC (see wiring diagram label for control box

component arrangement) or at factory--installed option

non--fused disconnect switch. Max wire size is #2 AWG

(copper only). (See Fig. 19.)

NOTE

: TEST LEADS -- Unit may be equipped with

short leads (pigtails) on the field line connection points on

contactor C or optional disconnect switch. These leads are
for factory run--test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.

50H

T

Содержание 50HT-A07

Страница 1: ...gency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glasses and work gloves Use quenching cloths for brazing operations and have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions attached to t...

Страница 2: ...erate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on Puron refrigerant equipment WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Ware safety glasses and gloves when handling refrigerants Keep...

Страница 3: ...3 C10314 Fig 1 Dimensional Drawing 50HT ...

Страница 4: ...4 C10315 Fig 1 Unit Dimensional Drawing cont 50HT ...

Страница 5: ... of Unit Installation The support method used for this unit will dictate different sequences for the steps of unit installation For example on curb mounted units some accessories must be installed on the unit before the unit is placed on the curb Review the following for recommended sequences for installation steps Curb mounted installation Install curb Install field fabricated ductwork inside cur...

Страница 6: ...Ductwork must be attached to curb and not to the unit The accessory thru the base power and gas connection package must be installed before the unit is set on the roof curb If electric and control wiring is to be routed through the basepan attach the accessory thru the base service connections to the basepan in accordance with the accessory installation instructions NOTE The gasketing of the unit ...

Страница 7: ...7 C10316 Fig 3 Roof Curb Details 50HT ...

Страница 8: ...d ductwork Step 6 Rig and Place Unit Keep unit upright and do not drop Spreader bars must be used when lifting the unit even when the top crate remains in place Rollers may be used to move unit across a roof Level by using unit frame as a reference See Table 1 and Fig 5 for additional information Lifting holes are provided in base rails as shown in Fig5 Refer to rigging instructions on unit Before...

Страница 9: ...penings with counter flashing and mastic in accordance with applicable codes Do not cover or obscure visibility to the unit s informative data plate when insulating horizontal ductwork Step 8 Install Outside Air Hood Economizer Hood Removal and Setup Factory Option 1 The hood is shipped in knock down form and located in the return air compartment It is attached to the economizer using two plastic ...

Страница 10: ... Metal Tray Qty 2 C08639 Fig 10 Damper Assembly CO2 Sensor Factory Option 1 CO2 sensor is now a factory option and must be used with an economizer 2 The CO2 sensor is located on the lower side of the economizer See Fig 11 3 If additional installation and operating instructions are required for the CO2 sensor please reference in stallation instruction 48 50H P 20SI 50HT ...

Страница 11: ...OMPRESSOR ACCESS PANEL C06023 Fig 12 Typical Access Panel Locations SEAL STRIP HOOD TOP SEAL STRIP HOOD SIDE SCREEN RETAINER HOOD SIDE SCREEN TRACKS OUTDOOR AIR INLET SCREEN SEAL STRIP OUTDOOR AIR HOOD UNASSEMBLED HOOD SIDES AND TOP ASSEMBLED TRACKS FOR AIR INLET SCREEN HOOD SIDE HOOD TOP C07504 Fig 13 Outdoor Air Hood Details 50HT ...

Страница 12: ...ood sides to the hood top Use screws provided to attach the hood sides to the unit See Fig 15 3 Remove the shipping tape holding the economizer ba rometric relief damper in place 4 Insert the hood divider between the hood sides See Fig 15 and 16 Secure hood divider with 2 screws on each hood side The hood divider is also used as the bottom filter rack for the aluminum filter 5 Open the filter clip...

Страница 13: ... electrical fault should occur This ground may consist of electrical wire connected to unit ground lug in control compartment or conduit approved for electrical ground when installed in accordance with NEC ANSI NFPA 70 latest edition in Canada Canadian Electrical Code CSA Canadian Standards Association C22 1 and local electrical codes WARNING NOTE Check all factory and field electrical connections...

Страница 14: ...o the unit power terminal blocks and equipment ground Maximum wire size is 2 ga AWG per pole Provide a ground fault and short circuit over current protection device fuse or breaker per NEC Article 440 or local codes Refer to unit informative data plate for MOCP Maximum Over current Protection device size All field wiring must comply with the NEC and local requirements All units except 208 230 v un...

Страница 15: ...o exit the cover Check for full closing and latching RECEPTACLE NOT INCLUDED COVER WHILE IN USE WEATHERPROOF BASE PLATE FOR GFCI RECEPTACLE C09022 Fig 22 Weatherproof Cover Installation Non powered type This type requires the field installation of a general purpose 125 volt 15 A circuit powered from a source elsewhere in the building Observe national and local codes when selecting wire size fuse o...

Страница 16: ...ontrol wires to pass through the basepan The 1 2 in electrical bulkhead connector allows the high voltage power wires to pass through the basepan See Fig 25 LOW VOLTAGE CONDUIT CONNECTOR HIGH VOLTAGE CONDUIT CONNECTOR C08637 Fig 25 Thru Base Connection Fittings Check tightness of connector lock nuts before connecting electrical conduits Field supplied and field installed liquid tight conduit conne...

Страница 17: ...he thermostat and will require a junction box and splice at the thermostat Unit without thru base connection kit Pass the thermostat control wires through the hole provided in the corner post then feed the wires through the conduit built into the raceway of the corner post to the control box Pull the wires over to the terminal strip on the upper left corner of the Controls Connection Board See Fig...

Страница 18: ...kage part number value is 1 and a bare heater model number value is 0 DISCONNECT MOUNTING LOCATION UNIT BLOCK OFF PANEL OUTDOOR ACCESS PANEL INDOOR ACCESS PANEL C08133 Fig 28 Typical Access Panel Location 3 6 Ton DISCONNECT MOUNTING LOCATION EMT OR RIGID CONDUIT FIELD SUPPLIED SINGLE POINT BOX CENTER POST HEATER COVERS HEATER MOUNTING BRACKET HEATER MODULE LOCATION 2 HEATER MODULE LOCATION 1 SINGL...

Страница 19: ...on the heater bulkhead to the left of Heater 1 Connect the VIO lead from Heater 1 to terminal TB4 1 For 2 stage heating connect the VIO lead from Heater 2 to terminal TB4 2 For 1 stage heating with 2 heater modules connect the VIO lead from both Heater 1 and 2 to terminal TB4 1 Connect both BRN leads to terminal TB4 3 See Fig 32 ORN BRN Field Connections HR1 On Heater 1 in Position 1 HR2 On Heater...

Страница 20: ...nel etc Duct smoke sensor controller Fastener 2X Controller cover Conduit nuts supplied by installer Conduit support plate Cover gasket ordering option Conduit couplings supplied by installer Terminal block cover Controller housing and electronics Alarm Power Test reset switch Trouble C08208 Fig 33 Controller Assembly Duct smoke sensor See Detail A Exhaust tube Plug Sampling tube ordered separatel...

Страница 21: ... through the side plates of the economizer housing placing it across the return air opening on the unit basepan See Fig 37 The holes in the sampling tube face downward into the return air stream The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location This sensor is shipped in a flat mounting...

Страница 22: ...basepan Flexible Exhaust Tubes Screws Sample Tube C08126 Fig 39 Return Air Detector Shipping Position C08127 Fig 40 Return Air Sensor Operating Position Additional Application Data Refer to Catalog No HKRNKA 1XA for discussions on additional control features of these smoke detectors including multiple unit coordination 50HT ...

Страница 23: ... 0 21 1 108A00 109A00 25 5 23 4 LEGEND CO Convenient outlet DISC Disconnect FLA Full load amps IFM Indoor fan motor LRA Locked rotor amps MCA Minimum circuit amps MOCP Maximum over current protection PE Power exhaust UNPWRD CO Unpowered convenient outlet NOTES 1 In compliance with NEC requirements for multimotor and combina tion load equipment refer to NEC Articles 430 and 440 the overcurrent prot...

Страница 24: ...7310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 03 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50HT 01SI Replaces NEW 50HT ...

Отзывы: